Fire SPK OPTI VF1604 WSM

Artikelnummer: 4239983
DKK 192.805,-
Pris (uden moms)
Tekniske data
Hydrauliske data
Maks. driftstryk PN 16 bar
Min. medietemperatur Tmin 4 °C
Maks. medietemperatur Tmax 25 °C
Omgivelsestemperatur min. Tmin 4 °C
Maks. omgivelsestemperatur Tmax 40 °C
Motordata
Nettilslutning 3~400 V, 50 Hz
Nominel motorydelse P2 4 kW
Mærkestrøm IN 7,4 A
Ydelse 0,87
Nominel hastighed n 2900 1/min
Tilkoblingstype Direkte online (DOL)
Kapslingsklasse motor IP55
Kapslingsklasse styreenhed IP54
Materialer
Pumpehus Rustfrit stål
Pumpehjul Rustfrit stål
Aksel Rustfrit stål
Materiale pakning EPDM
Materiale rørføring Stål
Installationsmål
På indsugningssiden rørtilslutning DNs DN 65
Rørtilslutning på tryksiden DNd DN 65
Priser
Pris (uden moms) DKK 192.805,-
Produktdata
Fabrikat Wilo
Produktbetegnelse Fire SPK OPTI VF1604 WSM
Artikelnummer 4239983
EAN nummer 4062679037233
Farve grøn/sølv
Min. bestillingsmængde 1
Til rådighed på markedet 2020-11-01
Emballage
Emballagetype Specialpalle
Emballageegenskab N/A
Antal pr. palle 1
Antal pr. lag 1
Dimensioner og vægt
Længdemål med emballage 1233 mm
Længde L 1033 mm
Højdemål med emballage 1510 mm
Højde H 1380 mm
Breddemål med emballage 878 mm
Bredde W 678 mm
Vægt brutto ca. m 186 kg
Vægt netto ca. m 156 kg
Udbudstekst

Pressure-boosting systems for firefighting in accordance with EN 16925 as fully automatic single pump compact unit for firefighting purposes consisting of: 2 electrical vertical multistage pumps, one main pump and one jockey pump, one switchgear equipped with firefighting dedicated controller for pumps and alarms and fixed on robust supports. Solid base frame with anti-avibration dampers, one circuit with double pressure switch, manometer, non-return valve, valve for main pump automatic start. Available in two versions, with direct suction connections, or with a suction manifold.

Control + alarm control E/J switchgear for fire-extinguishing systems in accordance with EN 16925 requirements.

Switchgear integrated in steel sheeting housing IP54.

Very high control quality and very simple operation due to the firefighting dedicated controller, with multi-languages screen, easy navigation with simple menu and push button plus immediate operation status with symbols. Communication-ready controller for supervising system operations.

System wired ready for connection and mounted on base frame with pipes.

Inlet pressure:

The maximum intake pressure must be taken into account when planning the system configuration (see Technical data).

The maximum permissible intake pressure is calculated from the maximum operating pressure of the system minus the maximum pump delivery head at Q = 0. For sprinkler installation following EN16925, the water pressure shall not exceed 12 bar.

Booster installed under suction condition.

It's necessary to install a priming tank for each main pump, with connection on the discharge pipe above the pump.

Volume flow

Up to 45 m3/h (12,5 l/s) system configuration per main pump.

Switchgear/control device for fire water supply systems

Wilo Control + alarm control E/J

Hardware:

Fully electronic central control unit and electro-mechanical components, built-in painted steel case, with protection class IP54, control and display and alarm devices on the front door.

Features and functions:

The controller design is suitable for the performance of each pump model. The device consists of several components:

Main switch: For switching the switchgear On/Off. (Unauthorised action in case of fire).

Display: Backlit graphic LCD display, built into the switch cabinet door for operating and display purposes. Displays the operating data and the receptive current operating statuses of pump and the controller. The menu selection as well as the parameter input are done by push buttons on the front door.

Microprocessor: Integrated PLC logic with thresholds, counters, alarms, status; 24 VAC auxiliary power supply; advanced I/O wired functions. The respective programming configuration is strictly dependent on system and sprinkler installation.

Indicators: Long-life indicator lights to show, power supply status, pump running, motor status, pressure switch on, automatic mode excluded, manual reset, alarm stop.

Buttons: Push button to manage manual start or manual stop, alarm reset and menu selection.

Fuse protection: Protection fuses, capable of carrying the start current for a period of no less than 20s.

Motor start: Direct start contactor.

Motor protection: Only for signaling.

Priming tank monitoring: By float switch to keep the water level at minimum 2/3 of the priming tank.

Power monitoring: Current, voltage, phases, cos phi and power of the pump.

Monitoring and controlling: Pump room temperature, working hours of the motor, pump status, pump statistics and starts, Jockey pump starts (if available), maintenance programme.

Fault message and acknowledgment: All alarm messages are displayed via LEDs or the graphic LCD. The LEDs color and alarm code must be acknowledged.

Software:

  • Factory programmed for fully automatic operation.
  • Voltage, pump current and pump power information.
  • Menu navigation with text on screen

Communication:

  • Isolated RS485 communication interface built in with Modbus RTU protocol.

Standards followed:

  • Fixed automatic sprinkler systems (EN16925) Electric motor pump part
  • Electrical Equipment of Machines (EN 60204-1)
  • Low-Voltage Switchgear and Controlgear Assemblies (EN 61439-1 and EN 61439-2)
  • EMC – Immunity for Industrial Environments (EN 61000-6-2)
  • EMC – Emission Standard for Residential, Commercial and Industrial (EN 61000-6-3)

Function description:

With the Wilo E control devices, electric motor pump and sensors for pump management or information level can be controlled. The switch gear, which is managed by means of a microprocessor, is used to control and regulate all necessary functions of a pressure boosting systems for firefighting in accordance with EN 16925, for testing or real sprinkling situation.

The operational logic for the fire extinguishing unit is based on the cascade calibration of the pressure switches for pump starting.

When a large quantity of water is requested, due to the opening of one or more circuits or due to a broken sprinkler, pressure decreases in the system. This drives the main pump to start through the switchgear controller.

Once the sprinkler circuit or the gate valve that supply the sprinkler heads is closed, the system reaches the maintaining pressure of the installation; it will be necessary to press the –Stop– buttons on front door to stop the pump.

Driftsdata
Løftehøjde maks. Hmax 52,0 m
medietemperatur T 4 °C
omgivelsestemperatur T 4 °C
Maks. driftstryk PN 16 bar
Motordata
Nettilslutning 3~400 V, 50 Hz
Nominel motorydelse P2 4 kW
Mærkestrøm IN 7,4 A
Ydelse 0,87
Nominel hastighed n 2900 1/min
Kapslingsklasse styreenhed IP54
Jockeypumpe
Mærkestrøm 2,7 A
Mærkekapacitet 1100 W
Pumpehjul jockeypumpe Rustfrit stål
Pumpehus jockeypumpe Støbejern
Aksel jockeypumpe Rustfrit stål
Statiske pakninger jockeypumpe EPDM
Installationsmål
På indsugningssiden rørtilslutning DNs DN 65
Rørtilslutning på tryksiden DNd DN 65
Informationer om ordreplaceringer
Fabrikat Wilo
Produktbetegnelse Fire SPK OPTI VF1604 WSM
Vægt netto ca. m 156 kg
Artikelnummer 4239983