Wilo-Control EC-Lift | Wilo
Your advantages
Wilo-Control EC-L

Your advantages

  • Reliable control and monitoring of up to three pumps, thanks to various monitoring and alarm functions
  • Flexible level measurement with level sensor, dynamic pressure bell or float switches
  • Increased plant safety when controlling pumps in explosive areas by extending the monitoring functionality in Ex-mode (hardware and software)
  • Easy operation with alphanumeric, symbol-based menu and operating button
  • Operating statuses can be viewed at any time. Greater ease of use via integration with remote monitoring systems via Modbus or optionally via GSM
  • Flexible installation. Universal power supply for single-phase current and three-phase current and a wide operating temperature range of -30 °C to + 60 °C
  • Universal use for water supply and sewage disposal – also for pumps in potentially explosive atmospheres
  • Advanced system control with individual operation and fault signal, optionally also in the event of power failure
  • Additional operational safety thanks to separate level recording for high water and dry-running protection
Series description

Design

Microcontroller-controlled switchgear for level-dependent control of up to three submersible pumps.

Equipment/function

Functions

  • Two different operating modes for a broad field of application:
    • "Drain" operating mode: For draining sewage chambers
    • "Fill" operating mode: For filling water tanks and rainwater storage tanks
  • Configurable overload protection
  • Thermal motor monitoring
  • Pump kick function
  • Adjustable follow-up time
  • Automatic pump alteration (for switchgear for 2 or 3 pumps)
  • Service life optimisation (for switchgear for 2 or 3 pumps)
  • Standby pump (for switchgear for 2 or 3 pumps)
  • Automatic fault-actuated switchover (for switchgear for 2 or 3 pumps)
  • Direction of rotation monitoring
  • High water alarm with forced switch-on of the connected pump(s)
  • Dry-running protection
  • Fault memory for 10 error messages including the type of fault
  • Operating mode "Ex" for loading presets for "Ex" applications

Equipment

  • Display of the current operating status and data, as well as faults via the LCD display and LEDs
  • Symbol-based menu navigation
  • Configuration of operating parameters and operation via operating button
  • Main switch (depending on version)
  • Remote access via ModBus
  • Integrated alarm buzzer
  • Explosion-proof version for direct connection of sensors within potentially explosive atmospheres

Typekey

Example:

Wilo-Control EC-L 1x12A-T34-DOL-WM-EMS-IPS

Control

Switchgear

EC

Easy control series

L

“Lift” version for water lifting applications

1

Number of pumps that can be connected

12 A

Maximum rated current per pump

T34

Mains connection:

  • M = 1~220–230 V, 50/60 Hz
  • T34 = 3~380–400 V, 50/60 Hz

DOL

Starting mode: Direct activation

WM

Installation type: Wall installation

EMS

Without main switch

IPS

Internal pressure sensor for direct connection of an immersion bell

Technical data

  • Mains connection: 1~220-230 V, 50/60 Hz or 3~380-400 V, 50/60 Hz
  • Max. rated power (P2) per pump: 4 kW
  • Maximum rated current IN per pump: 12 A
  • Activation type of connected pumps: Direct
  • Control voltage: 24 V DC
  • Ambient/operating temperature: -30…+50 °C
  • Storage temperature: -30…+60 °C
  • Max. relative humidity: 90 %, non-condensing
  • Housing material: Polycarbonate, UV-resistant
  • Protection class: IP54
  • Electrical safety: Pollution degree II

Construction

Microcontroller-controlled switchgear for level-dependent control of two or three submersible pumps with analogue or digital signal transmitters. Individual parameters are entered via symbol-based menu navigation and an operating button.

Inputs

  • 1x analogue precision input 4 – 20 mA for level control with level sensor to control 1 to 3 pumps
  • 2x (for 1 pump) or 3x (for 2 pumps) digital inputs for level control with float switch
  • 1x digital input for low water level with float switch (dry-running protection)
  • 1x digital input for high water signal with float switch (high water alarm)
  • 1x input for level control with an immersion bell (“IPS” version only)
  • 1x ... 3x inputs* for thermal winding monitoring with bimetallic temperature sensor. Connection of PTC sensors is not possible!
  • 1x ... 3x inputs* for connecting moisture sensors (e.g. motor compartment leakage or sealing chamber monitoring)
  • 1x digital input for External On/Off for remote activation and deactivation of automatic mode

Outputs

  • 1x potential-free contact for the collective run signal (SBM)
  • 1x potential-free contact for the collective fault signal (SSM)
  • 1x potential-free contact for the individual run signal (EBM) per pump
  • 1x potential-free contact for the individual fault signal (ESM) per pump
  • 1x analogue output 0-10 V for the output of the actual level value

*Depending on the number of pumps that can be connected.

Configuration

Caution! Signal transmitters are to be provided on-site. Switchgears are not protected against explosions and may only be used outside potentially explosive atmospheres. Signal transmitters within potentially explosive atmospheres must be connected through an intrinsically safe circuit, e.g. breakdown barrier or Ex cut-off relay. Direct connection of pumps within potentially explosive atmospheres is possible!

Documents

Installation and operating instructions

Wilo-Control EC-L

Article Number 2543252
Edition 2022-09
Number of pages 64
PDF (8 MB)

Installation and operating instructions (digital)

Wilo-Control EC-L

Article Number 2543252
Edition 2022-09
HTML (224 MB)
Product selection
Product descriptionDescriptionArticle number
EC-L-1x12A-MT34-DOL-WM

Microcontroller-controlled switchgear with LC display and symbol-based menu navigation for level-dependent control of a submersible pump by means of float switches or level sensor.

Notice! Printed installation and operating instructions have been enclosed with the product in the following languages: DE, EN, FR, PL, RU. All 28 language versions have been saved as PDF files on an enclosed USB pen drive. A notebook or tablet may be required for installing and commissioning.

2543210
EC-L-1x12A-MT34-DOL-WM-EMS

Microcontroller-controlled switchgear with LC display and symbol-based menu navigation for level-dependent control of a submersible pump by means of float switches or level sensor. WITHOUT main switch, mains isolator must be provided on-site!

Notice! Printed installation and operating instructions have been enclosed with the product in the following languages: DE, EN, FR, PL, RU. All 28 language versions have been saved as PDF files on an enclosed USB pen drive. A notebook or tablet may be required for installing and commissioning.

2543211
EC-L-1x12A-MT34-DOL-WM-EMS-IPS

Microcontroller-controlled switchgear with LC display, symbol-based menu navigation and integrated pressure transducer for level-dependent control of a submersible pump by means of float switches, level sensor or immersion bell. WITHOUT main switch, mains isolator must be provided on-site!

Notice! Printed installation and operating instructions have been enclosed with the product in the following languages: DE, EN, FR, PL, RU. All 28 language versions have been saved as PDF files on an enclosed USB pen drive. A notebook or tablet may be required for installing and commissioning.

2543212
EC-L-2x12A-MT34-DOL-WM

Microcontroller-controlled switchgear with LC display and symbol-based menu navigation for level-dependent control of submersible pumps by means of float switches or level sensor.

Notice! Printed installation and operating instructions have been enclosed with the product in the following languages: DE, EN, FR, PL, RU. All 28 language versions have been saved as PDF files on an enclosed USB pen drive. A notebook or tablet may be required for installing and commissioning.

2543220
EC-L-2x12A-MT34-DOL-WM-EMS

Microcontroller-controlled switchgear with LC display and symbol-based menu navigation for level-dependent control of submersible pumps by means of float switches or level sensor. WITHOUT main switch, mains isolator must be provided on-site!

Notice! Printed installation and operating instructions have been enclosed with the product in the following languages: DE, EN, FR, PL, RU. All 28 language versions have been saved as PDF files on an enclosed USB pen drive. A notebook or tablet may be required for installing and commissioning.

2543221
EC-L-2x12A-MT34-DOL-WM-EMS-IPS

Microcontroller-controlled switchgear with LC display, symbol-based menu navigation and integrated pressure transducer for level-dependent control of two submersible pumps by means of float switches, level sensor or immersion bell. WITHOUT main switch, mains isolator must be provided on-site!

Notice! Printed installation and operating instructions have been enclosed with the product in the following languages: DE, EN, FR, PL, RU. All 28 language versions have been saved as PDF files on an enclosed USB pen drive. A notebook or tablet may be required for installing and commissioning.

2543222
EC-L-3x12A-MT34-DOL-WM

Microcontroller-controlled switchgear with LCD display and symbol-based menu navigation for level-dependent control of three submersible pumps by means of a level sensor.

Notice! Printed installation and operating instructions have been enclosed with the product in the following languages: DE, EN, FR, PL, RU. All 28 language versions have been saved as PDF files on an enclosed USB pen drive. A notebook or tablet may be required for installing and commissioning.

2543230