CronoTwin-DL-E 40/200-7,5/2-S1
Article number: 2171062
Glanded twin-head pump with in-line design for pipe installation or installation on a base with built-in frequency converter for electronic control for constant or variable differential pressure (Δp-c/Δp-v), among other things.
Design:
- Single-stage low-pressure centrifugal pump
- Spiral housing in in-line design (suction and pressure ports with the same flanges in one line), flanges PN 16 – drilled acc. to EN 1092-2
- Pressure measuring connections (R 1/8) for mounted differential pressure sensor (version ...-R1 without differential pressure sensor)
- Pump housing and motor flange with cataphoretic coating as standard
- Mechanical seal S1 recommended for water-glycol mixtures with glycol proportions up to max. 50% by volume and a fluid temperature of -20 °C up to max. +110 °C and also for oil proportions in the water-glycol mixture.
Accessories:
- Mounting brackets for fixing to the foundation
- IR-Monitor
- IF module PLR
- IF module LON
- IF module Modbus
- IF module BACnet
- IF module CAN
- Control systems VR-HVAC/CCe-HVAC/SCe-HVAC
- Differential pressure sensor (DDG) sets 0-10 V for pumps in version ...-R1
Standard equipment:
- One-button manual operation level for:
- Pump On/Off
- Setpoint and speed adjustment
- Selecting the control mode: Δp-c (constant differential pressure), Δp-v (variable differential pressure), PID controller, n-constant (constant speed)
- Selection of operating mode in twin-head pump operation (main/standby operation, parallel operation)
- Configuration of operating parameters
- Fault acknowledgement
- Pump display for indication of:
- Control mode
- Setpoint (e.g. differential pressure or speed)
- Error and warning messages
- Actual values (e.g. power consumption, actual value of the sensor)
- Operating data (e.g. operating hours, energy consumption)
- Status data (e.g. status of SSM and SBM relay)
- Device data (e.g. pump name)
Additional functions:
- Interfaces: Control input "Overriding Off", "External pump cycling", analogue input 0–10 V, 2–10 V, 0–20 mA, 4–20 mA for constant speed (DDC) or for remote setpoint adjustment, analogue input 0–10 V, 2–10 V, 0–20 mA, 4–20 mA for actual value signal of the pressure sensor, Infrared interface for wireless communication with the operating and service unit Wilo-IR-Stick/IR-Monitor, plug-in position for Wilo IF modules for connecting to the building automation, configurable, potential-free fault and operating/ready message, interface for twin-head pump communication
- Three-phase AC motor with frequency converter
- Integrated dual pump management
- Adjustable time interval for pump cycling
- Integrated full motor protection
- Different operating modes for heating (HV) or air-conditioning (AC) applications
- Access disable
- Different operation levels: Standard/service
Operating Data | |
---|---|
Fluid temperature T | -20 °C |
Ambient temperature T | 0 °C |
Maximum operating pressure PN | 16 bar |
Note on dimensioning | 16 bar to 120 °C, 13 bar to 140 °C |
Minimum efficiency index (MEI) | 0.4 |
Drive | |
---|---|
Mains connection |
|
Motor efficiency class | IE4 |
Power consumption P1 max | 8700 W |
Rated power P2 | 7.5 kW |
Max current Imax | 13.8 A |
Max. speed nmax | 2960 1/min |
Interference emission | EN 61800-3 |
Interference immunity | EN 61800-3 |
Insulation class | F |
Protection class motor | IP55 |
Motor protection | PTC integrated |
Materials | |
---|---|
Pump housing | Grey cast iron |
Impeller | Grey cast iron |
Shaft | Stainless steel |
Shaft seal | Q1Q1X4GG |
Lantern | 5.1301/EN-GJL-250 KTL-coated |
Installation dimensions | |
---|---|
Pipe connection on the suction side DNs | DN 40 |
Pipe connection on the discharge side DNd | DN 40 |
Port-to-port length L0 | 440 mm |
Ordering information | |
---|---|
Brand | Wilo |
Product description | CronoTwin-DL-E 40/200-7,5/2-S1 |
Net weight, approx. m | 216 kg |
Article number | 2171062 |