Article number: 29993553
Technical data
Hydraulic data
Max. operating pressure p 10 bar
Pipe connection on the discharge side DNd R 1¼
Pipe connection on the suction side DNs R 1¼
Number of standby pumps 1
Number of operating pumps 1
Min. fluid temperature Tmin 3 °C
Max. fluid temperature Tmax 60 °C
Min. ambient temperature Tmin 5 °C
Max. ambient temperature Tmax 40 °C
Control
Rated voltage U 220-230 V
Mains frequency f 50 Hz
Protection class switchgear IP54
Motor data
Insulation class F
Protection class IP55
Rated power P2 0.75 kW
Motor efficiency 50% ηM 50% 75.6 %
Motor efficiency 75% ηM 75% 79.6 %
Motor efficiency 100% ηM 100% 80.7 %
Materials
Pump housing Stainless steel
Impeller Stainless steel
Shaft Stainless steel
Mechanical seal BQ1E3GG
Gasket material EPDM

ISAR MODH1-2.../SCe-EM Dimension Drawing

Dimensions H 940 mm
Dimensions H1 185 mm
Dimensions H2 359 mm
Dimensions L1 250 mm
Dimensions P 912 mm
Dimensions P1 337 mm
Dimensions P3 300 mm
Dimensions P4 0 mm
Dimensions H3 85 mm
Dimensions HS 400 mm
Dimensions LS 600 mm
Pipe connection on the discharge side DNd R 1¼
Pipe connection on the discharge side DNd PN 10
Pipe connection on the suction side DNs R 1¼
Pipe connection on the suction side DNs PN 10
Dimensions L 600 mm
Dimensions TS 210 mm
Dimensions X 430 mm

SCe-EM Wiring Diagram

3~ 400 V, 50 Hz, 3~ 380-460 V, 60 Hz

SCe-EM Wiring Diagram

Product data
Brand Wilo
Product description ISAR MODH1-2CH1-L-206/SCe
Article number 29993553
EAN number 5013608002654
Colour Green/black/silver
Minimum order quantity 1
Date of sales availability 2021-06-01
Packaging
Packaging type One-way pallet
Packaging property Transport packaging
Pieces per pallet 1
Number per layer 1
Dimension, weight
Length with packaging 800 mm
Length L 524 mm
Height with packaging 980 mm
Height H 830 mm
Width with packaging 1200 mm
Width W 635 mm
Gross weight, approx. m 74 kg
Net weight, approx. m 44 kg
Tender text

Compact pressure boosting system according to DIN 1988 and DIN EN 806, for indirect connection. Consisting of non self-priming, switched in parallel, horizontal stainless steel high-pressure multistage centrifugal pumps. Ready for connection with stainless steel pipework, mounted on a base frame, including control device with all necessary measurement and adjustment equipment.

For fully automatic water supply and pressure boosting in residential, commercial and public buildings, hotels, hospitals, department stores and for industrial systems.

For pumping drinking water, process water, cooling water or other service water, which does not affect the materials used, neither chemically nor mechanically, and does not contain any abrasive or long-fibre constituents. The ISAR booster is fully compliant to The Water Supply (Water Fittings) Regulations 1999 (Regulation 4) and is suitable for safe drinking water applications

Special features/product benefits

  • High operational reliability, thanks to system with one, two or three horizontal multistage CH1-L pumps with stainless steel hydraulics
  • Easy installation and maintenance thanks to special, flexibly adjustable connections to manifolds
  • Easy commissioning and operation with the Smart Controller
  • Drinking water approval (reg 4) for pumps with components made of stainless steel that come into contact with the fluid

Equipment/function

  • 2 or 3 CH1-L pumps per system
  • Components that come in contact with the fluid are corrosion-resistant
  • Electrogalvanized base frame with height-adjustable vibration absorbers for insulation against structure-borne noise
  • Stop valve on every pump on the suction and discharge sides
  • Non-return valve, pressure side
  • Pressure sensor, on the discharge side
  • Low-water cut-out switchgear on suction manifold
  • Pressure gauge, discharge side
  • Diaphragm pressure vessel (8 l/PN 10)
  • SCe comfort control device, maximum degree of control performance with symbol-based LCD display, simple navigation with clear menu and Green Button Technology for setting parameters for controlling the electronic pumps with frequency converters
  • Ready for integration into building automation with the SCe switchgear via standard Modbus RTU

Operation / display

  • LC display (backlit) for display of the operating data, controller parameters, operating statuses of the pumps, error messages and history memory
  • Menu navigation with symbols and menu numbers
  • LEDs for display of the system status (operation/fault)
  • Factory-preset parameters for easy commissioning/start
  • Setting of operating parameters and acknowledgement of fault messages using Green Button Technology
  • Lockable main switch
  • Operation with/without standby pump selectable by customer service
  • Elapsed time indicator for each pump and for entire system
  • Switching cycle counter for each pump and for entire system
  • Fault memory for the last 16 faults

Monitoring

  • Actual value of the system is output via a 0 – 10 volt analogue signal for external measurement/display applications, 10 volts correspond to the final sensor value
  • 4 – 20 mA sensor signal (conductivity test of the sensor cable) for control variable actual value
  • The pump mains power feed is protected via the circuit breaker
  • Automatic switchover to standby pump in the event of an operating pump fault
  • Monitoring of maximum and minimum system values with adjustable time delays and limits
  • Zero-flow test for switching off the system when no water is being drawn off (adjustable parameters)
  • Pipe filling function for filling empty pipes (initial filling of the consumer network)
  • Protection against low water level via contact, e.g. for float switch or pressure switch
  • Automatic shutdown of pumps if fault occurs or operation at preset emergency operation speed

Interfaces

  • Potential-free contacts for SBM/SSM collective operation and collective fault signals
  • Logic reversal can be applied to SBM and SSM
  • Contacts for external on/off, low water and second setpoint
  • External on/off via contact for deactivation of the system's automatic mode

Accessories

Accessories can be ordered optionally. Factory installation or retrofitting after technical checks.

Recommended accessories (to be ordered separately)

  • Flexible connection pipes or compensators
  • Threaded caps for systems with threaded manifold
  • BACnet activation code
Operating Data
Number of pumps 2
Fluid temperature T 3 °C
Ambient temperature T 5 °C
Maximum operating pressure PN 10 bar
Maximum inlet pressure p inl 6 bar
Control
Mains frequency f 50 Hz
Phase 1
Rated voltage U 220-230 V
Protection class switchgear IP54
Motor data
Rated power P2 0.75 kW
Rated voltage U 230 V
Rated current IN 3.4 A
Rated speed n 2900 1/min
Insulation class F
Protection class motor IP55
Materials
Pump housing Stainless steel
Impeller Stainless steel
Shaft Stainless steel
Shaft seal BQ1E3GG
Gasket material EPDM
Pipework material Stainless steel
Installation dimensions
Pipe connection on the suction side DNs R 1¼
Pipe connection on the discharge side DNd R 1¼
Ordering information
Brand Wilo
Product description ISAR MODH1-2CH1-L-206/SCe
Net weight, approx. m 44 kg
Article number 29993553
Documents

Installation and operating instructions

Wilo-Control SC-Booster (SC, SC-FC, SCe)

Article Number 2535460
Edition 1809
Number of pages 1795
Language ar, bg, cs, da, de, el, en, es, et, fi, fr, hr, hu, it, lt, lv, nl, no, pl, pt, ro, ru, sk, sl, sr, sv, tr, uk, zh
PDF (44 MB)

ISAR MODH 1 Maintenance Manual

Article Number CD_SE085
Edition 2018-XX
Number of pages 10
Language en
PDF (1 MB)

ISAR MODH 1 O & M

Article Number CD_TE0080
Edition 2018-XX
Number of pages 22
Language en
PDF (1 MB)