DCX
- Direction of rotation signal lamp for displaying the correct sense of rotation (only with 3~)
- Manual power adjustment with 3 speed stages
- Double pump for main/standby or parallel operation
- Pump housing with cataphoretic (KTL) coating protects against corrosion due to condensation formation
Design
CIRCULATEUR DOUBLE (NON DESTINE AU MARCHE EUROPEEN)
50 Hz
Application
Hot-water heating systems of all kinds, industrial circulation systems, air-conditioning systems and closed cooling circuitsEquipment/function
Operating modes
- Speed-stage switching
Manual functions
- Setting the speed stages: 3 speed stages
Automatic functions
- Internal protection against non-approved high winding temperatures (only for pumps for which P2 ≤180 W)
Signal and display functions
- Thermal winding contact (WSK, potential-free NC contact) (only for pumps for which P2 ≥180 W) for full motor protection in all speed levels with optional tripping unit SK 602N/SK 622N
- Rotation monitoring lamp (standard equipment for 3~pumps only)
- Display of selected speed stage
Dual pump management (double pump or 2 x single pumps)
- Main/standby operation or parallel operation (for automatic fault-actuated switchover/time-dependent pump cycling, a corresponding switchgear must be provided on-site)
Equipment
- For flange-end pumps: Flange versions
- Standard version for DN 32 to DN 65 pumps: PN 6/10 combination flange (PN 16 flange according to EN 1092-2) for PN 6 and PN 16 counter flanges,
- Standard version for pumps DN 80: PN 6 flange (designed for PN 16 according to EN 1092-2) for PN 6 counter flange
- Mounting bracket set-up (with horizontal shaft only):
- Standard version for pumps TOP-SD 40/15, 50/15, all TOP-SD 65 and TOP-SD 80.
- Special version for pumps TOP-SD 32/10, 40/3, 40/7, 40/10, 50/7, 50/10. M10 drilled hole for mounting bracket set-up available on request.
- Double switchover valve in pump housing
- Cable inlet possible from both sides (only for 1~pumps and 3~pumps with P2 ≥ 180 W)
Type key
Example: | DCX |
DCX | Standard double pump (flange-end pump, TOP‐SD 30/5 with threaded connection) |
40/ | Nominal connection diameter |
7 | Nominal delivery head [m] at Q = 0 m3/h |
Technical data
- Permitted temperature range -20 °C to +130 °C, for short periods (2 h) to +140 °C (TOP-SD 80/15, 80/20: -20 °C to +110 °C)
- Mains connection:
- 1~230 V, 50 Hz (depending on type)
- 3~230 V, 50 Hz (with optional switching plug)
- 3~400 V, 50 Hz
- Protection class IP X4D
- Screwed connection or flange connection (depending on type) Rp 1¼ to DN 80
- Max. operating pressure of standard version: 6/10 bar or 6 bar (special version: 10 bar)
Materials
- Pump housing: Grey cast iron
- Impeller: Plastic
- Shaft: stainless steel
- Bearing: Carbon, metal impregnated
Scope of delivery
- Double pump
- Including seals for screwed connection (only for DCX32-35)
- Including washers for flange screws (for nominal connection diameters DN 32 ‐ DN 65)
- Installation and operating instructions
Options
- Versions for special voltages on request
Take advantage of the latest replacement guide
The current replacement guide on all glandless pumps for heating and drinking water applications makes choosing the right pump easier for you. Here, you will find a suitable new Wilo pump for all known pumps built after 1975.
After entering your old pump data, select the current pump type.