Article number : 2198927
| Technical data | |
|---|---|
| Inlet connection | G ¾ |
| Outlet connection | G ¾ |
| Port-to-port length l0 | 710 mm |
| Min. refill pressure | 2 bar |
| Max. refill pressure | 8 bar |
| Maximum allowed limit of glycol in % | 30 % |
| Break tank volume V | 100 l |
| Min. operating pressure | 2 bar |
| Max. operating pressure PN | 10 bar |
| Min. fluid temperature | -10 °C |
| Max. fluid temperature | 70 °C |
| Max. ambient temperature | 45 °C |
| Min. ambient temperature | 3 °C |
| Max. working pressure | 8 |
| Min. working pressure | 3 |
| Motor data | |
|---|---|
| Max. contact capacity | 1~ 230V 50 Hz 3A |
| Rated power P2 | 2,2 W |
| Interface | RS485 (TIA-485A), optically insulated |
| Mains frequency f | 50 Hz |
| Phases | 1 |
| Rated voltage U | 230 V |
| Voltage tolerance | ±10 % |
| Rated current IN | 10,6 A |
| Sound-pressure level | 55 dB |
| Protection class | IP54 |
Wilo-Tagus Degassing
| Dimensions A | 710,0 mm |
| Dimensions B | 1270,0 mm |
| Dimensions C | 525,0 mm |
| Product data | |
|---|---|
| Brand | Wilo |
| Product description | Degassing and top-up automat Tagus vac 30 |
| Article number | 2198927 |
| EAN number | 4048482838441 |
| Colour | White |
| Minimum order quantity | 1 |
| Date of sales availability | 2018-04-09 |
| Packaging | |
|---|---|
| Packaging type | Euro pallet |
| Packaging property | Transport packaging |
| Pieces per pallet | 1 |
| Number per layer | 1 |
| Dimension, weight | |
|---|---|
| Length with packaging | 600 mm |
| Length L | 525 mm |
| Height with packaging | 1435 mm |
| Height H | 1270 mm |
| Width with packaging | 750 mm |
| Width W | 710 mm |
| Gross weight, approx. m | 75 kg |
| Net weight, approx. m | 60 kg |
For active degassing and automatic topping up of closed heating and cooling systems.
The Tagus vac is a pressure step degasser that makes use of vacuum for highly efficient degassing of closed systems. Moreover, the Tagus vac ensures automatic topping-up of the system after the top-up water has been degassed.
Can be easily used in combination with a diaphragm pressure expansion vessel or pressure expansion automat.
Special features/product advantages
- Effective deaeration and top-up for a high fluid quality by central degassing for both system and top-up water
- Self-regulated refilling with degassed water thanks to the turbo operation mode and the external refill contact (230V)
- Assembled and ready for connection.
- Clear operation via the intuitive display.
- Active degassing by patented PALL-Ring technology for high performance de-aeration
- Integrated glanded pump of the MHI series
| Technical data | |
|---|---|
| Installation | Vertical |
| Max. operating pressure PN | 10 bar |
| Max. working pressure | 8 |
| Min. working pressure | 3 |
| Min. refill pressure | 2 bar |
| Max. refill pressure | 8 bar |
| Min. fluid temperature T | -10 °C |
| Max. fluid temperature T | 70 °C |
| Min. ambient temperature | 3 °C |
| Max. ambient temperature | 45 °C |
| Maximum allowed limit of glycol in % | 30 % |
| Motor data | |
|---|---|
| Mains frequency f | 50 Hz |
| Phases | 1 |
| Rated voltage U | 230 V |
| Voltage tolerance | ±10 % |
| Rated current IN | 10,6 A |
| Protection class | IP54 |
| Sound-pressure level | 55 dB |
| Ordering information | |
|---|---|
| EAN number | 4048482838441 |
| Item no. | 2198927 |
| Make | Wilo |
| Net weight, approx. | 60 kg |