Special features/product advantages

  • Energy savings due to integrated electronic power adjustment
  • Optional interfaces for bus communication using plug-in IF-Modules
  • Simple operation due to tried-and-tested Green Button Technology and display
  • Integrated full motor protection (PTC thermistor sensor) with trip electronics
  • Meets user requirements due to performance and main dimensions in accordance with EN 733 (DIN for standard pumps)

Series description

Design

Electronically controlled glanded single pump in monobloc design with flange connection and automatic power adjustment.

Application

Pumping of heating water (acc. to VDI 2035), cold water and water/glycol mixtures without abrasive substances in heating, cold water and cooling systems.

Type key

ExampleBL-E 40/160-5.5/2-R1
BL-EMonobloc pump with electronic control
40Nominal diameter DN of the pipe connection (pressure port)
160Nominal impeller diameter in mm
5.5Rated motor power P2 in kW
2Number of poles
-R1Version without differential pressure sensor

Technical data

  • Minimum Efficiency Index (MEI) ≥ 0.4
  • Permissible temperature range of -20 °C to +140 °C
  • Mains connection
    • 3~440 V -5/±10 %, 50/60 Hz
    • 3~400 V ±10 %, 50/60 Hz
    • 3~380 V -5/±10 %, 50/60 Hz
  • Protection class IP 55
  • Nominal diameter DN 32 to DN 125
  • Max. operating pressure 16 bar (120 °C)

Description/design

Single-stage low-pressure centrifugal pump in block design, with axial suction port and radially arranged pressure port with

  • Mechanical seal
  • Flange connection with pressure measuring connection R 1/8
  • Lantern
  • Coupling
  • Drive with integrated electronic speed control

Materials

  • Pump housing and lantern: Standard: EN-GJL-250; optional: Spheroidal cast iron EN-GJS-400-18-LT
  • Impeller: Standard: EN-GJL-200; optional: Bronze CuSn 10
  • Shaft: 1.4122
  • Mechanical seal: AQEGG other mechanical seals on request

Equipment/function

Operating modes

  • Δp-c for constant differential pressure
  • Δp-v for variable differential pressure
  • PID control
  • Control mode (n = constant)

Manual operation level

  • Green button and display

Manual functions

  • Differential pressure setpoint setting
  • Setting the speed (manual control mode)
  • Setting the operating mode
  • Setting the pump ON/OFF
  • Configuration of all operating parameters
  • Fault acknowledgement

External control functions

  • "Overriding Off" control input
  • Analogue input 0 – 10 V, 0 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 2 – 10 V, 4 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 0 – 10 V for actual value signal from pressure sensor
  • Analogue input 2 – 10 V, 0 – 20 mA, 4 – 20 mA for actual value signal from pressure sensor

Signal and display functions

  • Collective fault signal SSM
  • Collective run signal SBM

Data exchange

  • Infrared interface for wireless data exchange with IR-Monitor/IR-Stick
  • Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation

Safety functions

  • Full motor protection with integrated trip electronics
  • Access disable

Dual pump management (2 x single pump; Y-piece application only)

  • Main/standby operation (automatic fault-actuated switchover)
  • Pump cycling main/standby operation after 24 hours
  • Parallel operation

Scope of delivery

  • Pump
  • Installation and operating instructions

Options

  • Variant …-R1 without differential pressure sensor
  • ...-L1 variant with bronze impeller (at additional charge)
  • ...-H1 variant with housing made of spheroidal cast iron (at additional charge)
  • ...-S1/-S2 variant with special mechanical seal (at additional charge)

Accessories

  • Supporting blocks for installation on a base
  • IR-Monitor, Wilo-IR-Stick
  • IF-Module PLR for connecting to PLR/interface converter
  • IF-Module LON for connection to the LONWORKS network
  • IF-Module BACnet
  • IF-Module Modbus
  • CAN IF-Module
  • Control system VR-HVAC
  • Control system CCe-HVAC
  • Control system SCe-HVAC
  • Differential pressure sensor (DDG)

General notes - ErP (ecological design-) directive

The benchmark for most efficient water pumps is MEI ≥ 0.70The efficiency of a pump with a trimmed impeller is usually lower than that of a pump with the full impeller diameter. The trimming of the impeller will adapt the pump to a fixed duty point, leading to reduced energy consumption. The minimum efficiency index (MEI) is based on the full impeller diameter.The operation of this water pump with variable duty points may be more efficient and economic when controlled, for example, by the use of a variable speed drive that matches the pump duty to the system.Information on benchmark efficiency is available at www.europump.org/efficiencychartsPumps with power consumption > 150 kW or a volume flow QBEP < 6 m3/h are not subject to the Ecodesign Directive for water pumps. Therefore, no MEI value is shown.

Duty chart

Pump curves

Product

Approved fluids (other fluids on request)

Heating water (in accordance with VDI 2035)

Water-glycol mixtures (for 20-40 vol.% glycol and fluid temperature ≤ 40 °C)

Cooling and cold water

Heat transfer oil

Special version at additional charge

Permitted field of application

Standard version for operating pressure pmax

16 bar (up to +120 °C) bar

Special version for operating pressure pmax

- bar

Temperature range at max. ambient temperature +40 °C

-20...+140 °C (depending on the fluid)

Max. ambient temperature

+40 °C

Installation in closed buildings

Outdoor installation

-

Pipe connections

Nominal connection diameters DN

32 - 150

Flanges (according to EN 1092-2)

PN 16 (PN25 on request)

Materials

Pump housing

EN-GJL-250

Lantern

EN-GJL-250

Impeller

EN-GJL-200

Impeller (special version)

G-CuSn10

Pump shaft

1.4122

Mechanical seal

AQEGG

Other mechanical seals

On request

Electrical connection

Mains connection

3~380 V, 50/60 Hz

Speed range

750-2900 rpm

Motor/electronics

Motor technology

Asynchronous motor

Integrated full motor protection

Protection class

IP 55

Insulation class

F

Emitted interference

EN 61800-3

Interference resistance

EN 61800-3

Residual-current protection device (RCD)

Installation options

Pipe installation (≤ 15 kW motor power)

Support-bracket mounting

Downloads

General overview

Edition 2017
Page format A4
Number of pages 72

PDF (46 MB)

Download

Wilo-IL-E/DL-E/BL-E

Article Number 2112769-72, 2122801
Edition 1512
Version number 01
Page format A4
Number of pages 72

PDF (9 MB)

Download

Product

Tipps & Guides

General Overview 2018

PDF: Wilo-CronoBloc-BL-E

Configure

Page selection

Format selection

Optional information

You can enter any personal information that you want to be displayed in the header.

Download