Search
Contact
E-mail
Catalogue creation
My favorites
Product comparison
CPA-FS3/15 SD | Wilo

CPA-FS3/15 SD

Article number : 2485480
Technical data
Technical data
Mains connection 3~380 V, 50/60 Hz
Min. rated current I 32 A
Max. rated current per pump I 92 A
Activation type Star-Delta (YΔ)
Control Without frequency converter
Protection class IP54
Max. number of controllable pumps 3
Max. rated power per pump motor P2 45 kW
Phases 3
Materials
Material, housing 1.0330/DC01 (CCR Coated)

Standard: 3~ 380 V, 50/60 Hz

Product data
Brand Wilo
Product description CPA-FS3/15 SD
Article number 2485480
Minimum order quantity 1
Date of sales availability 2010-01-01
Packaging
Packaging type Euro pallet
Packaging property Transport packaging
Pieces per pallet 1
Number per layer 1
Dimension, weight
Length with packaging 1200 mm
Length L 750 mm
Height with packaging 900 mm
Height H 1000 mm
Width with packaging 800 mm
Width W 300 mm
Gross weight, approx. m 69 kg
Net weight, approx. m 47 kg
Tender text

Operating Principle

• CPA-HS (analogue sensor control): A 4-20 mA level transmitter in the sump sends a continuous signal to the panel PLC. Each pump has its own user-defined start level; the PLC stages pumps in or out to keep the liquid at the programmed minimum level.

• CPA-FS (float switch control): The system operates with a minimum-level float, a maximum-level float, and one auxiliary float per pump. Pumps start and stop sequentially as each float is reached.

• Two selectable modes via the touch-screen HMI

– Mode 0 – Emergency: All pumps start individually at their set level and stop together when the minimum level is reached.

– Mode 1 – Standard: Pumps start individually at their set levels, then stop one-by-one as the water falls; the last running pump stops at the minimum level.

Product Features and Benefits

• Lockable main isolator and Hand-0-Auto selector for every pump

• Phase-failure relay and emergency stop for enhanced safety

• Automatic duty rotation and instant standby takeover on pump fault

• Touch-screen display shows all set-points, levels and pump status; operating hours can be reset per pump

• Adjustable start/stop delays and individual run / rest timers for each pump

• Built-in self-test (auto test) and service hour counter for preventive maintenance

• Two-mode operation (Emergency / Standard) adapts to site priorities

• HS version: accepts 4-20 mA analogue level input

• FS version: accepts float-switch inputs

• IP54 powder-coated steel enclosure withstands humid underground chambers

• Digital multimeter on the front panel displays voltage, current and frequency in real time

• Moisture (leak) sensor & PTC thermistor relay inputs for every motor

Technical data
Max. number of controllable pumps 3
Phases 3
Rated voltage U 380 V
Mains frequency f
  • 50 Hz
  • 60 Hz
Min. rated current I 32 A
Max. rated current per pump I 92 A
Activation type Star-Delta (YΔ)
Protection class IP54
Material, housing 1.0330/DC01 (CCR Coated)
Length L 750 mm
Width W 300 mm
Height H 1000 mm
Net weight, approx. 47 kg
Make Wilo
Item no. 2485480
Documents

Installation and operating instructions

Wilo- Operating Manual CPA HS/FS Control Panel

Edition 2018-XX
Number of pages 17
Language en
PDF (3 MB)

Group Statement

Group Statement REACH

Edition 2021-05
Number of pages 5
Language language neutral
PDF (224 KB)