Technical data
  • Mains connection with tolerance
    3~400 V ±10%, 50/60 Hz
  • Min. rated current I
    0.1 A
  • Max. nominal current I
    1.2 A
  • Output signal
    0-10V
  • Max. rated power per pump motor P2
    0.37 kW
  • Protection class
    IP54
  • Activation type
    Electronic (E)
  • Max. number of controllable pumps
    3
  • Control
    With frequency converter
  • Installation
    Wall-mounted installation
Operating data
  • Min. storage temperature
    -10 °C
  • Max. storage temperature
    50 °C
  • Min. ambient temperature
    0 °C
  • Max. ambient temperature
    40 °C
Materials
  • Material, housing
    1.0308
Information for order placements
  • Length L
    210 mm
  • Width W
    600 mm
  • Height H
    400 mm
  • Net weight, approx. m
    22.20 kg
  • Make
    Wilo
  • Product description
    CCe-HVAC system 3 x 0.37
  • Item no.
    2536648

Tender text

Wilo-Comfort Controller for digital, stepless power control of one-pump and multi-pump systems in heating, air-conditioning and ventilation applications. For infinitely variable, electronically controlled pumps or pumps with integrated frequency converter.

Completely electronic Comfort-Controller (CCe) in the sheet metal enclosure (colour: pebble grey), completely wired. Switchgear suitable for connection to 3/PE 400V/50 Hz three phase nets in accordance with IEC 60038 (other voltages on request), comprised of internal power supply, CPU, backup battery, analogue/digital modules, power pack with fuses, contactors and motor protection devices.

Fully graphics-capable touch screen with 3-colour backlight for indicating the operating status operation/ fault/ acknowledged fault, and supporting symbols and plain text for menu navigation in up to 27 languages, with European and Asiatic characters. 3 user levels, display and selection of menu language, passwords, operating parameters, elapsed time indicator (individual and total operating hours), history memory for operating and error messages with time stamp via real time clock, pump status and control variable actual value display, actual pressure display, diagram function, main switch, internal revision switch, Manual-0-Automatic for each pump. Operating mode selection Manual-0-Automatic for each pump via Touch panel, potential-free contacts for collective SBM/SSM run and fault signals (changeover contact) as well as ON/OFF connection for external systems (on-site potential-free NC contact), input 0/4-20 mA for external setpoint adjustment.

Overload protection via TWC, motor protection via motor protection switch, starting from 5.5 kW thermal overload relay.

Digital inputs for alarm signals, e.g. anti-frost protection (on-site potential-free NC contact), PID controller, automatic pump cycling and running time optimisation with multi-pump systems. Automatic, load-sensitive cut-in of 1 to n peak-load pump(s) depending on the following, programmable control variables:

  • Pressure - constant, p-c
  • Differential pressure - constant, dp-c
  • Differential pressure - variable, dp-v
  • Temperature setter, n= f(T)
  • Speed setter, n=f(analogue In)
  • Temperature control, T-c
  • Differential pressure - constant, dT
  • Differential pressure - variable, dT-v
  • Other types of control on request

Three setpoints are selectable by default. Automatic fault-actuated switchover on idle pump(s). Short test run of pump(s) during standstill, pilot pump function. Option for live-zero evaluation for conductivity test (sensor/setpoint input), select from:

  • Signal and all drives full load
  • Signal and system shut-down
  • Signal and one pump at speed adjustable on frequency converter

Extra charge for optional modules (installation in factory or later after technical clarification):

  • For connection to BMS systems in accordance with VDI 3814, via analogue/GSM modem, web server.
  • For connection to bus systems: Profibus, LON-Bus, CAN-Bus, Modbus RTU, Ethernet, others on request.
  • for external remote setpoint adjustment (differential pressure level) or manual control mode using 0/2 - 10 V signals.
  • Evaluation relay for PTC, individual operation and fault signals
  • Battery-backed power supply unit
  • Measurement of electrical parameters, such as voltage, current, effective power, power factor, etc.

Ordering example: Wilo CCe-HVAC 4x5.5 WM: Switchgear for 4 pumps with P2=5.5 kW in version as switch cabinet for wall fixation.

Scope of delivery

  • Switchgear
  • Installation and operating instructions
  • Wiring diagram
Technical data
  • Max. number of controllable pumps
    3
  • Phase
    3
  • Rated voltage U
    400 V
  • Min. rated current I
    0.1 A
  • Max. nominal current I
    1.2 A
  • Activation type
    Electronic (E)
  • Protection class
    IP54
  • Min. ambient temperature
    0 °C
  • Max. ambient temperature
    40 °C
  • Control
    With frequency converter
  • Installation
    Wall-mounted installation
  • Material, housing
    1.0308
  • Length L
    210 mm
  • Width W
    600 mm
  • Height H
    400 mm
  • Net weight, approx. m
    22.20 kg
  • Make
    Wilo
  • Item no.
    2536648

Ordering information

Information for order placements
  • Brand
    Wilo
  • Product description
    CCe-HVAC system 3 x 0.37
  • EAN number
    4048482236711
  • Article number
    2536648
  • Gross weight, approx. m
    23.9 kg
  • Net weight, approx. m
    22 kg
  • Overall length L
    210.0 mm
  • Height without packaging H
    400 mm
  • Colour
    grey
  • Packaging property
    Transport packaging
  • Packaging type
    Cardboard box
  • Number per layer
    1
  • Width without packaging L
    600.0 mm
  • Minimum order quantity
    1
  • Pieces per pallet
    1

Downloads

REACH regulation

Edition 2018-10
Page format 209.9 x 296.7 mm
Number of pages 4

PDF (581 kB)

Shkarko

PDF: CCe-HVAC system 3 x 0.37

Konfiguro

Përzgjedhja e faqes

Madhësia e faqes

Informacione fakultative

Mund të futni çdo informacion personal që dëshironi të shfaqni në kokë.

Shkarkime