COR-2 Helix VE 1006/ECe-WMS
Hydraulic data | |
---|---|
Max. operating pressure p | 16 bar |
Pipe connection on the discharge side DNd | R 2½ |
Pipe connection on the suction side DNs | R 2½ |
Number of stages | - |
Number of standby pumps | 0 |
Number of operating pumps | 2 |
Min. fluid temperature Tmin | 3 °C |
Max. fluid temperature Tmax | 50 °C |
Min. ambient temperature Tmin | 5 °C |
Max. ambient temperature Tmax | 40 °C |
Motor data (per motor) | |
---|---|
Mains connection | 3~380 V, 50/60 Hz |
Voltage tolerance | 400/50:+/-10%, 380/60:+/-10%, 460/60:+/-10% |
Insulation class | F |
Protection class | IP55 |
Rated power P2 | 4 kW |
Rated current IN | 7,9 A |
Motor efficiency 50% ηM 50% | 89 % |
Motor efficiency 75% ηM 75% | 89,5 % |
Motor efficiency 100% ηM 100% | 89,5 % |
Materials | |
---|---|
Pump housing | Stainless steel |
Impeller | Stainless steel |
Shaft | Stainless steel |
Mechanical seal | Q1BE3GG |
Gasket material | EPDM |
3~400 V ≤7.5 kW
Prices | |
---|---|
Price (excl. VAT) | on request |
Product data | |
---|---|
Brand | Wilo |
Product description | COR-2 Helix VE 1006/ECe-WMS |
Article number | 2864218 |
EAN number | - |
Colour | Green/black/silver |
Minimum order quantity | 1 |
Date of sales availability | 2013-03-01 |
Packaging | |
---|---|
Packaging type | One-way pallet |
Packaging property | Transport packaging |
Pieces per pallet | 1 |
Number per layer | 1 |
Dimension, weight | |
---|---|
Length with packaging | 1100 mm |
Length L | 600 mm |
Height with packaging | 1520 mm |
Height H | 1370 mm |
Width with packaging | 1050 mm |
Width W | 895 mm |
Gross weight, approx. m | 251 kg |
Net weight, approx. m | 236 kg |
Compact pressure-boosting system in accordance with DIN 1988 and DIN EN 806, for direct or indirect connection. Consisting of non-self-priming, vertical stainless-steel high-pressure multistage centrifugal pumps, connected in parallel with an integrated frequency converter. Ready for connection with stainless steel pipework, mounted on a base frame, including control device with all necessary measurement and adjustment equipment.
For fully automatic water supply and pressure boosting in residential, commercial and public buildings, hotels, hospitals, department stores and for industrial systems.
For pumping drinking water, hot water, process water, cooling water or other water meant for consumption, which does not affect the materials used, neither chemically nor mechanically, and does not contain any abrasive or long-fibre constituents.
Special features/product benefits
Favourable price/performance ratio as a result of the compact system and stainless steel high-pressure multistage centrifugal pumps from the Helix VE series with integrated air-cooled frequency converter
Remarkably wide control range
Integrated full motor protection with thermistor sensor (PTC)
Integrated low-water detection with automatic deactivation via the performance characteristics of the motor control electronics
Heavy-duty system which satisfies all the requirements of DIN 1988 (EN 806)
WRAS/ KTW/ ACS approval of the pumps for all parts that come in contact with the fluid (EPDM version)
High-efficiency pump hydraulics of the Helix V series in connection with IE3 standard motor, including 0.75 kW and larger (optional for smaller motor power)
Bidirectional mechanical seals in the pumps for easy maintenance
Flexible lantern design permits direct access to the mechanical seal
The spacer coupling enables the mechanical seal to be replaced without dismantling the motor (from 7.5 kW)
Hydraulics of entire system are pressure-loss optimised
Parts that come in contact with the fluid are corrosion-resistant
Comfort CC-FC control device with extended functions, PLC microcomputer and graphics-capable touchscreen, including frequency converter for continuously variable control of the base-load pump
Factory testing and presetting to optimum operating range
Equipment/function
2-3 Helix VE pumps per system
Continuous control of the pump by the integrated frequency converter
Parts that come into contact with fluid are corrosion-resistant
Base frame made of electrolytically galvanised steel, with height-adjustable vibration absorbers for insulation against structure-borne noise
Shut-off valve on the suction and discharge sides of each pump
Non-return valve on the discharge side of each pump
Diaphragm expansion tank, 8 l, PN10 on the discharge side
Pressure sensor, discharge side
Optional pressure gauge, suction side
Pressure gauge, discharge side
Optional protection against low water level
ECe switchgear in a sheet metal enclosure, IP54 protection class consisting of internal control voltage supply unit, microprocessor, analogue and digital input and output modules, for controlling electronic pumps with frequency converters
Operation/display
Fully electronic Easy-controller (ECe) with internal power supply, microprocessor, analogue and digital inputs and outputs for controlling and linking speed-controlled single pumps
Factory preset parameterisation for easy commissioning
Setpoint adjustment, operating parameters and acknowledgement of fault signals using Green Button Technology
LCD display (backlit) to view operating data, controller parameters, operating statuses of the pumps, error messages and history memory
LEDs for display of the system status (operation/fault)
Lockable main switch
Menu navigation with plain text and symbol representation
Locking the parameter settings
Operation with/without standby pump selectable
Elapsed time indicator for each pump
Elapsed time indicator for the whole system
Mains On/Off counter for the whole system
Start counter for each pump
Fault log with the last 10 faults; error display with code numbers
Quick access to key functions via the Easy Actions menu
Control
7 menu levels corresponding to the common menu structure for the EC-controller family; fully automatic control for 1 to 3 frequency-controlled pumps by setpoint/actual value comparison
Adjustable switch levels and delay times
Adjustable frequency range and start/stop ramps on the pumps
4 – 20 mA sensor signal (with wire break test) for control variable actual value
Automatic, load-sensitive cut-in of 1 to n peak-load pump(s) depending on the pressure - constant, p-c control variable
Adaptive PID controller facilitates pressure surge-free switching off/on of base-load and peak-load pumps
Operating mode of the pumps freely selectable (manual, off, automatic)
Automatic pump cycling:
The base-load pump is cycled at each new demand after system shutdowns, regardless of operating hours
Pump cycling dependent on operating hours, cycling of the base-load pump after six operating hours
Automatic pump test run (pump kick), alternatively: automatic pump test (pump kick) in standby mode with adjustable parameters
Test
Wire break test for the sensor cable
Selectable system behaviour in the event of a sensor fault
Protection of the pump mains power feed via circuit breaker (not for version without power element)
Automatic switchover to the standby pumps in the event of a fault on the operating pump
Zero-flow test for deactivation of the system if no water is extracted, the base-load pump is switched off at Q = 0
Protection against low water level via contact e.g. for float switch or pressure switch with adjustable follow-up time
Potential-free contacts for collective run signals (SBM) and collective fault signals (SSM) with selectable behaviour and external activation/deactivation of the system via contact
Individual run signal (EBM) and individual fault signal (ESM)
Interfaces
Potential-free contacts for EBM/ESM individual run and individual fault signals
Potential-free contacts for SBM/SSM collective run and collective fault signals
Protection against low water level via contact
External on/off via contact for deactivation of the system's automatic mode
ModBus RTU (RS485) communication interface
Optional accessories (factory installation or retrofitting after technical checks)
Recommended accessories (to be ordered separately)
Optional WMS low-water cut-out switchgear kit
Flexible connection pipes or compensators
Break tank for system separation
Diaphragm expansion tank
Threaded caps for systems with threaded joint tubing
Standards followed
Specifications for installations inside buildings conveying water for human consumption (TRWI) DIN 1988 (EN806)
Diaphragm pressure vessel/diaphragm expansion tank DIN 4807
Electronic equipment for use in power installations EN 50178
Electrical equipment of machines EN 60204-1
Safety of household and similar electrical appliances EN 60335-1
EN 60439-1/61439-1 – Low-voltage switchgears and equipment
EMC – Interference immunity for industrial environments EN 61000-6-2
EMC – Interference emission for residential, commercial and light-industrial environments (EN 61000-6-3)
Operating Data | |
---|---|
Number of pumps | 2 |
Fluid temperature T | 3 °C |
Ambient temperature T | 5 °C |
Maximum operating pressure PN | 16 bar |
Maximum inlet pressure p inl | 10 bar |
Motor data (per motor) | |
---|---|
Mains connection |
|
Rated power P2 | 4 kW |
Rated current IN | 7,9 A |
Rated speed n | 3500 1/min |
Motor efficiency class | IE4 |
Insulation class | F |
Protection class motor | IP55 |
Protection class switchgear | IP54 |
Materials | |
---|---|
Pump housing | Stainless steel |
Impeller | Stainless steel |
Shaft | Stainless steel |
Shaft seal | Q1BE3GG |
Gasket material | EPDM |
Pipework material | Stainless steel |
Installation dimensions | |
---|---|
Pipe connection on the suction side DNs | R 2½ |
Pipe connection on the discharge side DNd | R 2½ |
Ordering information | |
---|---|
Brand | Wilo |
Product description | COR-2 Helix VE 1006/ECe-WMS |
Net weight, approx. m | 236 kg |
Article number | 2864218 |