Search
Contact
E-mail
Catalogue creation
My favorites
Product comparison
Break tank for fire extinguishing systems (rectangular version), 1000 L | Wilo
Similar to figure

Break tank for fire extinguishing systems (rectangular version), 1000 L

Article number: 2528258
Technical data
Technical data
Evacuation connection G 1
Inlet connection 2x Ø60mm (2“)
Outlet connection DN 100
Connection standard DIN EN 1092-1
Overflow 1 x HT 125
Break tank volume V 1000 l
tank contents -
Min. volume flow V 26.7 m³/h
Max. volume flow Q 33.3 m³/h
Break tank design Q4/2020 VBH 1000 Liter
Min. fluid temperature 5 °C
Max. fluid temperature 40 °C
Min. ambient temperature 3 °C
Max. ambient temperature 40 °C
Dimensions
Dimensions B 830.0 mm
Dimensions B1 310.0 mm
Dimensions B2 100.0 mm
Dimensions D 508.0 mm
Dimensions H 1855.0 mm
Dimensions H1 200.0 mm
Dimensions H2 1445.0 mm
Dimensions H3 1740.0 mm
Dimensions H4 60.0 mm
Dimensions H5 120.0 mm
Dimensions H6 100.0 mm
Dimensions L 1460.0 mm
Dimensions L1 160 mm
Dimensions l2 400 mm
Dimensions L3 100.0 mm
Dimensions L4 1695.0 mm
Materials
Tank material PE
Product data
Brand Wilo
Product description Break tank for fire extinguishing systems (rectangular version), 1000 L
Article number 2528258
EAN number 4016322939894
Colour Black
Minimum order quantity 1
Date of sales availability 2010-01-01
Packaging
Packaging type Special pallet
Packaging property Transport packaging
Pieces per pallet 1
Number per layer 1
Dimension, weight
Length with packaging 2400 mm
Length L 1695 mm
Height with packaging 2205 mm
Height H 1995 mm
Width with packaging 900 mm
Width W 830 mm
Gross weight, approx. m 193 kg
Net weight, approx. m 145 kg
Tender text

Atmospherically ventilated break tank for indirect connection to the drinking water supply network. System separation in accordance with DIN EN 1717 by means of safety device “free drain”, type AB in accordance with EN 13077.

The overflow alarm fitted as standard can be connected to a switchgear and then triggers an alarm signal when the break tank overflows.

When using, please observe the corresponding standards (DIN 1988-600, DIN 1988-500) and the regulations of the local water supply companies.

Fields of application:

  • Indirect connection of fire-extinguishing systems, in accordance with DIN 1988-600, to the public drinking water network.
  • Indirect connection of pressure-boosting system, in accordance with DIN 1988-500, to the public drinking water network.

Scope of delivery

PE tank in cornered construction form with

  • Water level indicator
  • Draining
  • Float switch as low-water signal transmitter
  • Venting and exhaust with valve plate
  • Inspection opening with cover that can be sealed without tools
  • Inner wash plates for slowing down the fluid
  • Inlet, overflow, draw-off connection

Installation instructions

  • Flat, horizontal, frost-resisting
  • Provide sufficient space for inspection
Technical data
Break tank volume V 1000 l
Min. fluid temperature 5 °C
Max. fluid temperature 40 °C
Tank material PE
Inlet connection 2x Ø60mm (2“)
Outlet connection DN 100
Flush connection - in
Overflow 1 x HT 125
Evacuation connection G 1
Ordering information
Length L 1695 mm
Width W 830 mm
Height H 1995 mm
Net weight, approx. 145 kg
Make Wilo
Item no. 2528258
Documents

Installation and operating instructions

Wilo-VBH

Article Number 2530098
Edition 2023-11
Number of pages 111
Language de, en, fr
PDF (2 MB)
BIM/CAD

3D_DWG

BREAK TANK 1000L ANGULARLY FLA PE

Language language neutral
DWG (443 KB)

3D_STEP

BREAK TANK 1000L ANGULARLY FLA PE

Language language neutral
STP (392 KB)

2D_DWG_TOP

BREAK TANK 1000L ANGULARLY FLA PE

Language language neutral
DWG (18 KB)

2D_DWG_FRONT

BREAK TANK 1000L ANGULARLY FLA PE

Language language neutral
DWG (20 KB)

2D_DWG_RIGHT

BREAK TANK 1000L ANGULARLY FLA PE

Language language neutral
DWG (22 KB)