Series description

Design

Compact particle separator delivered as kit and easy to install. Kit consisting of mechanical and hydraulic components: Circulation pump, particle separator, drain valve, automatic volume flow limiter, ventilation unit, switchbox for monitoring the circulation pump. For wall fixation or floor installation (type-dependent). Suction connection and pressure connection, as well as the mains connection are performed onsite. Manual emptying of the system.

Application

WILO-SiClean removes magnetic and non-magnetic particles from heating systems via natural physical phenomena. The ventilation unit can also be used to expel micro bubbles. For installation in commercial properties (office buildings, hotels, hospitals, shopping centres, schools,...) and heating and air conditioning systems for district heating.

Type key

Example:Wilo-SiClean 2
SiCleanStandard version, manually operated, with an inline circulation pump with glandless technology
2Size of the set

Special features/product advantages

  • Removal of magnetic and non-magnetic particles from the medium and venting of micro bubbles
  • High cleaning efficiency due to physical effects (gravity, filtration, magnetic effects, pressure reduction effect)
  • Easy to use due to ease of installation, maintenance, and simplified settings
  • Corrosion-resistant thanks to stainless steel particle separator

Equipment/function

  • Circulation pump type: WILO-Yonos PICO (SiClean 0.5/1/2/3/4), Wilo-Yonos MAXO (SiClean 5)
  • Anti-corrosive, hydraulic components made of stainless steel
  • Fabric-reinforced hoses connected to inlet and outlet of the particle separator. Hoses connected to the return pipe, in bypass for smaller, low-cost connections and lower pressure losses
  • Pre-assembled venting unit for the expulsion of micro-bubbles
  • Movable magnetic rods for efficient separation of iron oxide particles
  • Volume flow limiter for automatic adjustment of the flow rate.
  • Manual purge valve for quick and easy draining of collected particles
  • Switchbox for monitoring the circulation pump

Scope of delivery

  • Particle separator Wilo-SiClean (pre-assembled kit)
  • Switchbox
  • Wilo-SiClean installation and operating instructions
  • Circulation pump installation and operating instructions

Installation drawings

Installation drawing

Integration of Wilo-SiClean in the heating system is performed in each case as a bypass installation in the return of the heating circuit.

1 Wilo-SiClean

2 Heat generator

3Heating circuit feed

4Heating circuit return

Downloads

General overview

Edition 2017
Page format A4
Number of pages 72

PDF (46 MB)

Download

Wilo-SiClean

Article Number 4192809
Edition 1504
Version number 01
Page format A4
Number of pages 16

PDF (766 kB)

Download

Product

Tipps & Guides

General Overview 2018

PDF: Wilo-SiClean

Configure

Page selection

Format selection

Optional information

You can enter any personal information that you want to be displayed in the header.

Download