CO-2Helix V414/EC
Hydraulic data | |
---|---|
Maximum inlet pressure p inl | 6 bar |
Maximum operating pressure PN | 16 bar |
Pipe connection on the discharge side DNd | R 1½ |
Pipe connection on the suction side DNs | R 1½ |
Number of pumps | 2 |
Number of standby pumps | 1 |
Number of operating pumps | 1 |
Min. fluid temperature Tmin | 3 °C |
Max. fluid temperature Tmax | 50 °C |
Min. ambient temperature Tmin | 5 °C |
Max. ambient temperature Tmax | 40 °C |
Motor data (per motor) | |
---|---|
Mains connection | 3~400 V, 50 Hz |
Voltage tolerance | ±10 % |
Rated power P2 | 2.2 kW |
Rated current IN | 4.3 A |
Rated speed n | 2900 1/min |
Insulation class | F |
Protection class | IP55 |
Motor efficiency 50% ηM 50% | 84.8 % |
Motor efficiency 75% ηM 75% | 86.2 % |
Motor efficiency 100% ηM 100% | 85.9 % |
Materials | |
---|---|
Pipework material | Stainless steel |
Prices | |
---|---|
Price (excl. VAT) | on request |
Product data | |
---|---|
Brand | Wilo |
Product description | CO-2Helix V414/EC |
Article number | 4261937 |
EAN number | 4062679320342 |
Colour | Green/black/silver |
Minimum order quantity | 1 |
Date of sales availability | 2023-05-16 |
Packaging | |
---|---|
Packaging type | Special pallet |
Packaging property | Transport packaging |
Pieces per pallet | 1 |
Number per layer | 1 |
Dimension, weight | |
---|---|
Length with packaging | 1050 mm |
Length L | 600 mm |
Height with packaging | 1485 mm |
Height H | 1360 mm |
Width with packaging | 800 mm |
Width W | 580 mm |
Gross weight, approx. m | 152 kg |
Net weight, approx. m | 126 kg |
Compact pressure-boosting system in accordance with DIN 1988 and DIN EN 806, for direct or indirect connection. Consisting of non-self-priming, vertically mounted, stainless steel high-pressure multistage centrifugal pumps connected in parallel – glanded version. Ready for connection with stainless steel pipework, mounted on a base frame, including control device with all necessary measurement and adjustment equipment.
For fully automatic water supply and pressure boosting in residential¬, commercial¬ and public buildings, hotels, hospitals, department stores and for industrial systems.
For pumping drinking water, process water, cooling water, firefighting water (apart from fire-fighting systems in accordance with DIN 14462 and with the approval of the local fire protection authorities) or other types of industrial water that do not corrode the materials either chemically or mechanically and do not contain abrasive or long-fibre constituents.
Special features/product benefits
- Heavy-duty system which satisfies all the requirements of DIN 1988 (EN 806)
- WRAS/ACS approval of the pumps for all parts that come in contact with the fluid (EPDM version)
- High-efficiency pump hydraulics of the Helix V series in conjunction with IE3 IEC standard motors
- Bidirectional mechanical seals in the pumps for easy maintenance
- Flexible lantern design permits direct access to the mechanical seal (from 15 kW)
- The spacer coupling enables the mechanical seal to be replaced without dismantling the motor (from 15 kW)
- Hydraulics of entire system are pressure-loss optimised
- Parts that come in contact with the fluid are corrosion-resistant
- Easy commissioning and operation with the Easy Controller
- Factory testing and presetting to optimum working range
Equipment/function
- Stainless steel high-pressure multistage centrifugal pumps of the Helix V series
- Base frame made of electrolytically galvanised steel, with height-adjustable oscillation absorbers for insulation against structure-borne noise
- Shut-off device on the suction and discharge sides of each pump
- Non-return valve on the discharge side of each pump
- Pressure sensor (4 – 20 mA), discharge side
- Pressure gauge, discharge side
- Automatic pump control by means of a fully electronic
- EC-control with IP54 plastic housing, consisting of an internal power supply unit, microprocessor, analogue and digital input and output modules
Operation/display
- Fully electronic Easy Controller with internal power supply unit, microprocessor, analogue and digital inputs and outputs for controlling and linking constant speed single pumps
- Configuration of operating parameters via potentiometer
- Configuration of pump operating mode and acknowledgement of fault signals via H-0-A switch
- LED display (3x7 segments, alphanumeric) to indicate the set pressure, controller parameters and error messages
- LEDs for display of the system status (mains voltage/operation/fault/low water)
- Lockable main switch
Control
- Fully automatic control for a fixed speed pumps by means of setpoint/actual value comparison
- 4 – 20 mA sensor signal (with conductivity test) for control variable actual value
- Operating mode of the pumps freely selectable (manual, off, automatic)
- Automatic pump test run (pump kick):
- Can be activated by means of DIP switch
- Time between two pump test runs is six hours
- Zero-flow cut-off over pressure and time
- H-0-A (manual-zero-automatic) switch: preselection of the operating mode of the pump and manual operation in the event of a controller fault – Manual (emergency/test mode available at mains power, motor protection available, automatic resetting), 0 (pump switched off – cannot be switched on via the controller) and Auto (pump enabled for automatic mode via the controller)
Monitoring
- Conductivity test of the sensor cable
- Phase failure monitoring
- Motor current monitoring via converter in devices for direct start
- Protection of the pump mains power feeds in devices for direct starting is provided via circuit breakers
- Monitoring of maximum and minimum system values with adjustable time delays and limits
- Protection against low water level via contact e.g. for float switch or pressure switch
Interfaces
- Potential-free contact for collective fault signal (SSM)
- External on/off via contact for deactivation of the system automatic mode (function can be activated via DIP switch)
Optional accessories (factory installation or retrofitting after technical checks)
- Manual-0-Automatic switch Preselection of the operating mode of each pump and manual operation in the event of a controller fault – “Manual” (emergency/test mode available at mains power, motor protection available), “0” (pump switched off – cannot be switched on using the controller) and “Auto” (pump enabled for automatic mode via the controller)
- Evaluation relay for PTC motor protection
- Individual operation and fault signal, low-water signal
- Signal converter for 0/2 –10 V to 0/4 – 20 mA
- Soft starter for peak-load pumps
- Connection to BMS systems in accordance with VDI 3814
Recommended accessories (to be ordered separately)
- Optional WMS low-water cut-out switchgear kit
- Flexible connection pipes or compensators
- Break tank for system separation
- Diaphragm pressure vessel
- Threaded caps for systems with threaded joint tubing
Standards followed
- Codes of practice for drinking water installations – DIN 1988 (EN 806)
- Diaphragm pressure vessel/diaphragm expansion tank DIN 4807
- Electronic equipment for use in power installations EN 50178
- Electrical equipment of machines EN 60204-1
- Safety of household and similar electrical appliances EN 60335-1
- Low-voltage switchgear and controlgear assemblies EN 60439-1/61439-1
- EMC – Interference immunity for industrial environments EN 61000-6-2
- EMC – Interference emission for residential, commercial and light-industrial environments (EN 61000-6-3)
Operating Data | |
---|---|
Number of pumps | 2 |
Fluid temperature T | 3 °C |
Ambient temperature T | 5 °C |
Maximum operating pressure PN | 16 bar |
Maximum inlet pressure p inl | 6 bar |
Motor data (per motor) | |
---|---|
Mains connection | 3~400 V, 50 Hz |
Rated power P2 | 2.2 kW |
Rated current IN | 4.3 A |
Rated speed n | 2900 1/min |
Motor efficiency class | IE3 |
Insulation class | F |
Protection class motor | IP55 |
Protection class switchgear | IP54 |
Materials | |
---|---|
Shaft seal | BQ1EGG |
Pipework material | Stainless steel |
Installation dimensions | |
---|---|
Pipe connection on the suction side DNs | R 1½ |
Pipe connection on the discharge side DNd | R 1½ |
Ordering information | |
---|---|
Brand | Wilo |
Product description | CO-2Helix V414/EC |
Net weight, approx. m | 126 kg |
Article number | 4261937 |