Search
Contact
E-mail
Catalogue creation
My favorites
Product comparison
SC-FC-HVAC system 3x16A-FC-BM (star-delta-starting) | Wilo
Similar to figure

SC-FC-HVAC system 3x16A-FC-BM (star-delta-starting)

Article number: 2545472
Technical data
Technical data
Min. rated current I 13.1 A
Max. rated current per pump I 16 A
Protection class IP54
Activation type Star-Delta (YΔ)
Max. number of controllable pumps 3
Control With frequency converter
Installation Base-mounted installation
Materials
Material, housing Steel
Material Steel
Product data
Brand Wilo
Product description SC-FC-HVAC system 3x16A-FC-BM (star-delta-starting)
Article number 2545472
EAN number 4048482652771
Colour grey
Minimum order quantity 1
Date of sales availability 2010-01-01
Packaging
Packaging type Euro pallet
Packaging property Transport packaging
Pieces per pallet 1
Number per layer 1
Dimension, weight
Length with packaging 800 mm
Length L 400 mm
Height with packaging 2050 mm
Height H 1900 mm
Width with packaging 1200 mm
Width W 800 mm
Gross weight, approx. m 168 kg
Net weight, approx. m 163 kg
Tender text

Wilo-Smart Controller for digital, stepless power control of one-pump and multi-pump systems in heating, air-conditioning and ventilation applications.

SC-FC version: For the control of conventional fixed speed pumps via contactors (cascade connection), but control of a pump via frequency converters as a base-load pump, control of the peak-load pumps in cascade connection.

Hardware

Fully electronic Wilo-Smart Controller (SC) in steel sheeting enclosure (colour: pebble grey), comprised of internal power supply, microprocessor with “Soft-SPS”, analogue and digital inputs and outputs, LCD display (backlit) for displaying operating data, control parameters, operating states of the pumps, error messages and history memory. LEDs for display of system status (operation/fault), setting of operating parameters and acknowledgement of fault messages via Green Button Technology, lockable main switch, potential-free contacts for SBM/SSM collective operation and collective fault signals, contacts for external On/Off and 2nd setpoint, conductivity test in the sensor cable. Fuse protection of the pump motors and frequency converter: By motor protection switch in the direct starting version; by fusible cut-out in the star-delta-starting version in combination with thermal triggers. Contactors for switching on the pumps; star-delta-starting models include thermal triggering and a time relay for the star-delta combination. Frequency converter with sine filter for infinitely variable control of the base-load pump. Actual value output via analogue signal 0-10 V for external measurement/display option, 10 V corresponds to the sensor end value, input 0/4-20 mA for external setpoint adjustment. Automatic, load-sensitive cut-in from 1 to n peak-load pump(s) depending on the control variables

  • Pressure - constant, p-c
  • Differential pressure - constant, dp-c
  • Differential pressure - variable, dp-v
  • Temperature setter, n = f(Tx)
  • Speed setter, n=f(analogue In)
  • Differential pressure - constant, dT

Software functions

Fully automatic control for 1 to n pumps with frequency-controlled base-load pump by means of setpoint/actual value comparison, 4-20 mA sensor signal (conductivity test) for control variable actual values, menu navigation with symbols and menu numbers.

2 parameter sets can be selected: Easy Menu (setpoint & control mode) or expert Menu (operation and control parameters)

Can be selected by Customer Service with or without standby pump, automatic switching of an operating pump to the reserve pump in the event of a fault, operating mode of the pumps can be selected freely (manual, off, automatic), elapsed time indicator for each pump and system, switching cycle counter for each pump and system.

Monitoring of Max. and Min. values of the system with adjustable delay times and limits, external On/Off via contact for deactivation of the Automatic mode of the system, fault memory of the last 16 faults, setpoint switching of 2nd setpoint can be activated by contact, SBM and SSM logic reversal possible, parameters pre-set at the factory for simple commissioning.

Automatic, configurable pump cycling

  • Standard setting: Impulse - The base-load pump is cycled at each new demand, regardless of operating hours
  • Alternative: Pump cycling dependent on operating hours, cycling of the base-load pump after the specified operating hours

Automatic pump trial run (pump kick)

  • Can be activated
  • Time between two pump trial runs is freely programmable

Standards followed

  • Electrical Equipment of Machines EN 60204-1
  • Low-voltage switchgear combinations EN 61439-1 and 61439-2
  • EMC - Immunity for Industrial Environments EN 61000-6-2
  • EMC emitted interference for domestic accommodation, trade and commercial premises and small companies EN 61000-6-3 (for SC-FC only to 7.5 kW, over this EN 61000-6-4 emitted interference industrial premises)

Extra charge for optional modules for connection to BMS and bus systems (installation at the factory or subsequently after technical clarification):

  • H-0-A (Manual-Zero-Automatic) switch: preselection of the operating mode of each pump and manual operation in the event of a controller fault “Manual” (emergency/test mode available at mains power, motor protection available), “O” (pump switched off – cannot be switched on using the controller) and “Auto” (pump enabled for automatic mode via the controller).
  • Evaluation relay for PTC
  • Individual running and fault signals
  • Converter 0/2-10 V in 0/4 to 20 mA
  • Soft starter for peak-load pumps
  • Connection to BMS systems in accordance with VDI 3814
  • Bus systems: BACnet, LON, Modbus RTU

Scope of delivery

  • Switchgear
  • Installation and operating instructions
  • Wiring diagram
Technical data
Max. number of controllable pumps 3
Phases 3
Rated voltage U 380/400 V
Min. rated current I 13.1 A
Max. rated current per pump I 16 A
Activation type Star-Delta (YΔ)
Protection class IP54
Min. ambient temperature 0 °C
Max. ambient temperature 40 °C
Control With frequency converter
Installation Base-mounted installation
Material, housing Steel
Length L 400 mm
Width W 800 mm
Height H 1900 mm
Net weight, approx. 163 kg
Make Wilo
Item no. 2545472
Services

With Wilo as your partner, you can not only be sure of choosing high-quality product solutions, but also of benefiting from a comprehensive, worry-free package of well thought-out services. We collaborate to develop a service concept tailored to your individual needs; with our expertise and personal consultancy, we make sure that the operation of your systems is as energy-efficient, reliable and economical as possible. All the while our competent Wilo service technicians are ready to assist you with fast, reliable and on-time support.

Read more

Recommended services

Commissioning
Commissioning Switchgears
    
2219392

For perfect functioning of the pump(s) / system(s), it is recommended to have the commissioning carried out by the works' own WILO SE Customer Service Department. Optimum setting and efficient operation of the system are ensured as a result. Commissioning is comprised of the following points:

  • Commissioning of system(s) according to checklist
  • Parameterisation and setting of switchgear
  • Testing and adaptation of initial compressing of pressure tanks (filling up to 80 litres incl.)
  • Functional check of fitted system(s)
  • Practice-oriented operation instruction
  • Wilo commissioning protocol

The price for commissioning only applies to system(s) which have been installed in accordance with the installation and operating instructions and state-of-the-art technology. No costs for any materials which may be required are included.

Maintenance
Maintenance BASIC Switchgears
    
2219532

In order to ensure and guarantee operational reliability of the pumps/systems, it is recommended to have regular and DIN-compliant inspections and maintenance carried out by the works' own WILO SE Customer Service Department. The tasks are carried out in accordance with DIN 31051 / DIN EN 13306. The tasks comprise the following points:

  • Visual inspection of the pumps/systems
  • Mechanical check
  • Electrical check
  • Testing pressure vessels that may be on hand
  • Review and, if necessary, adjustment of the system parameters
  • Creating a maintenance protocol

Scheduling and organisation is performed by WILO. Other individual maintenance offers are possible on request.

Maintenance COMFORT Switchgears
    
2219494

In order to ensure and guarantee operational reliability of the pumps/systems, it is recommended to have regular and DIN-compliant inspections and maintenance carried out by the works' own WILO SE Customer Service Department. The tasks are carried out in accordance with DIN 31051 / DIN EN 13306. The tasks comprise the following points:

  • Visual inspection of the pumps/systems
  • Mechanical check
  • Electrical check
  • Testing and possible filling of pressure vessels that may be on hand
  • Review and, if necessary, adjustment of the system parameters
  • Creating a maintenance protocol
  • Consumable materials are included in the contract price
  • Elimination of payroll and travel expenses for deployments between maintenance intervals (during normal service hours)

Scheduling and organisation is performed by WILO. Other individual maintenance offers are possible on request.

Maintenance PREMIUM Switchgears
    
2219547

In order to ensure and guarantee operational reliability of the pumps/systems, it is recommended to have regular and DIN-compliant inspections and maintenance carried out by the works' own WILO SE Customer Service Department. The tasks are carried out in accordance with DIN 31051 / DIN EN 13306. The tasks comprise the following points:

  • Visual inspection of the pumps/systems
  • Mechanical check
  • Electrical check
  • Testing and possible filling of pressure vessels that may be on hand
  • Checking the system parameters
  • Creating a maintenance protocol
  • Consumable materials are included in the contract price
  • Elimination of payroll and travel expenses for deployments between maintenance intervals (during and outside normal service hours)
  • Software updates
  • Includes wearing parts

Scheduling and organisation is performed by WILO. Other individual maintenance offers are possible on request.

More suitable services

Wilo-Live Assistant
Wilo-Live Assistant Service
    
2216415

The Wilo-Live Assistant is a technical advisor at your side during pump service. By using the Wilo-Live Assistant, our expert advisers can support you in the boiler or equipment room via video transmission – live and in real time. You use your smartphone to show the installation set-up, while the Wilo expert follows everything on their screen. They can see the components as well as other details and can thus determine where the fault or breakdown originates. We prevent downtime and ensure operational reliability of your pumps and systems!

The Wilo-Live Assistant includes:

  • Interactive live support via video chat
  • Direct contact with an expert
  • Just-in-time solution to ensure maximum operational reliability of your pumps and systems
Supervision
Supervision Switchgears
    
2219324

Wilo supports during the concept phase to ensure quality work and cost efficiency. Our competent and qualified Wilo Service will support you with recommendations and technical advice throughout the entire project.

Supervision includes:

  • Regular on-site visits ensure the quality of information and advice
  • Technical consultancy, also available on site
  • Status report with recommendations after the visit
  • Comprehensive support from a Wilo expert
Repair
Repair Switchgears
    
2219613

Wilo Service draws on their competence and experience while consulting on site to decide whether the pump can actually be repaired on site or has to be sent in for a factory repair. Wilo also provides spare parts or a replacement pump to restore the operational reliability of the system.

Repair includes:

  • Verification and elimination of error causes by experienced Wilo experts
  • Non-binding estimate for repairs
  • Electric-hydraulic test run to ensure correct data regarding functionality, quality and performance of the pump or system
  • Coating of various pump or system components for an optimised efficiency factor
  • Use of genuine spare parts only
  • Documentation of the repair in the service report