Search
Contact
E-mail
Catalogue creation
My favorites
Product comparison
CronoTwin-DL-E 50/170-7,5/2-R1 | Wilo
Similar to figure

CronoTwin-DL-E 50/170-7,5/2-R1

Article number: 2159461
Technical data
Tender text

Glanded twin-head pump with in-line design for pipe installation or installation on a base with built-in frequency converter for electronic control for constant or variable differential pressure (Δp-c/Δp-v), among other things.

Design:

  • Single-stage low-pressure centrifugal pump
  • Spiral housing in in-line design (suction and pressure ports with the same flanges in one line), flanges PN 16 – drilled acc. to EN 1092-2
  • Pressure measuring connections (R 1/8) for mounted differential pressure sensor (version ...-R1 without differential pressure sensor)
  • Pump housing and motor flange with cataphoretic coating as standard
  • Mechanical seal for water feed up to T=140 °C. A glycol admixture of 20 to 40% by vol. is permitted up to Tmax = +40 °C
  • Special mechanical seals for water-glycol mixtures deviating from the 20–40% glycol by volume and a fluid temperature of ≤ 40 °C or fluids other than water (additional charge).

Accessories:

  • Mounting brackets for fixing to the foundation
  • IR-Monitor
  • IF module PLR
  • IF module LON
  • IF module Modbus
  • IF module BACnet
  • IF module CAN
  • Control systems VR-HVAC/CCe-HVAC/SCe-HVAC
  • Differential pressure sensor (DDG) sets 0-10 V for pumps in version ...-R1

Standard equipment:

  • One-button manual operation level for:
    • Pump On/Off
    • Setpoint and speed adjustment
    • Selecting the control mode: Δp-c (constant differential pressure), Δp-v (variable differential pressure), PID controller, n-constant (constant speed)
    • Selection of operating mode in dual pump operation (main/standby operation, parallel operation)
    • Configuration of operating parameters
    • Fault acknowledgement
  • Pump display for displaying:
    • Control mode
    • Setpoint (e.g. differential pressure or speed)
    • Error and warning messages
    • Actual values (e.g. power consumption, actual value of the sensor)
    • Operating data (e.g. operating hours, energy consumption)
    • Status data (e.g. status of SSM and SBM relay)
    • Device data (e.g. pump name)

Additional functions:

  • Interfaces: Control input "Overriding Off", "External pump cycling", analogue input 0–10 V, 2–10 V, 0–20 mA, 4–20 mA for control mode (DDC) or for remote setpoint adjustment, analogue input 0–10 V, 2–10 V, 0–20 mA, 4–20 mA for actual value signal of the pressure sensor, Infrared interface for wireless communication with the operating and service unit Wilo-IR Stick/IR-Monitor, plug-in position for Wilo IF-Module for connecting to the building automation, configurable, potential-free fault and operating/ready message, interface for dual pump communication
  • Three-phase AC motor with frequency converter
  • Integrated dual pump management
  • Adjustable time interval for pump cycling
  • Integrated full motor protection
  • Different operating modes for heating mode (HV) or air-conditioning mode (AC)
  • Access disable
  • Different operation levels: Standard / Service
Operating Data
Min. fluid temperature Tmin -20 °C
Max. fluid temperature Tmax 140 °C
Min. ambient temperature Tmin 0 °C
Max. ambient temperature Tmax 40 °C
Maximum operating pressure PN 16 bar
Note on dimensioning 16 bar to 120 °C, 13 bar to 140 °C
Minimum efficiency index (MEI) ≥0.4
Drive
Mains connection
  • 3~380 V, 50/60 Hz
  • 3~400 V, 50/60 Hz
  • 3~440 V, 50/60 Hz
Motor efficiency class IE4
Power consumption P1 max 8400 W
Rated power P2 7.5 kW
Max current Imax 13.4 A
Max. speed nmax 2960 1/min
Interference emission EN 61800-3
Interference immunity EN 61800-3
Insulation class F
Protection class motor IP55
Motor protection PTC integrated
Materials
Pump housing Grey cast iron
Impeller Grey cast iron
Shaft Stainless steel
Shaft seal AQ1EGG
Lantern 5.1301/EN-GJL-250 KTL-coated
Installation dimensions
Pipe connection on the suction side DNs DN 50
Pipe connection on the discharge side DNd DN 50
Port-to-port length L0 340 mm
Ordering information
Brand Wilo
Product description CronoTwin-DL-E 50/170-7,5/2-R1
Net weight, approx. m 197 kg
Article number 2159461
Documents

Installation and operating instructions

Wilo-CronoLine-IL-E/DL-E/BL-E

Article Number 2160196
Edition 2022-08
Page format 209.9 x 297.0 mm
Number of pages 260
PDF (27 MB)

Certificate REACH

REACH Regulation

Edition 2021-05
Page format 209.9 x 297.0 mm
Number of pages 4
PDF (262 KB)

BIM/CAD

3D_DWG

DL-E50/170-7,5/2-R1

DWG (3 MB)

3D_STEP

DL-E50/170-7,5/2-R1

STP (3 MB)

2D_DWG_TOP

DL-E50/170-7,5/2-R1

DWG (19 KB)

2D_DWG_FRONT

DL-E50/170-7,5/2-R1

DWG (29 KB)

2D_DWG_RIGHT

DL-E50/170-7,5/2-R1

DWG (24 KB)

Services

With Wilo as your partner, you can not only be sure of choosing high-quality product solutions, but also of benefiting from a comprehensive, worry-free package of well thought-out services. We collaborate to develop a service concept tailored to your individual needs; with our expertise and personal consultancy, we make sure that the operation of your systems is as energy-efficient, reliable and economical as possible. All the while our competent Wilo service technicians are ready to assist you with fast, reliable and on-time support.

Read more

Recommended services

Commissioning
Commissioning Glanded pumps
    
2219391

High performance is our strength.

Entrust the Wilo commissioning-service with ensuring a smooth process when implementing new systems in your installations. We will happily accompany you throughout the commissioning process of our products and support you step-by-step. You will benefit directly from the advantages of our products and their performance in operation. Our qualified service technicians will familiarise you with all strengths to guarantee a safe and optimal start.

Why you should take advantage of our commissioning expertise:

The pump is part of a complex supply system, that is why the focus of professional installers during commissioning is primarily on the higher-level system technology. However, the optimal pump settings – as a part of the overall system – are crucial for energy consumption and therefore for the efficiency and operational reliability of the entire system.

The advantage of using professional installers is that they hand over a system to the customer which is energy efficient from the start and they do not have to acquire detailed knowledge of each control and pump series for this. This significantly reduces both energy costs and pump wear. The commissioning service provided by the Wilo service also includes instruction of the responsible building service engineer.