Drinking water circulation with temperature monitoring for maximum hygiene.

Your advantages
Wilo-SiFresh

Drinking water circulation with temperature monitoring for maximum hygiene.

Circulation, continuous temperature monitoring and water exchange within 72 hours enable the Wilo-SiFresh cold drinking water system to provide the highest standard of drinking water hygiene in accordance with DIN EN 806-2. The compact system has an integrated Wilo-Stratos MAXO-Z and a convenient operating unit with central control for the temperature and water exchange intervals. With only one central flushing station, the effort required for installation and maintenance is comparatively low. The system should be combined with flow-through cooling to maintain the temperature even more efficiently. Depending on the structural conditions and utilisation behaviour, the flushing volume required to maintain the temperature and exchange water can be reduced by up to 90%.


Your advantages

  • Continuous temperature monitoring, circulation and individually programmable time intervals for the water exchange ensure highest standard of drinking water hygiene
  • Display of temperature data for the last 24 hours and quantities of water drawn for the last 7 days
  • Compact system with central control for the temperature, water exchange intervals and easy maintenance
  • Easy commissioning via intuitive operating elements, a large display and Green Button Technology
  • Optional: can be combined with flow-through cooling for efficient temperature maintenance
  • State-of-the-art interfaces that enable integration into the building automation
  • Pre-assembled ball valve for shutting off the water circulation for maintenance tasks
Series description

Design

Drinking water circulation system ready for connection with integrated circulator with stainless steel housing and flushing device

Application

Drinking water circulation for hygienic provision and saving of drinking water in connection with flow-through cooling.

Equipment/function

  • Menu-prompted operation and display
  • Adjustment of max. potable water temperature
  • Setting a timed flushing interval
  • Integrated temperature sensors for continuous temperature monitoring
  • Retrofittable interface modules for communication and integration into the building automation system

Control mode

  • Δp-c for constant differential pressure

Optional functions

  • Q-Limitmax. for limiting the maximum volume flow
  • Q-Limitmin. for limiting the minimum volume flow
  • No-Flow Stop (zero-flow-deactivation)

Manual settings

  • Setting the related operating parameters
  • Pump venting function
  • Key lock for disabling the settings
  • Function for resetting the factory settings or the saved restoration points (parameter sets)
  • Parameterising the binary inputs
  • Parameterising the relay output

External interfaces and their functions

2 x digital inputs:

  • For potential-free control outputs or switch
  • Parametrisable functions:
    • Overflow monitoring
    • Ext. Off
    • Ext. Min
    • Ext. Max
    • MANUAL (BMS-OFF)
    • Key lock

Signal and display functions

  • Display status operation display:
    • Setpoint
    • Actual delivery head
    • Actual volume flow
    • Power consumption
    • Electric consumption
    • Temperature
  • Status display LED:
    • Faultless operation (green LED)
    • Pump communication (blue LED)
  • Display status of display fault (display red):
    • Error codes and error description in full text
    • Remedial measures
  • Display status of display warning (display yellow):
    • Warning codes and description of the warning in full text
    • Remedial measures
  • Display status process indicator (display blue):
    • System flush (water exchange)
    • Pump venting
    • Update procedure
  • Display BMS communication (display blue):
    • Summary of the active BMS parameters (baud rate, address...)
  • Collective fault signal SSM (potential-free changeover contact)

Typekey

Example:

Wilo-SiFresh

Wilo-

Brand name

SiFresh

Drinking water circulation system

Technical data

  • Fluid temperature: Drinking water +2 °C ... +65 °C
  • Ambient temperature: 0 °C ... +40 °C
  • Mains connection 1~230 V, 50/60 Hz
  • Screwed connection: Rp ¾"
  • Max. operating pressure: 10 bar

Materials

High-efficiency pump:

  • Bearing: Carbon-graphite
  • Impeller: PPS-GF40
  • Pump housing: Stainless steel
  • Shaft: 1.4122, DLC-coated

PT1000 temperature sensor immersion sleeves:

  • Stainless steel

Solenoid valve:

  • Stainless steel

Pipework:

  • Stainless steel

Ball valve:

  • Stainless steel

Scope of delivery

  • Drinking water circulation system ready for connection
  • Fixation material
  • 2x ball valve
  • Installation and operating instructions
Documents

Installation and operating instructions

Wilo-SiFresh

Article Number 4261502
Edition 2023-09
Number of pages 272
Language de, en, fr, it, nl
PDF (7 MB)

Group Statement

Group Statement REACH

Edition 2021-05
Number of pages 5
Language language neutral
PDF (279 KB)

CE

CE 2223825-02

Number of pages 6
Language language neutral
PDF (282 KB)
Product selection
Product descriptionMains connectionRated power P2Gross weight, approx. mArticle numberPrice (excl. VAT)
SiFresh
1~230 V, 50/60 Hz
0.26 kW
28 kg
4261503
on request