Search
Contact
E-mail
Catalogue creation
My favorites
Product comparison
XTREME 2T/10-F2 | Wilo

XTREME 2T/10-F2

Article number : 2855289
Technical data
Technical data
Mains connection 3~400 V, 50/60 Hz
Min. rated current I 3,5 A
Max. rated current per pump I 32 A
Activation type Direct On Line (DOL)
Control Without frequency converter
Protection class IP55
Max. number of controllable pumps 2
Max. rated power per pump motor P2 15 kW
Phases 3
Materials
Material, housing ABS

Standard: 3~ 400 V, 50/60 Hz

Product data
Brand Wilo
Product description XTREME 2T/10-F2
Article number 2855289
Minimum order quantity 1
Date of sales availability 2010-01-01
Packaging
Packaging type Cardboard box
Packaging property Transport packaging
Pieces per pallet 1
Number per layer 1
Dimension, weight
Length with packaging 380 mm
Length L 220 mm
Height with packaging 350 mm
Height H 300 mm
Width with packaging 280 mm
Width W 140 mm
Gross weight, approx. m 6,5 kg
Net weight, approx. m 6 kg
Tender text

Operating Principle

• Clean-water booster / circulation systems: A 4-20 mA pressure or level transmitter feeds the controller; pumps are started and stopped at the set-point shown on the display.Each new start selects the next pump in the rotation schedule to equalise running hours.

• Waste-water / drainage systems: The panel is driven by float switches or stainless-steel electrodes. As the liquid rises, pumps enter the duty sequence one-by-one; they fall out again as the level drops.

• Five selectable modes (via HMI): Waste Water, Clean Water, Sensor, Multi-tank, and Stop/Start—giving one panel the versatility to cover most HVAC or infrastructure duties.

Product Features and Benefits

• Digital HMI with password protection, factory-reset shortcut and bar/metre display options

• Universal level/pressure inputs: works with 4-20 mA transmitters, level floats or stainless-steel electrodes—no extra interface cards required

• Configurable protection limits: adjustable over-/under-voltage thresholds, 50 / 60 Hz supply selection and cos φ monitoring for advanced motor safety

• 12 V / 30 mA alarm output for panel beacons or buzzers; all alarm relays are freely configurable

• Self-learning pump current: the controller automatically detects each motor’s rated amperage during commissioning

• Per-pump status & fault data on screen plus individual run/fault relay contacts for BMS integration

• Leakage and PTC inputs for every pump and a dedicated high-level input for priority alarms • External On/Off terminals enable remote start/stop via dry contact

• Adjustable timings: start/stop delays, initial power-on delay, continuous-run timeout, I max (≤ 15 s), I min (≤ 120 s) and cos φ delay

• Switching limits: maximum 99 starts per session and up to 9 starts per minute prevent short-cycling

• Service-interval timer up to 9 999 h (≈ 13 months) triggers maintenance reminders • Dry-run management: four programmable retry intervals; test function can be enabled or disabled from the menu

• Periodic test and manual runtime entry ensure standby pumps remain operational • Up to ten thermistor reset cycles can be set per pump for enhanced protection

• Five selectable operating modes (Waste-water, Clean-water, Sensor, Multi-tank, Stop/Start) cover most booster, circulation and drainage duties

• IP55 powder-coated steel enclosure for robust operation in demanding plant-room or pit environments

Technical data
Max. number of controllable pumps 2
Phases 3
Rated voltage U 400 V
Mains frequency f
  • 50 Hz
  • 60 Hz
Min. rated current I 3,5 A
Max. rated current per pump I 32 A
Activation type Direct On Line (DOL)
Protection class IP55
Material, housing ABS
Length L 220 mm
Width W 140 mm
Height H 300 mm
Net weight, approx. 6 kg
Make Wilo
Item no. 2855289
Documents

Installation and operating instructions

Wilo- Operating Manual Xtreme 2 Control Panel

Edition 2018-XX
Number of pages 58
Language en
PDF (4 MB)

Group Statement

Group Statement REACH

Edition 2021-05
Number of pages 5
Language language neutral
PDF (271 KB)