Contact

011 608 2780

Sinum Double Pump Unit D130 400V

Data sheet

Technical data
  • Rated current IN
    12.8 A
  • Rated power P2
    6.0 W
  • Protection class
    IP54
  • Interface
    RS485 (TIA-485A), optically insulated
  • Connection input
    G 1½
  • Connection output
    G 1½
  • Tank connection
    G1½-PN10-DIN-ISO228-1
  • Max. refill pressure
    6 bar
  • Min. refill pressure
    4 bar
  • Min. boiler output
    3300 kW
  • Max. boiler output
    10000 kW
  • Break tank volume V
    130 l
  • Maximum allowed limit of glycol in %
    50 %
Operating data
  • Min. operating pressure
    8
  • Max. operating pressure PN
    14 bar
  • Min. storage temperature
    5 °C
  • Max. storage temperature
    50 °C
  • Min. fluid temperature
    3 °C
  • Max. fluid temperature
    70 °C
  • Min. ambient temperature
    3 °C
  • Max. ambient temperature
    50 °C
Information for order placements
  • Net weight, approx. m
    153.00 kg
  • Make
    Wilo
  • Item no.
    2198873
  • Installation
    Horizontal

Tender text

For pressurisation, deaeration and topping up in sealed heating installations (acc. to EN12828) and chilled water (cooling) installations.

Sinums with pump units are used for storage of expansion water, deaeration and topping up your installation automatically as an integrated controlled unit carried out with state of the art micro-electronics. The Sinum balanced pressure expansion equipment is sized according to the total system volume and the boiler or chiller load. The Sinum vessel is 80% efficient irrespective of the static height of the system. It is the ideal solution for large installations or high installations where standard

diaphragm expansion equipment is limited.

Special features/Product advantages

  • Easy installation thanks to intuitive menu navigation in the HMI, large display and self-learning microprocessor.
  • Different operating modes guarantee continuous degassing.
  • Advanced technology ensures low power consumption, long service life and easy maintenance.
  • Improved convenience through volumetric controls and automatic topping-up during the heating and cooling cycles.
  • Modular design offers a high level of installation flexibility.
  • Optional: Integration in existing building management systems through digital and analogue outputs.
Technical data
  • Break tank volume V
    130 l
  • Installation
    Horizontal
  • Connectable
    yes
  • Digital control unit
    yes
  • Exchangeable membrane
    no
  • Min. operating pressure
    8
  • Max. operating pressure PN
    14 bar
  • Min. refill pressure
    4 bar
  • Max. refill pressure
    6 bar
  • Min. fluid temperature T
    3 °C
  • Max. fluid temperature T
    70 °C
  • Min. ambient temperature
    3 °C
  • Max. ambient temperature
    50 °C
  • Min. storage temperature
    5 °C
  • Max. storage temperature
    50 °C
  • Maximum allowed limit of glycol in %
    50 %
  • Mains frequency f
    50 Hz
  • Phase
    3
  • Rated voltage U
    400 V
  • Voltage tolerance
    ±10 %
  • Rated current IN
    12.8 A
  • Protection class
    IP54
  • Max. boiler output
    10000 kW
  • Min. boiler output
    3300 kW
  • Connection inlet
    G 1½
  • Connection outlet
    G 1½
  • Item no.
    2198873
  • EAN number
    4048482837901
  • Make
    Wilo
  • Net weight, approx. m
    153.00 kg

Ordering information

Information for order placements
  • Brand
    Wilo
  • Product description
    Sinum Double Pump Unit D130 400V
  • EAN number
    4048482837901
  • Article number
    2198873
  • Gross weight, approx. m
    188.0 kg
  • Net weight, approx. m
    153 kg
  • Overall length L
    540.0 mm
  • Height without packaging H
    1190 mm
  • Colour
    White
  • Packaging property
    Transport packaging
  • Packaging type
    Europallet
  • Number per layer
    1
  • Width without packaging L
    530.0 mm
  • Minimum order quantity
    1
  • Pieces per pallet
    1

Downloads

Wilo-

Article Number 2200594
Edition 2018-11
Version number 03
Page format 209.9 x 297.0 mm
Number of pages 328

PDF (45 MB)

Download