Data sheet
| Product data | |
|---|---|
| Product description | Para 25-130/6-43/LINX |
| Pump housing | RS |
| Hydraulic data | |
|---|---|
| Maximum operating pressure PN | 10 bar |
| Max. fluid temperature Tmax | 95 °C |
| Min. fluid temperature Tmin | -10 °C |
| Min. ambient temperature Tmin | -10 °C |
| Max. ambient temperature Tmax | 70 °C |
| Permitted fluids | Water Ethylene glycol Propylene glycol |
| Minimum suction head at 50 °C m | 0.5 m |
| Minimum suction head at 95 °C m | 4.5 m |
| Motor data | |
|---|---|
| Control mode | LINX |
| Energy efficiency index (EEI) * | ≤ 0.20 |
| Mains connection | 1~230 V +10/-15%, 50/60 Hz |
| Power consumption P1 min | 1 W |
| Power consumption P1 max | 43 W |
| Power consumption in standby mode P1 | ≤ 0.5 W |
| Max current Imax | 0.44 A |
| Approvals and markings | CE EAC UA UKCA |
| Motor protection | integrated |
| Protection class | IPX4D |
| Insulation class | F |
| Materials | |
|---|---|
| Pump housing | Cast iron with cataphoresis treatment |
| Impeller | PP-GF40 |
| Shaft | Stainless steel |
| Bearing | Carbon-graphite |
| Installation | |
|---|---|
| Pipe connection, suction side DNs | G 1½ |
| Pipe connection, discharge side DNd | G 1½ |
| Port-to-port length L0 | 130 mm |
Dimensions and dimensions drawings
Para 25-130/6-43/LINX-12