Your advantages
Wilo-SiFire EN

Your advantages

  • Pressure-loss optimised system designed in accordance with the EN 12845 Standard with electrical or diesel drive, jockey pump for maintaining system pressure
  • Flexible, modular and solid construction for safe transport and simple installation
  • Bypass volume flow for the protection of the pump with spacer coupling for simple maintenance
  • High-quality SC-Fire control prepared for BACnet and Modbus building management system integration
  • Special baseplate for minimal vibrations, cable laid in the construction in such a way as to ensure maximum reliability and service life

Series description
SiFire EN

Design

Pressure-boosting systems for firefighting according to EN 12845. Consists of 1 or 2 pumps, depending on the module, with horizontal baseplate - EN 733 - with spacer coupling, electric or diesel motor and a multistage, vertical electric jockey pump.

Application

Fully automatic water supply of fire-fighting systems with a sprinkler system in residential, commercial, public and industrial buildings, as well as hotels, hospitals and department stores.

Equipment/function

  • One or two pumps with a horizontal base frame from the series 32-200 to 150-315, with an IE-equivalent standard motor or diesel motor
  • With a diaphragm installed directly on the main pump housing to prevent overheating in the event of zero flow
  • Jockey pump of Medana CV1-L series with pressure switch and vertical pressure tank 20 l, PN 16
  • One switch cabinet per pump, fixed to a robust support structure. SC Fire model: E for the electric motor and D for the diesel motor, both equipped with Smart Controller, plus J for the jockey pump
  • Base frame made of electro-galvanised steel with height-adjustable holder for the outlet manifold
  • Pipework made of steel; painted with epoxy resin. Manifold with flanges
  • Shutting gate with safety lock on the discharge side of each pump
  • Swing check valve on the discharge side of each pump
  • A circuit with dual pressure switch, pressure gauge, swing check valve, valve for the main pump and standby pump for automatic start
  • Concentric cone on the discharge side of the main and standby pump, for speed limitation according to the parameters specified in EN 12845
  • DN 2" connection for the supply tank of the pumps
  • Pressure measurement on the discharge side
  • Only for the model with diesel motor:
    • Vibration damping sleeve on the discharge side of the pump
    • Vibration damper under the base frame of the pump
    • Fuel tank with level sensor and sufficient volume for six hours of autonomous operation
    • 2 or 4 batteries on the base frame and battery charger at the SC Fire switch cabinet
  • Accessories upon request: Note on fluids: Approved fluids are generally waters which do not attack the materials used, neither chemically nor mechanically, and do not contain any abrasive or long-fibre constituents. System in accordance with EN 12845
    • Horizontal 500 l supply tank, with float valve and pressure switch for LL-alarm (water shortage)
    • Flow meter: Kit with eccentric cone on the suction side, complete with butterfly valve with hand lever or handwheel
    • Vacuum gauge with valve
    • Valves with electrical contact
    • Vibration damping sleeve for the manifold
    • Remote control panel for transmitting level A and level B alarms
    • Density meter for battery
    • Spare parts kit for the diesel motor
    • Silencer (30 dBA) for the diesel motor
    • Hydraulic heat exchanger for the diesel motor

Typekey

Example:

Wilo-SiFire EN 40/200-180-7.5/10.5/0.55 EDJ

SiFire

Compact pressure boosting system for fire fighting equipment

EN

in acc. with EN 12845

40/200

Type of main pump

180

Actual impeller diameter of the main pump

7.5

Power of the electric motor [kW]

10.5

Power of the diesel motor [kW]

00:55

Power of the motor for the jockey pump [kW]

EDJ

Configuration

E

An electric pump

D

A diesel pump

J

A jockey pump

Technical data

  • Mains connection 3~400 V, 50 Hz (1~230 V, 50 Hz for the control panel of the diesel pump)
  • IE-equivalent standard motors, diesel motor with direct injection or turbo diesel motor with air or water cooling
  • Max. ambient temperature +4°C to +40°C (+10°C to +40°C, if a diesel pump is installed)
  • Max. fluid temperature +40°C
  • Max. operating pressure 10 or 16 bar
  • Max. inlet pressure 6 bar
  • Volume flow 10 m³/h to 750 m³/h
  • Max. delivery head 128 m
  • Nominal connection diameters on the pressure side DN 65 to DN 250
  • Nominal connection diameters on the intake side DN 50 to DN 200
  • Switch cabinet protection class IP54
  • Main/standby pump with horizontal base plate in accordance with EN 733
  • With epoxy resin painted piping and hydraulic connections
  • Permitted fluids:Note on fluids: Approved fluids are generally waters which do not attack the materials used, neither chemically nor mechanically, and do not contain any abrasive or long-fibre constituents. System in accordance with EN 12845
    • Non-aggressive, clean water
    • Fire water

Materials

For the pump with a horizontal base frame, depending on the model

  • Impellers made of bronze CuSn10 or CuAl10Fe5Ni5 or stainless steel AISI 316/ 1.4401
  • Pump housing made of grey cast iron EN-GJL-250
  • Shaft made of stainless steel AISI420/1.4021 or AISI 431/ 1.4057
  • Neck rings made of stainless steel AISI316L/1.4409 or bronze

For the jockey pump

  • Impellers made of stainless steel AISI 304/ 1.4301
  • Pump housing made of stainless steel AISI304/1.4301
  • Shaft made of stainless steel AISI 304/ 1.4301
  • O-ring seals made of EPDM

Construction

  • Base frame: Manufactured from profiles consisting of electro-galvanised steel with brackets for the switch cabinets and the outlet manifold. Special square holes at the bottom for forklift trucks, as well as integrated hooks for lifting slings. Side profiles at the top on each side to enhance the rigidity of the system when moving and lifting.
  • Plastic cover at the rear which provides visual access to the valve position and pressure gauge.
  • Pipework: Complete pipework with flanges made of epoxy resin painted steel, suitable for the connection of all common piping materials; the dimensions of the pipework must correspond to the overall hydraulic performance of the pressure boosting system
  • Pumps: 1 or 2 pumps with horizontal base frame - EN 733 - with spacer coupling, electric or diesel motor.
  • • Back-pull-out model to ensure the internal parts of the pump are easy to access without having to move the motor or piping.
  • Valves: The main pumps are fitted with a shut-off valve and non-return valve on the discharge side, both of which are painted with epoxy resin and adapted for a flange connection.
  • Diaphragm pressure vessel: Diaphragm pressure vessel 20 l/PN16, on the discharge side of the jockey pump, with drain plug.
  • Tank: The fuel tank is made of metal painted with epoxy resin and is located behind the bracket of the switch cabinet
  • Sensors and display: 2 pressure switches, 2/16 bar per pump, on the discharge side, for activating the pump start via the SCFire controller and regulator. The discharge side pressure gauge (∅ 63 mm) is located in the middle of the rear panel.
  • Controller: The system is equipped as standard with a separate switchgear/control device (SC Fire) for the electric or diesel motor and a switchgear/control device for the jockey pump.

Scope of delivery

  • Factory-mounted, ready-for-installation pressure boosting system, which has been checked for functionality and impermeability
  • Installation and operating instructions
  • Required accessories on request

Consulting guide

Inlet pressure

The maximum inlet pressure must be taken into account when designing the system configuration (see Technical data). The maximum permissible inlet pressure is calculated from the maximum operating pressure of the system minus the maximum delivery head of the pump at Q = 0. For sprinkler systems in accordance with EN 12845, the water pressure should not exceed 12 bar. In sprinkler systems with a pronounced slope, in which the difference in height between the highest and lowest sprinkler is more than 45 m, the water pressure can be higher than 12 bar at the pump outlet or in the piping, provided that all of the system components are designed for this pressure level.

Installation of the pressure boosting pump under suction conditions.

For each main pump, it is necessary to install a supply tank with connection to the discharge pipe above the pump.

Volume flow

Up to 750 m³/h (208 l/s) system configuration for each main pump.

Operation

The operating logic for the fire extinguishing unit is based on the cascade calibration of the pressure switches for starting the pump.

The jockey pump is started and stopped automatically by a pressure switch. It is designed in such a way that not only individual sprinklers are supplied with fluid and pressure, but the entire system. This ensures the main pump is prevented from being started and that the system remains pressurised. If a lower pressure value is caused by the demand for water, which is not compensated by the jockey pump, the main and standby pump are started one after the other. The system starts automatically, it can be stopped manually using the switch on the front of the control panel.

Documents

Installation and operating instructions

Wilo-MVIL

Article Number 4086201
Edition 1502
Number of pages 13
PDF (934 KB)

Wilo-Control SC-Fire Diesel

Article Number 2541367
Edition 1510
Number of pages 34
PDF (1 MB)

Wilo-Control SC-Fire Electric

Article Number 2539954, 2541365, 2541366
Edition 1510
Number of pages 32
PDF (2 MB)

Wilo-Control SC-Fire Jockey

Number of pages 10
PDF (727 KB)

Wilo-SiFire EN

Article Number 4188030
Edition 2019-12
Number of pages 108
PDF (9 MB)

Wilo-MVIL

Article Number 4086201
Edition 1502
Number of pages 148
PDF (6 MB)

Wilo-MVIL

Article Number 4086201
Edition 1502
Number of pages 13
PDF (1 MB)

Wilo-Control SC-Fire Electric

Article Number 2539954, 2541365, 2541366
Edition 1510
Number of pages 31
PDF (1 MB)

Wilo-Priming tank 500 L

Article Number 4228982
Edition 2019-05
Number of pages 451
PDF (18 MB)
Product selection
Number of results: 433
29 … 756 m³/h
[432]
Product descriptionSystem output without standby pump QMaximum operating pressure PNGross weight, approx. mArticle number
SiFire-EN-100/200-212-47,7DJ
250 m³/h
16 bar
1251 kg
4241666
SiFire-EN-100/200-219-55/55EEJ
387 m³/h
10 bar
1682 kg
4183978
SiFire-EN-100/200-219-55/66EDJ
387 m³/h
10 bar
1960 kg
4184047
SiFire-EN-100/200-219-55E
387 m³/h
10 bar
973 kg
4183702
SiFire-EN-100/200-219-66D
387 m³/h
10 bar
920 kg
4183840
SiFire-EN-100/200-219-66DJ
387 m³/h
10 bar
968 kg
4183909
SiFire-EN-100/200-222-55/55EEJ
323 m³/h
16 bar
1790 kg
4241730
SiFire-EN-100/200-222-55/66EDJ
323 m³/h
16 bar
2084 kg
4241780
SiFire-EN-100/200-222-55E
323 m³/h
16 bar
1317 kg
4241442
SiFire-EN-100/200-222-55EJ
323 m³/h
16 bar
1361 kg
4241517
SiFire-EN-100/200-222-66D
323 m³/h
16 bar
1273 kg
4241592
SiFire-EN-100/200-222-66DJ
323 m³/h
16 bar
1402 kg
4241667
SiFire-EN-100/200-228-66D
321 m³/h
16 bar
1128 kg
4241593
SiFire-EN-100/200-228-66DJ
321 m³/h
16 bar
1257 kg
4241668
SiFire-EN-100/200-228-75E
321 m³/h
16 bar
1356 kg
4241443
SiFire-EN-100/200-228-75EJ
321 m³/h
16 bar
1400 kg
4241518
SiFire-EN-100/250-233-55/55EEJ
348 m³/h
10 bar
1710 kg
4183979
SiFire-EN-100/250-233-55/66EDJ
348 m³/h
10 bar
1994 kg
4184048
SiFire-EN-100/250-233-55E
348 m³/h
10 bar
987 kg
4183703
SiFire-EN-100/250-233-55EJ
348 m³/h
10 bar
1040 kg
4183772
SiFire-EN-100/250-255-90E
276 m³/h
16 bar
1550 kg
4241444
SiFire-EN-100/250-255-90EJ
276 m³/h
16 bar
1594 kg
4241519
SiFire-EN-100/250-255-100D
276 m³/h
16 bar
1148 kg
4241594
SiFire-EN-100/250-255-100DJ
276 m³/h
16 bar
1277 kg
4241669
SiFire-EN-100/250-260-100D
273 m³/h
16 bar
1148 kg
4241595
SiFire-EN-100/250-260-100DJ
273 m³/h
16 bar
1277 kg
4241670
SiFire-EN-100/250-260-110E
273 m³/h
16 bar
1600 kg
4241445
SiFire-EN-100/250-260-110EJ
273 m³/h
16 bar
1644 kg
4241520
SiFire-EN-100/250-267-109D
273 m³/h
16 bar
1153 kg
4241596
SiFire-EN-100/250-267-109DJ
273 m³/h
16 bar
1282 kg
4241671
SiFire-EN-100/250-267-110E
273 m³/h
16 bar
1681 kg
4241446
SiFire-EN-100/250-267-110EJ
273 m³/h
16 bar
1725 kg
4241521
SiFire-EN-100/250-280-132E
273 m³/h
16 bar
1401 kg
4241447
SiFire-EN-100/250-280-132EJ
273 m³/h
16 bar
1445 kg
4241522
SiFire-EN-100/250-280-145D
273 m³/h
16 bar
1304 kg
4241597
SiFire-EN-100/250-280-145DJ
273 m³/h
16 bar
1433 kg
4241672
SiFire-EN-100/315-285-132E
421 m³/h
16 bar
1595 kg
4241448
SiFire-EN-100/315-285-132EJ
421 m³/h
16 bar
1639 kg
4241523
SiFire-EN-100/315-285-145D
421 m³/h
16 bar
1351 kg
4241598
SiFire-EN-100/315-285-145DJ
421 m³/h
16 bar
1480 kg
4241673
SiFire-EN-100/315-296-145D
345 m³/h
16 bar
1496 kg
4241599
SiFire-EN-100/315-296-145DJ
345 m³/h
16 bar
1625 kg
4241674
SiFire-EN-100/315-296-160E
345 m³/h
16 bar
1631 kg
4241449
SiFire-EN-100/315-296-160EJ
345 m³/h
16 bar
1675 kg
4241524
SiFire-EN-100/315-302-160E
349 m³/h
16 bar
1712 kg
4241450
SiFire-EN-100/315-302-160EJ
349 m³/h
16 bar
1756 kg
4241525
SiFire-EN-100/315-302-197D
349 m³/h
16 bar
1496 kg
4241600
SiFire-EN-100/315-302-197DJ
349 m³/h
16 bar
1625 kg
4241675
SiFire-EN-100/315-318-197D
360 m³/h
16 bar
1496 kg
4241601
SiFire-EN-100/315-318-197DJ
360 m³/h
16 bar
1625 kg
4241676