Stratos GIGA B 50/1-17/1,9
Data sheet
Hydraulic data
-
Minimum efficiency index (MEI)0.7
-
Maximum operating pressure p16 bar
-
Min. fluid temperature Tmin-20 °C
-
Max. fluid temperature Tmax140 °C
-
Min. ambient temperature Tmin0 °C
-
Max. ambient temperature Tmax40 °C
Motor data
-
Mains connection3~400 V, 50/60 Hz
-
Motor efficiency classIE5
-
Rated power P21.90 kW
-
Rated current IN2.90 A
-
Rated speed n2180 rpm
-
Max. speed nmax2180 rpm
-
Emitted interferenceEN 61800-3
-
Interference resistanceEN 61800-3
-
Insulation classF
-
Protection class motorIP55
-
Threaded cable connection1 x M12x1.5
Materials
-
Pump housing5.1301, KTL-coated
-
ImpellerPPS-GF40
-
Shaft1.4542
-
Shaft sealAQ1EGG
-
Lantern5.1301, KTL-coated
Approved liquids (other liquids upon request)
-
Heating water (as per VDI 2035)yes
-
Heat carrier oilSpecial version at additional charge
-
Cooling and cold water circulation systemsyes
-
Water-glycol mixtures (at 20 – 40 vol. % glycol and fluid temperature ≤ 40 °C)yes
Installation dimensions
-
Pipe connection on the suction side RPSDN 65
-
Pipe connection on the pressure side RPDDN 50
Information for order placements
-
BrandWilo
-
Product descriptionStratos GIGA B 50/1-17/1,9
-
EAN number4048482778365
-
Article number2189110
-
Net weight, approx. m41 kg
-
Gross weight, approx. m48.0 kg
-
Length with packaging795 mm
-
Height with packaging615 mm
-
Width with packaging515 mm
-
Packaging propertyTransport packaging
-
Packaging typeCardboard box
-
Minimum order quantity1
Tender text
High-efficiency monobloc pump with EC motor of energy efficiency class IE5 in accordance with IEC 60034-30-2 and electronic power adjustment in glanded pump design. The pump is configured as a single-stage low-pressure centrifugal pump with flange connection and mechanical seal. The Stratos GIGA B has been predominantly designed for pumping heating water (acc. to VDI 2035), cold water and water-glycol mixtures without abrasive substances in heating, air-conditioning and cooling systems.
Design:
- Single-stage low-pressure centrifugal pump with one-piece shaft in monobloc design including foot on pump housing
- Flange and housing measurements according to EN 733
- PN 16 flange – drilled according to EN 1092-2
- Pressure measuring connections (R 1/8) for mounted differential pressure sensor (version ...-R1 without differential pressure sensor)
- Pump housing and motor flange with cataphoretic coating as standard
- Mechanical seal for pumping water up to Tmax. = +140 °C. A glycol admixture of 20 % to 40 % by volume is permitted up to T ≤ +40 °C. An alternative mechanical seal must be provided in water-glycol mixtures with glycol proportions > 40 % up to maximum 50 % by volume and a fluid temperature of > +40 °C up to maximum +120 °C or fluids other than water.
- Connection voltages: 3~480 V ±10% 50/60 Hz; 3~440 V ±10% 50/60 Hz; 3~400 V ±10% 50/60 Hz; 3~380 V -5 % +10% 50/60 Hz
Accessories:
- Mounting brackets for fixing to the foundation
- Differential pressure sensor kits 0 – 10 V for pumps in version ...-R1
- IR-Monitor
- IR-Stick
- IF-Module PLR
- IF-Module LON
- IF-Module Modbus
- IF-Module BACnet
- CAN IF-Module
Standard equipment:
- Green button manual operation level for:
- Pump On/Off
- Selecting the control mode: Δp-c (constant differential pressure), Δp-v (variable differential pressure), PID controller, n-constant (constant speed)
- Setpoint and speed adjustment
- Configuration of operating parameters
- Fault acknowledgement
- Pump display for displaying:
- Control mode
- Setpoint (e.g. differential pressure or speed)
- Error and warning messages
- Actual values (e.g. power consumption, actual value of the sensor)
- Operating data (e.g. operating hours, energy consumption)
- Status data (e.g. status of SSM and SBM relay)
- Device data (e.g. pump name)
- Operating mode (for Y-piece installation only: main/standby operation, parallel operation)
Additional functions:
- Analogue interfaces 0 – 10 V, 2 – 10 V, 0 – 20 mA, 4 – 20 mA, built-in dual pump management for application in the Y-piece, two configurable signalling relays for operating and fault signals, configurable fault response adapted to HVAC applications, access disable on the pump, built-in full motor protection (PTC thermistor sensor) with trip electronics, condensation drain holes in the motor housing as standard (sealed in delivered condition), infrared interface for wireless communication with the operating and service unit Wilo-IR-Monitor and Wilo-IR-Stick, plug-in position for Wilo IF-Module Modbus, BACnet, CAN, PLR, LON for connecting to the building automation.
Operating data
-
Fluid mediaWater
-
Maximum operating pressure PN16 bar
-
Minimum efficiency index (MEI)0.7
Motor data
-
Motor efficiency classIE5
-
Emitted interferenceEN 61800-3
-
Interference resistanceEN 61800-3
-
Mains connection3~400 V, 50/60 Hz
-
Rated power P21900.0 W
-
Max. speed nmax2180 rpm
-
Rated current IN2.90 A
-
Insulation classF
-
Protection class motorIP55
-
Motor protectionintegrated
Materials
-
Pump housing5.1301, KTL-coated
-
ImpellerPPS-GF40
-
Shaft1.4542
-
Shaft sealAQ1EGG
-
Lantern5.1301, KTL-coated
Installation dimensions
-
Pipe connection on the suction side RPSDN 65
-
Pipe connection on the pressure side RPDDN 50
Information for order placements
-
BrandWilo
-
Product descriptionStratos GIGA B 50/1-17/1,9
-
Net weight, approx. m41 kg
-
Article number2189110
Wiring diagram
IL-E

L1, L2, L3: | Mains connection: 3~440 V ±10%, 50/60 Hz; 3~400 V ±10%, 50/60 Hz; 3~380 V -5%/+10%, 50/60 Hz |
PE: | Protective conductor connection |
DDG: | Connection for differential pressure sensor |
In1 (1): | Actual value input 0-10 V/0-20 mA; 2-10 V/4-20 mA |
GND (2): | Ground connection for In1 and In2 |
+ 24 V (3): | DC voltage output for an external consumer/sensor. Max load 60 mA |
In2: | Setpoint input 0-10 V/0-20 mA; 2-10 V/4-20 mA |
MP: | Multi-pump, interface for dual pump management |
Ext. off: | Control input “Overriding Off”The pump can be switched on or off via an external, potential-free contact (24 V DC/10 mA). |
SBM:* | Potential-free collective run signal (changeover contact according to VDI 3814) |
SSM:* | Potential-free collective fault signal (changeover contact according to VDI 3814) |
aux: | External pump cycling (only with dual pump operation). Pump cycling can be performed using an external, potential-free contact (24 VDC/10 mA) |
DIP switch: | 1: Switchover between operation (O) and service mode (S)2: Activate/deactivate the menu for access disable |
Optional: | IF-Modules for connection to the building automation |
* Load capacity of contacts for SBM and SSM: min.: 12 V DC/10 mA max.: 250 V AC/1 A |

Ordering information
Information for order placements
-
BrandWilo
-
Product descriptionStratos GIGA B 50/1-17/1,9
-
EAN number4048482778365
-
Article number2189110
-
Gross weight, approx. m48.0 kg
-
Net weight, approx. m41 kg
-
Overall length L560.0 mm
-
Height without packaging H408 mm
-
Colourgreen/silver
-
Packaging propertyTransport packaging
-
Packaging typeCardboard box
-
Number per layer1
-
Width without packaging L276.0 mm
-
Minimum order quantity1
-
Pieces per pallet1