FLA Compact-2 Helix V 1611 DS16

Data sheet

Hydraulic data
  • Maximum inlet pressure p inl
    6 bar
  • Maximum operating pressure PN
    16 bar
  • Min. fluid temperature T
    3 °C
  • Max. fluid temperature T
    40 °C
  • Min. ambient temperature T
    5 °C
  • Max. ambient temperature T
    40 °C
Motor data
  • Mains connection
    3~400 V, 50 Hz
  • Rated power P2
    7.50 kW
  • Rated current IN
    13.70 A
  • Power factor cos φ
    0.88
  • Rated speed n
    2900 rpm
  • Activation type
    Direct/Star-delta
  • Protection class motor
    IP55
  • Protection class control panel
    IP54
Materials
  • Pump housing
    1.4301, X5CrNi18-10
  • Impeller
    1.4307, X2CrNi18-9
  • Shaft
    1.4301, X5CrNi18-10
  • Gasket material
    EPDM
  • Pipework material
    1.4307, X2CrNi18-9
Installation dimensions
  • Pipe connection on the suction side DNs
    -
  • Pipe connection on the pressure side DNd
    R 2½
Information for order placements
  • Net weight, approx. m
    398 kg
  • Brand
    Wilo
  • Product description
    FLA Compact-2 Helix V 1611 DS16
  • Article number
    2540137

Tender text

Pressure boosting system as a fully automatic double pump compact unit (100% redundancy) for fire fighting purposes in accordance with DIN 14462, consisting of:

Break tank (540 l) with TZW approval for incoming water. Non self-priming, vertical stainless steel high-pressure multistage centrifugal pumps with three-phase AC motor. Shaft sealing by standard cartridge mechanical seal (Helix pumps). Diaphragm pressure vessel (capacity 8 l), integrated non-return valve, shut-off valves on suction and pressure side (secured against unauthorised operation), pressure switch and pressure gauge for automatic system control. Comes as standard with pump protection by means of minimum volume discharge via bypass circuit without auxiliary energy.

Switchgear FLA for fire extinguishing systems according to DIN 14462, designed in accordance with TÜV requirements.

Switchgear integrated in a sheet metal enclosure, painted in RAL 7035. With built-in motor protection only for signalling of faults. Motor protection is active in the test run.

Switch for Manual-Automatic mode Control of the pumps by pressure switch in automatic mode; expandable to up to 8 contacts (in series connection), e.g. External On/Off, limit switch etc. (more than 8 contacts on request). All pressure switch and limit switch signals are monitored for wire break and short-circuit.

System with programmable time switch for daily test run and programmable follow-up time. Dry-running protection relay, e.g. for connection of low water float switches from the WILO FLA break tanks or level electrodes, etc.; low water status only for signalling of faults. Protection against low water level is active in the test run.

With signal lamps for ready to run (green), pump ON (green), fault (red), operation started externally (white) and potential-free contacts for ready to run, pump ON and collective fault signal.

The system has been mounted on the base frame with wires and pipes are ready for connection.

The tank can be connected directly to the suction side of the pumps.

Additional text for systems with max. discharge pressure (inlet pressure + zero-delivery head) > 8.0 bar: The customer must take suitable measures to ensure that the flow pressure of 8 bar and the resting pressure of 12 bar are not exceeded at any fire hose reel.

Operating data
  • Fluid media
    Water
  • Max. delivery head H
    142.40
  • Maximum operating pressure PN
    16 bar
  • Maximum inlet pressure p inl
    6 bar
Motor data
  • Mains connection
    3~400 V, 50 Hz
  • Rated power P2
    7.50 kW
  • Rated current IN
    13.70 A
  • Power factor cos φ
    0.88
  • Rated speed n
    2900 rpm
  • Activation type
    Direct/Star-delta
  • Protection class motor
    IP55
  • Protection class control panel
    IP54
Materials
  • Pump housing
    1.4301, X5CrNi18-10
  • Impeller
    1.4307, X2CrNi18-9
  • Shaft
    1.4301, X5CrNi18-10
  • Shaft seal
    Q1BE3GG
  • Gasket material
    EPDM
  • Pipework material
    1.4307, X2CrNi18-9
Installation dimensions
  • Pipe connection on the suction side DNs
    -
  • Pipe connection on the pressure side DNd
    R 2½
Information for order placements
  • Brand
    Wilo
  • Product description
    FLA Compact-2 Helix V 1611 DS16
  • Net weight, approx. m
    398 kg
  • Article number
    2540137

Ordering information

Information for order placements
  • Brand
    Wilo
  • Product description
    FLA Compact-2 Helix V 1611 DS16
  • EAN number
    4048482427768
  • Article number
    2540137
  • Gross weight, approx. m
    466.0 kg
  • Net weight, approx. m
    398 kg
  • Overall length L
    2245.0 mm
  • Height without packaging H
    1790 mm
  • Colour
    Green/black/silver
  • Packaging property
    Transport packaging
  • Packaging type
    Special pallet
  • Number per layer
    1
  • Width without packaging L
    800.0 mm
  • Minimum order quantity
    1
  • Pieces per pallet
    1

Downloads

REACH regulation

Edition 2018-10
Page format 209.9 x 296.7 mm
Number of pages 4

PDF (581 kB)

Download

PDF: FLA Compact-2 Helix V 1611 DS16

Configure

Page selection

Format selection

Optional information

You can enter any personal information that you want to be displayed in the header.

Download