VeroLine-IP-E 80/115-2,2/2 | Wilo
Similar to figure

VeroLine-IP-E 80/115-2,2/2

Technical data
Tender text

Glanded centrifugal pump with in-line design for pipe installation with built-in frequency converter for electronic control for constant or variable differential pressure (dp-c/dp-v). Three-phase AC motor with frequency converter.

Design:

  • Single-stage low-pressure centrifugal pump with one-piece shaft
  • Spiral housing, in-line design
  • PN 16 flange – drilled according to EN 1092-2
  • Pressure measuring connections (R 1/8) for mounted differential pressure sensor (version ...-R1 without differential pressure sensor)
  • Pump housing and motor flange with cataphoretic coating as standard
  • Mechanical seal for water feed up to T=120 °C. A glycol admixture of 20 to 40% by vol. is permitted up to Tmax = +40 °C. Other mechanical seals or other fluids/temperatures on request.

Accessories:

  • Mounting brackets for fixing to the foundation
  • IR-Monitor
  • IR-Stick
  • IF module PLR
  • IF module LON
  • IF module Modbus
  • IF module BACnet
  • IF module CAN
  • Control systems VR-HVAC/CCe-HVAC/SCe-HVAC
  • Differential pressure sensor (DDG) sets 0-10 V for pumps in version ...-R1

Standard equipment:

  • One-button manual operation level for:
    • Pump On/Off
    • Setpoint and speed adjustment
    • Selecting the control mode: Δp-c (constant differential pressure), Δp-v (variable differential pressure), PID controller, n-constant (constant speed)
    • Selection of operating mode in dual pump operation (main/standby operation, parallel operation)
    • Configuration of operating parameters
    • Fault acknowledgement
  • Pump display for displaying:
    • Control mode
    • Setpoint (e.g. differential pressure or speed)
    • Error and warning messages
    • Actual values (e.g. power consumption, actual value of the sensor)
    • Operating data (e.g. operating hours, energy consumption)
    • Status data (e.g. status of SSM and SBM relay)
    • Device data (e.g. pump name)

Additional functions:

  • Interfaces: Control input "Overriding Off", "External pump cycling" (effective only in dual pump operation), analogue input 0–10 V, 2–10 V, 0–20 mA, 4–20 mA for control mode (DDC) or for remote setpoint adjustment, analogue input 0–10 V, 2–10 V, 0–20 mA, 4–20 mA for actual value signal of the pressure sensor, Infrared interface for wireless communication with the operating and service unit Wilo-IR-Stick/IR-Monitor, plug-in position for Wilo IF-Module Modbus, BACnet, CAN, PLR, LON for connecting to the building automation, configurable, potential-free fault and operating/ready message, interface for dual pump communication
  • Adjustable time interval for pump cycling (in dual pump mode)
  • Integrated full motor protection
  • Different operating modes for heating mode (HV) or air-conditioning mode (AC)
  • Access disable
  • Different operation levels: Standard / Service
Operating data
Fluid media
Water
Fluid temperature T
-20 °C
Ambient temperature T
0 °C
Maximum operating pressure PN
10 bar
Minimum efficiency index (MEI)
0.4
Motor data
Motor efficiency class
IE4
Interference emission
EN 61800-3
Interference immunity
EN 61800-3
Mains connection
3~380 V, 50/60 Hz
Rated power P2
2200 W
Max. speed nmax
2940 1/min
Rated current IN
6.6 A
Insulation class
F
Protection class motor
IP55
Motor protection
Materials
Pump housing
Cast iron
Impeller
PPE/PS-GF30
Shaft
Stainless steel
Shaft seal
AQ1EGG
Lantern
Cast iron
Installation dimensions
Pipe connection on the suction side DNs
DN 80
Pipe connection on the discharge side DNd
DN 80
Port-to-port length L0
360 mm
Ordering information
Brand
Wilo
Product description
VeroLine-IP-E 80/115-2,2/2
Net weight, approx. m
47 kg
Article number
2158828
Downloads

Installation and operating instructions

Wilo-VeroLine-IP-E Wilo-VeroTwin-DP-E

Article Number 2144990
Edition 2017-11
Page format 209.9 x 297.0 mm
Number of pages 236
PDF (21 MB)

Certificate REACH (Documents)

REACH regulation

Edition 2020-08
Page format 209.9 x 297.0 mm
Number of pages 2
PDF (158 KB)
BIM/CAD

IP-E80/115-2,2/2

DWG (1 MB)

IP-E80/115-2,2/2

STP (2 MB)

IP-E80/115-2,2/2

DWG (18 KB)

IP-E80/115-2,2/2

DWG (19 KB)

IP-E80/115-2,2/2

DWG (22 KB)