VeroTwin-DP-E 50/130-2,2/2-R1

Data sheet

Materials
  • Pump housing
    5.1301, EN-GJL-250
  • Impeller
    PPE/PS-GF30
  • Lantern
    5.1301, EN-GJL-250
  • Shaft
    1.4021, X20Cr13
Operating data
  • Min. fluid temperature T
    -20 °C
  • Max. fluid temperature T
    120 °C
  • Maximum operating pressure p
    10 bar
  • Max. ambient temperature T
    40 °C
  • Minimum efficiency index (MEI)
    0.4
Motor data
  • Mains connection
    3~440 V, 50 Hz
  • Motor efficiency class
    IE4
  • Emitted interference
    EN 61800-3
  • Interference resistance
    EN 61800-3
  • Rated power P2
    2.20 kW
  • Rated current IN
    6.80 A
  • Rated speed n
    2900 rpm
  • Max. speed nmax
    2900 rpm
  • Protection class motor
    IP55
Installation dimensions
  • Port-to-port length L0
    340 mm
  • Pipe connection on the suction side
    DN 50
  • Pipe connection on the pressure side
    DN 50
Information for order placements
  • Net weight, approx. m
    74 kg
  • Brand
    Wilo
  • Product description
    VeroTwin-DP-E 50/130-2,2/2-R1
  • Article number
    2159010

Dimensions and dimensions drawings

VeroTwin-DP-E 50/130-2,2/2-R1

VeroTwin-DP-E 50/130-2,2/2-R1

Note:

Housing with feet for installation on a base and drilled holes M10, brackets on request.

VeroTwin-DP-E 50/130-2,2/2-R1

Pump curves

VeroTwin-DP-E 50/130-2,2/2, Parallel operation

VeroTwin-DP-E 50/130-2,2/2, Parallel operation

VeroTwin-DP-E 50/130-2,2/2, Individual operation

VeroTwin-DP-E 50/130-2,2/2, Individual operation
VeroTwin-DP-E 50/130-2,2/2, Parallel operation
VeroTwin-DP-E 50/130-2,2/2, Individual operation

Wiring diagram

IL-E

IL-E

L1, L2, L3:Mains connection: 3~440 V ±10%, 50/60 Hz; 3~400 V ±10%, 50/60 Hz; 3~380 V -5%/+10%, 50/60 Hz
PE:Protective conductor connection
DDG:Connection for differential pressure sensor
In1 (1):Actual value input 0-10 V/0-20 mA; 2-10 V/4-20 mA
GND (2):Ground connection for In1 and In2
+ 24 V (3):DC voltage output for an external consumer/sensor. Max load 60 mA
In2:Setpoint input 0-10 V/0-20 mA; 2-10 V/4-20 mA
MP:Multi-pump, interface for dual pump management
Ext. off:Control input “Overriding Off”The pump can be switched on or off via an external, potential-free contact (24 V DC/10 mA).
SBM:*Potential-free collective run signal (changeover contact according to VDI 3814)
SSM:*Potential-free collective fault signal (changeover contact according to VDI 3814)
aux:External pump cycling (only with dual pump operation). Pump cycling can be performed using an external, potential-free contact (24 VDC/10 mA)
DIP switch:1: Switchover between operation (O) and service mode (S)2: Activate/deactivate the menu for access disable
Optional:IF-Modules for connection to the building automation

* Load capacity of contacts for SBM and SSM:

min.: 12 V DC/10 mA

max.: 250 V AC/1 A

IL-E

Ordering information

Information for order placements
  • Brand
    Wilo
  • Product description
    VeroTwin-DP-E 50/130-2,2/2-R1
  • EAN number
    4048482649313
  • Article number
    2159010
  • Gross weight, approx. m
    101.3 kg
  • Net weight, approx. m
    74 kg
  • Overall length L
    447.0 mm
  • Height without packaging H
    396 mm
  • Colour
    Green
  • Packaging property
    Transport packaging
  • Packaging type
    Europallet
  • Number per layer
    1
  • Width without packaging L
    742.0 mm
  • Minimum order quantity
    1
  • Pieces per pallet
    1

Tender text

Glanded twin-head pump with in-line design for pipe installation or installation on a base with built-in frequency converter for electronic control for constant or variable differential pressure (Δp-c/Δp-v), among other things. Three-phase AC motor with frequency converter

Design:

  • Single-stage low-pressure centrifugal pump with one-piece shaft
  • Spiral housing, in-line design
  • PN 16 flange – drilled according to EN 1092-2
  • Pressure measuring connections (R 1/8) for mounted differential pressure sensor (version ...-R1 without differential pressure sensor)
  • Pump housing and motor flange with cataphoretic coating as standard
  • Mechanical seal for water feed up to T=120 °C. A glycol admixture of 20 to 40% by vol. is permitted up to Tmax = +40 °C. Other mechanical seals or other fluids/temperatures on request.

Accessories:

  • Mounting brackets for fixing to the foundation
  • IR-Monitor
  • IF module PLR
  • IF module LON
  • IF module Modbus
  • IF module BACnet
  • IF module CAN
  • Differential pressure sensor (DDG) sets 0-10 V for pumps in version ...-R1

Standard equipment:

  • One-button manual operation level for:
    • Pump On/Off
    • Setpoint and speed adjustment
    • Selecting the control mode: Δp-c (constant differential pressure), Δp-v (variable differential pressure), PID controller, n-constant (constant speed)
    • Selection of operating mode in dual pump operation (main/standby operation, parallel operation)
    • Configuration of operating parameters
    • Fault acknowledgement
  • Pump display for displaying:
    • Control mode
    • Setpoint (e.g. differential pressure or speed)
    • Error and warning messages
    • Actual values (e.g. power consumption, actual value of the sensor)
    • Operating data (e.g. operating hours, energy consumption)
    • Status data (e.g. status of SSM and SBM relay)
    • Device data (e.g. pump name)

Additional functions:

  • Interfaces: Control input "Overriding Off", "External pump cycling" (effective only in dual pump operation), analogue input 0–10 V, 2–10 V, 0–20 mA, 4–20 mA for control mode (DDC) or for remote setpoint adjustment, analogue input 0–10 V, 2–10 V, 0–20 mA, 4–20 mA for actual value signal of the pressure sensor, Infrared interface for wireless communication with the operating and service unit Wilo-IR-Stick/IR-Monitor, plug-in position for Wilo IF-Module Modbus, BACnet, CAN, PLR, LON for connecting to the building automation, configurable, potential-free fault and operating/ready message, interface for dual pump communication
  • Adjustable time interval for pump cycling (in dual pump mode)
  • Integrated full motor protection
  • Different operating modes for heating mode (HV) or air-conditioning mode (AC)
  • Access disable
  • Different operation levels: Standard / Service
Materials
  • Pump housing
    5.1301, EN-GJL-250
  • Impeller
    PPE/PS-GF30
  • Lantern
    5.1301, EN-GJL-250
  • Shaft
    1.4021, X20Cr13
Operating data
  • Fluid media
    Water
  • Min. fluid temperature T
    -20 °C
  • Max. fluid temperature T
    120 °C
  • Maximum operating pressure p
    10 bar
  • Max. ambient temperature T
    40 °C
  • Minimum efficiency index (MEI)
    0.4
Motor data
  • Emitted interference
    EN 61800-3
  • Interference resistance
    EN 61800-3
  • Mains connection
    3~440 V, 50 Hz
  • Rated power P2
    2200 W
  • Max. speed nmax
    2900 rpm
  • Rated current IN
    6.80 A
  • Protection class motor
    IP55
  • Insulation class
    F
  • Integrated full motor protection
    yes
Installation dimensions
  • Pipe connection on the suction side
    DN 50
  • Pipe connection on the pressure side
    DN 50
Information for order placements
  • Net weight, approx. m
    74 kg
  • Brand
    Wilo
  • Product description
    VeroTwin-DP-E 50/130-2,2/2-R1
  • Article number
    2159010

Downloads

Wilo-VeroLine IP-E, DP-E

Article Number 2144991
Edition 1505
Version number 01
Page format A4
Number of pages 1

PDF (100 MB)

Download

REACH Regulation

Edition 2018-10
Page format 209.9 x 296.7 mm
Number of pages 4

PDF (581 kB)

Download

PDF: VeroTwin-DP-E 50/130-2,2/2-R1

Configure

Page selection

Format selection

Optional information

You can enter any personal information that you want to be displayed in the header.

Download