Contact

1-800-266-8866*

*Toll Free

Wilo-Isar MODV1-1 | Wilo
Your advantages
Wilo-Isar MODV1-1

Your advantages

  • High operational reliability thanks to system with one, two or three vertical multistage CV1-L pumps with stainless steel hydraulics
  • Easy hydraulic installation and maintenance with the O-ring assembly
  • Easy commissioning and operation thanks to the Easy Control panel
  • Drinking water approval (ACS and UBA-conformity) for all relevant components
  • Adjustable vibration absorbers for a low noise operation.
Series description
Wilo-Isar MODV1-1

Design

Pressure-boosting system with 1, 2 or 3 non-self-priming stainless steel high-pressure multistage centrifugal pumps switched in parallel

Application

  • Fully automatic water supply and pressure boosting in inlet mode, either from the public water supply network or from a tank, for domestic, commercial, industrial and municipal applications (e.g. residential, office, administration buildings, hotels, hospitals, trades, industry, water supply companies).
  • Pumping drinking water, process water, cooling water or other industrial water, which does not affect the materials used, neither chemically nor mechanically, and does not have any abrasive or long-fibre constituents

Equipment/function

  • 1 – 2 or 3 CV1-L pumps per system
  • Components that come in contact with the fluid are corrosion-resistant
  • Electrogalvanized base frame with height-adjustable vibration absorbers for insulation against structure-borne noise
  • Stop valve on every pump on the suction and pressure sides
  • Non-return valve, pressure side
  • Pressure sensor, on the discharge side
  • Pressure gauge optional, on the suction side
  • Pressure gauge, discharge side
  • Low-water cut-out switchgear, optional
  • EC-control with IP54 plastic housing, consisting of an internal power supply unit, microprocessor, analogue and digital input and output modules

Typekey

Example:

Wilo-ISAR MODV1-1CV1-L-213/EC

Wilo

Brand

ISAR

Multistage booster

MOD

Commercial series

V

Vertical booster

1

Product level (1=Entry, 3= Standard, 5=Premium)

1

Number of pumps

CV1-L

Pump series

2

Rated volume flow [m3/h] of the single pump

13

Number of single pump stages

EC

Control panel (Easy Controller)

Technical data

  • 3~400 V ± 10 %, 50 Hz; 3~380/440 V ±10 %, 60 Hz mains connection, depending on type also 1~230 V, 50/60 Hz (other versions on request)
  • Max. fluid temperature 50 °C (70 °C optional)
  • Max. ambient temperature 40 °C
  • Operating pressure 10 bar
  • Inlet pressure 6 bar
  • Nominal connection diameter, on the discharge side R 2"/DN 100
  • Nominal connection diameter, on the inlet side R 2"/DN 100
  • Protection class IP54
  • Fuse protection on mains side A, AC 3 according to motor power and EVU regulations
  • Approved fluids (other fluids on request). Approved fluids are generally waters which do not attack the materials used, neither chemically nor mechanically, and do not contain any abrasive or long-fibre constituents.
  • Cooling water
  • Drinking and process water

Materials

Single pump:

  • Impellers, stage chambers and pump housing made of stainless steel 1.4301/1.4404
  • Shaft of stainless steel 1.4404
  • EPDM gasket (EP851)/FKM (Viton)
  • Mechanical seal made of tungsten carbide/carbon
  • Bearing of tungsten carbide
  • Pump support foot made of aluminium

Construction

  • Base frame: electrogalvanized and provided with height-adjustable vibration absorbers for comprehensive insulation against structure-borne noise; other versions on request
  • Pipework: complete pipework made of stainless steel, suitable for the connection of all piping materials used in building services; the pipework dimensions must correspond to the overall hydraulic performance of the pressure-boosting system
  • Pumps: 1-2 or 3 pumps of the CH1-L series 2.., 4.., 6.., 10.. switched in parallel; all pump components coming into contact with fluid are made of 1.4301/1.4404 stainless steel
  • Valves: each pump is equipped on the suction and pressure side with a stop valve or with annular shut-off valves and a pressure-side non-return valve
  • Diaphragm pressure vessel: 8 l/PN 10 located on the discharge side with a butyl rubber diaphragm, completely safe in accordance with food safety laws; for testing and inspection purposes, with a ball valve, as well as drain and throughflow fitting according to DIN 4807
  • Pressure sensor: 4 to 20 mA, on the discharge side for activating the central EC-controller
  • Pressure indication: Pressure gauge (ø 63 mm) on the discharge side; additional digital display of the discharge pressure in the alphanumeric display of the EC-controller
  • Controller: the system is standard-equipped with an EC-controller

Delivery state

  • Factory-mounted, ready for connection pressure-boosting system checked for functionality and impermeability
  • Packaging
  • Installation and operating instructions
Downloads

Installation and operating instructions

Wilo Isar-MODH1#Wilo Isar-MODV1

Article Number 2552079
Edition 2021-04
Page format 209.9 x 297.0 mm
Number of pages 64
PDF (8 MB)

Certificate REACH (Documents)

REACH Regulation

Edition 2021-05
Page format 209.9 x 297.0 mm
Number of pages 4
PDF (212 KB)
Product list
Product descriptionPipe connection on the suction side DNsPipe connection on the discharge side DNdMaximum operating pressure PNGross weight, approx. mArticle number
Isar MODV1-1CV1-L-209/EC
G 1
G 1
16 bar
83 kg
2554091
Isar MODV1-1CV1-L-211/EC
G 1
G 1
16 bar
84 kg
2554092
Isar MODV1-1CV1-L-213/EC
G 1
G 1
16 bar
88 kg
2554093
Isar MODV1-1CV1-L-215/EC
G 1
G 1
16 bar
93 kg
2554094
Isar MODV1-1CV1-L-216/EC
G 1
G 1
16 bar
94 kg
2554095
Isar MODV1-1CV1-L-409/EC
G 1
G 1
16 bar
83 kg
2554096
Isar MODV1-1CV1-L-411/EC
G 1
G 1
16 bar
87 kg
2554097
Isar MODV1-1CV1-L-413/EC
G 1
G 1
16 bar
92 kg
2554098
Isar MODV1-1CV1-L-415/EC
G 1
G 1
16 bar
93 kg
2554099
Isar MODV1-1CV1-L-606/EC
G 1¼
G 1¼
16 bar
87 kg
2554100
Isar MODV1-1CV1-L-607/EC
G 1¼
G 1¼
16 bar
92 kg
2554101
Isar MODV1-1CV1-L-608/EC
G 1¼
G 1¼
16 bar
93 kg
2554102
Isar MODV1-1CV1-L-609/EC
G 1¼
G 1¼
16 bar
96 kg
2554103
Isar MODV1-1CV1-L-610/EC
G 1¼
G 1¼
16 bar
97 kg
2554104
Isar MODV1-1CV1-L-611/EC
G 1¼
G 1¼
16 bar
104 kg
2554105
Isar MODV1-1CV1-L-612/EC
G 1¼
G 1¼
16 bar
105 kg
2554106
Isar MODV1-1CV1-L-1006/EC
G 1½
G 1½
16 bar
95 kg
2554107
Isar MODV1-1CV1-L-1007/EC
G 1½
G 1½
16 bar
96 kg
2554108
Isar MODV1-1CV1-L-1008/EC
G 1½
G 1½
16 bar
103 kg
2554109
Isar MODV1-1CV1-L-1009/EC
G 1½
G 1½
16 bar
104 kg
2554110
Isar MODV1-1CV1-L-1010/EC
G 1½
G 1½
16 bar
140 kg
2554111
Isar MODV1-1CV1-L-1011/EC
G 1½
G 1½
16 bar
141 kg
2554112
Isar MODV1-1CV1-L-1606/EC
G 2
G 2
16 bar
103 kg
2554113
Isar MODV1-1CV1-L-1607/EC
G 2
G 2
16 bar
138 kg
2554114
Isar MODV1-1CV1-L-1608/EC
G 2
G 2
16 bar
139 kg
2554115