Search
Contact
E-mail
Catalogue creation
My favorites
Product comparison
CIF-Module CANopen | Wilo
Abbildung ähnlich

CIF-Module CANopen

Article number: 2190369
Technical data
Technical data
Line type CAN bus cable, twisted in pairs, shielded, 1 x 2 x 0.5 mm² / 120 Ω characteristic impedance (line type B in accordance with TIA 485-A)
Line length 200 m
Spur line max. 10 m, in total max. 50 m
Terminal cross-section 1,5 mm²
Interface CAN in accordance with ISO 11898-2, optically insulated
Speed 125 kBit/s, constant
Format -
Protocol CANopen in accordance with CiA DS301 V 4.02
Profile -
Product data
Brand Wilo
Product description CIF-Module CANopen
Article number 2190369
EAN number 4048482802732
Colour Black
Minimum order quantity 1
Date of sales availability 2019-11-15
Packaging
Packaging type Cardboard box
Packaging property Sales packaging
Pieces per pallet 1
Number per layer 1
Dimension, weight
Length with packaging 200 mm
Length L 74 mm
Height with packaging 145 mm
Height H 34 mm
Width with packaging 145 mm
Width W 70 mm
Gross weight, approx. m 0.4 kg
Net weight, approx. m 0.1 kg
Tender text

Interface module as retrofittable plug-in module for extending the communication interfaces of the pump in accordance with various standards and protocol variants according to type key.

General functions

Serial, digital interface for connection to building automation for the transfer of data points as:

  • Control commands to the pump
  • Messages from the pump
  • Process values

Equipment

CAN 2.0A interface with CANopen protocol

Information about the download

http://www.wilo.de/automation (German)

http://www.wilo.com/automation (English)

Scope of delivery

  • CIF module
  • 2x threaded cable glands M16x1.5 (suitable for Stratos MAXO)
  • Installation and operating instructions

Bus lines (shielded!) must be provided by the customer

Technical data
Line type CAN bus cable, twisted in pairs, shielded, 1 x 2 x 0.5 mm² / 120 Ω characteristic impedance (line type B in accordance with TIA 485-A)
Line length 200 m
Spur line max. 10 m, in total max. 50 m
Terminal cross-section 1,5 mm²
Interface CAN in accordance with ISO 11898-2, optically insulated
Speed 125 kBit/s, constant
Format -
Protocol CANopen in accordance with CiA DS301 V 4.02
Profile -
Net weight, approx. 0.06 kg
Make Wilo
Item no. 2190369
Documents

Installation and operating instructions

Wilo-CIF-Module

Article Number 2193854
Edition 2020-11
Number of pages 56
PDF (2 MB)