Wilo-FLA-2
Wilo-FLA 2 Helix V 3604
Your advantages
- Sturdy system with 2 Helix FIRST V or MVI stainless steel high-pressure multistage centrifugal pumps, in accordance with DIN 1988 and DIN 14462
- Absolute operational reliability for 2-pump systems with 100 % redundancy
- Easy adjustment and operational reliability due to the FLA control unit
- Pre-set throttle valve on the discharge side of the pump to protect the pump at low volume flows
FLA
Design
Pressure-boosting system for fire-fighting systems with indirect connection in accordance with DIN 14462:2012.
With 2 vertical stainless steel high-pressure multistage centrifugal pumps in glanded version
Application
Fully automatic water supply for fire-fighting systems with wall hydrants of the type "F" in domestic, commercial and public buildings, hotels, hospitals, shopping centres and also offices and industrial buildings
Equipment/function
- 2 Helix FIRST V 16, 22, 36, 52 or MVI 70 series pumps, equipped with IE2 motors
- Automatic pump control via FLA control unit
- Components that come in contact with the fluid are corrosion-resistant
- Base frame made of galvanised steel, with height-adjustable vibration absorbers for insulation against structure-borne noise
- Pipework made of 1.4301 stainless steel
- Gear-operated shut-off ball cock or annular shut-off valve on the suction and pressure side of every pump
- Non-return valve, pressure side
- Throttle valve of stainless steel 1.4571 on the suction side of every pump
- Pressure switch, on the pressure side
- Pressure gauge, on the pressure side
- Diaphragm pressure vessel 8 l, PN 16, on the pressure side
- Accessories: Atmospherically ventilated break tank in accordance with DIN 14462:2012 with free exhaust in accordance with EN 13077, type AB in accordance with DIN EN 1717
Typekey
Example: | Wilo- FLA – 2 Helix V 2204 PN10 |
FLA | Fire extinguishing system |
2 | Number of pumps |
Helix V | Pump series |
22 | Rated volume flow [m3/h] |
04 | Number of pump stages |
PN10 | Pressure control up to 10 bar (pump type-dependent) |
Technical data
- Mains connection 3~400 V, 50 Hz
- Max. fluid temperature 50 °C
- Operating pressure 10 or 16 bar
- Inlet pressure from break tank < 1 bar
- Nominal connection diameter on pressure side R 2" - DN 125
- Nominal connection diameter on suction side Rp 2"- DN 125
- Operating unit protection class IP 54
Materials
- Impellers, diffusers, stage housing made of stainless steel 1.4307
- Pump housing made of EN-GJL-250, cataphoretically coated
- Shaft of stainless steel 1.4057
- 1.4404 shaft protection sleeve
- O-Ring gaskets made of EPDM (FKM gasket on request)
- Pipework made of 1.4301 stainless steel
Construction
- Base frame: made of electrolytically galvanised steel and provided with height-adjustable vibration absorbers for comprehensive insulation against structure-borne noise; other versions on request
- Pipework: complete pipework made of stainless steel 1.4301, suitable for the connection of all conventional piping materials; the pipework is dimensioned according to the overall hydraulic performance of the FLA pressure boosting system
- Pumps: Helix FIRST V 16, 22, 36, 52 and MVI 70 series pumps; all pump components in contact with fluid are made of stainless steel/EN-GJL-250, with cataphoretic coating. For more information about the pump, please refer to the catalogue section "High-pressure multistage centrifugal pumps"
- Valves: For each pump, the non-return valve has a 1.4571 needle-type throttle for returning the bypass volume flow to the break tank. All throttle valves and shut-off devices are sealed and protected against unauthorised adjustment. The pumps are equipped with an automatic air vent valve on the top of the hydraulics.
- Diaphragm pressure vessel: 8 l/PN 16 arranged on the discharge side. For testing and inspection purposes, equipped with a special throughflow fitting that enables the diaphragm pressure vessel to be shut-off and drained
- Pressure switch: A pressure switch arranged on the discharge side, for activation of the central FLA controller
- Pressure indication: Pressure gauge (ø 63 mm) on the discharge side; additional digital display of operating pressure and setting parameters in the FLA controller
- Control device/controller: The system is equipped with a specific FLA controller as standard
Scope of delivery
- Factory-mounted, connection-ready pressure boosting system checked for functionality and impermeability
- Packaging