Wilo-TOP-RL

Series description

Your advantages

  • Manual power adjustment with 3 speed stages
  • Pump housing with cataphoretic (KTL) coating protects against corrosion due to condensation formation

Construction

Glandless circulation pump with screwed connection or flange connection

Application

Hot-water heating systems of all kinds, air-conditioning systems, closed cooling circuits, industrial circulation systems

Equipment/function

Operating modes

  • Speed-stage switching

Manual functions

  • Setting of speed stages (3 speed stages)

Automatic functions

  • Full motor protection with integrated trip electronics (optional for all types with Wilo-Protect-Module C)

External control functions

  • "Overriding Off" control input (optional for all types with Wilo-Protect-Module C)

Signal and display functions

  • Individual/collective fault signal (potential-free NC contact) (optional for all types with Wilo-Protect-Module C)
  • Collective fault signal (potential-free NC contact) (optional for all types with Wilo-Protect-Module C)
  • Individual run signal (potential-free NO contact) (optional for all types with Wilo-Protect-Module C)
  • Fault signal light (optional for all types with Wilo-Protect-Module C)

Dual pump management (twin-head pump or 2 x single pump)

  • Main/standby mode (automatic fault-actuated switchover / time-dependent pump cycling) (optional for all types with Wilo-Protect-Module C)

Equipment

  • With flange pump: Flange version
    • Standard version for pump DN 40: Combination flange PN 6/10 (flange PN 16 acc. to EN 1092-2) for counter flange PN 6 and PN 16,

Scope of delivery

  • Pump
  • Seals for threaded connection
  • Including washers for flange bolts (for nominal connection diameter DN 40)
  • Installation and operating instructions

Type key

Example:

Wilo-TOP‐RL 40/4

TOP-RL

Standard pump (screw-end pump or flange-end pump)

40/

Nominal connection diameter

4

Nominal delivery head [m] at Q = 0 m3 /h

Technical data

  • Permitted temperature range -20 °C to +130 °C, for short periods (2 h) to +140 °C
  • Mains connection 1~230 V, 50 Hz
  • Protection class IP X4D
  • Screwed connection or flange connection (depending on type) Rp 1. Rp 1¼ or DN 40
  • Max. operating pressure, standard version: 10 bar or 6/10 bar

Materials

  • Pump housing: Grey cast iron
  • Impeller: Plastic
  • Shaft: stainless steel
  • Bearing: Carbon, metal impregnated

Downloads

REACH regulation

Edition 2018-10
Page format 209.9 x 296.7 mm
Number of pages 4

PDF (581 kB)

Download

General overview 2019 International version

Article Number 2200591
Edition 2018
Version number 1
Page format 209.9 x 297.0 mm
Number of pages 74

PDF (42 MB)

Download

Product

PDF: Wilo-TOP-RL

Configure

Page selection

Format selection

Optional information

You can enter any personal information that you want to be displayed in the header.

Download