Similar to figure
Break tank for fire extinguishing systems (round version), 1000 L
Article number: 2528243
Atmospherically ventilated break tank for indirect connection to the drinking water supply network. System separation in accordance with DIN EN 1717 by means of safety device “free drain”, type AB in accordance with EN 13077.
The overflow alarm fitted as standard can be connected to a switchgear and then triggers an alarm signal when the break tank overflows.
When using, please observe the corresponding standards (DIN 1988-600, DIN 1988-500) and the regulations of the local water supply companies.
Fields of application
- Indirect connection of fire extinguishing systems, in accordance with DIN 1988-600, to the public drinking water network.
- Indirect connection of pressure-boosting system, in accordance with DIN 1988-500, to the public drinking water network.
Scope of delivery
Round design PE tank with:
- Water level indicator
- Draining
- Float switch as low-water signal transmitter
- Venting and exhaust with valve plate
- Inspection opening with cover that can be closed without tools
- Inner wash plates for slowing down the fluid
- Inlet, overflow, draw-off connection
Installation instructions
- Flat, horizontal, frost-resisting
- Provide sufficient space for inspection
Technical data | |
---|---|
Break tank volume V | 1000 l |
Min. fluid temperature | 5 °C |
Max. fluid temperature | 40 °C |
Tank material | PE |
Inlet connection | 2x Ø60mm (2“) |
Outlet connection | DN 100 |
Flush connection | - in |
Overflow | 1 x HT 125 |
Evacuation connection | Rp ½ |
Ordering information | |
---|---|
Length L | 1200 mm |
Width W | 1000 mm |
Height H | 2150 mm |
Net weight, approx. | 86 kg |
Make | Wilo |
Item no. | 2528243 |