Suche
Kontakt
E-Mail
Katalogerstellung
Meine Favoriten
Produktvergleich
Wilo-Trennsystem Basic | Wilo
Your advantages
Wilo separation system Basic

Your advantages

  • The ready-to-plug system and compact design with various hydraulic connection options allow for an easy installation
  • Convenient operation and simple setting functions provided by electronic functions HiControl 1
  • Integrated self-protection routines ensure a high level of reliability
  • A break tank with safety device provides hygienic safety in accordance with EN 1717 Fluid category 5
  • Easy maintenance through direct access to the system components
Series description
Wilo separation system Basic

Design

Automatic drinking water separation system

Application

The drinking water separation system is designed for applications where a hygienically clean separation of public water supplies is required:

  • Animal drinking troughs
  • Sports ground irrigation
  • Garden irrigation

Equipment/function

Ready for connection module with compact construction, consisting of:

  • HiMulti 3 P self-priming centrifugal pump, mounted on a base frame with oscillation absorbers
  • 11 l replenishment reservoir for fresh water replenishment with float valve
  • Connection on the discharge side, Rp 1" hose
  • Connection for municipal water supply network R ¾"
  • 1.5 m mains connection cable and plug
  • Potential-free contact for optional external alarm or fault message available
  • Electronic control device with integrated switch-off quantity detection and dry-running protection

Typekey

Example:

Wilo-TRSB1-25 EM

Wilo

Brand name

TRSB

Basic separation system

1

Product level

2

Rated flow rate Q in m³/h

5

Number of impellers

EM

Single-phase

Technical data

  • Mains connection: 1~230 V, 50 Hz
  • Protection class: IPX4
  • Insulation class: F
  • Rated speed: 2900 rpm
  • Motor with integrated thermal motor protection probe
  • Max. volume flow: 4.5 m3/h
  • Max. operating pressure: 8 bar
  • Triggering pressure: 1.5 bar
  • Max. fluid temperature: +5 °C to +30 °C
  • Max. ambient temperature: +5 °C to +40 °C
  • Break tank volume: 11 litres
  • Nominal connection diameters:
    • Discharge port: G 1" thread, union nut
    • Suction connection G 3/4" male thread
  • Overflow:
    • Operational overflow: Hose nipple Ø 19-21
    • Emergency overflow: free discharge according to EN 1717, liquid category 5

Materials

  • Technopolymer pump housing
  • Shaft 1.4021 stainless steel
  • Impeller PPE/PS-GF30
  • Ceramic / carbon mechanical seal

Construction

Automatic drinking water separation system as a compact module for potable water and non-potable water in accordance with EN 1717 liquid category 5.

All parts that come into contact with the fluid are corrosion-proof.

Scope of delivery

  • Ready-for-connection system with fixation material
  • Installation and operating instructions
  • "Protect from frost" sticker
  • "Not drinking water" sticker

Options

  • Overflow signalling device
  • Cover cap made of EPP
Documents

Group Statement

Group Statement REACH

Edition 2021-05
Number of pages 5
Language language neutral
PDF (279 KB)
Product selection
Product descriptionArticle number
TRSB1-24 EM
2551979
TRSB1-25 EM
2551980