DDG (4-20mA)

Series description

Construction

-

Equipment/function

The differential pressure sensor (DDG) converts a hydrostatic differential pressure, generated for example by a pump in a pipe, into an electrical signal. This signal can be analysed by a control unit, e.g. a Wilo control device, in order to monitor the system requirements and adjust them using the pump.

The differential pressure sensor is connected to the pressure measurement sites by copper pipes of Ød = 6 mm. The connections are configured as cutting ring unions.

The sensor can be mounted using the fixing elements provided.

Technical data

Technical data

Maximum operating voltage: 15 – 30 V DC

Rated voltage: 24 V DC

Current output: 4 – 20 mA

Protection class: IP55

Pressure measurement range:

DDG 10: 0 to 1.0 bar

DDG 20: 0 to 2.0 bar

DDG 40: 0 to 4.0 bar

DDG 60: 0 to 6.0 bar

DDG 100: 0 to 10.0 bar

Temperatures

  • Fluid temperature: -20 °C to +80 °C
  • Ambient temperature: 0 °C to +70 °C
  • Storage temperature: -30 °C to +80 °C

Pressure rating

  • Overpressure, static: 21 bar
  • Overpressure, dynamic: 2.5 x pmax

Pressure peaks above this must be avoided mechanically.

Fields of application

Suitable for all common types of fluids such as heating water, water with viscous component, cooling water or cold water.

This sensor is not suitable for fluids containing oil.

Series

DDG (4-20mA)

Downloads

REACH regulation

Edition 2019-10
Page format 209.9 x 296.7 mm
Number of pages 4

PDF (853 kB)

Download

Product

PDF: DDG (4-20mA)

Configure

Page selection

Format selection

Optional information

You can enter any personal information that you want to be displayed in the header.

Download