Wilo-VeroLine-IP-E

Series description

Special features/product advantages

  • Energy savings due to integrated electronic power adjustment
  • Optional interfaces for bus communication using plug-in IF-Modules
  • Simple operation with Green Button Technology and display
  • Integrated dual pump management
  • Integrated full motor protection (PTC thermistor sensor) with trip electronics

Design type

Electronically controlled glanded single pump in in-line design with flange connection and automatic power adjustment

Application

Pumping of heating water (acc. to VDI 2035), cold water and water/glycol mixtures without abrasive substances in heating, cold water and cooling systems.

Equipment/function

Operating modes

  • Δp-c for constant differential pressure
  • Δp-v for variable differential pressure
  • PID control
  • Constant speed (n=constant)

Manual operation level

  • Green button and display

Manual functions

  • Differential pressure setpoint setting
  • Setting the speed (manual control mode)
  • Setting the operating mode
  • Setting the pump ON/OFF
  • Configuration of all operating parameters
  • Fault acknowledgement

External control functions

  • "Overriding Off" control input
  • “External pump cycling” control input (effective only in dual pump operation)
  • Analogue input 0 – 10 V, 0 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 2 – 10 V, 4 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 0 – 10 V for actual value signal from pressure sensor
  • Analogue input 2 – 10 V, 0 – 20 mA, 4 – 20 mA for actual value signal from pressure sensor

Signal and display functions

  • Collective fault signal SSM
  • Collective run signal SBM

Data exchange

  • Infrared interface for wireless data exchange with IR-Monitor/IR-Stick
  • Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation

Safety functions

  • Full motor protection with integrated trip electronics
  • Access disable

Dual pump management (double pump or 2 x single pumps)

  • Main/standby operation (automatic fault-actuated switchover)
  • Pump cycling main/standby operation after 24 hours
  • Parallel operation
  • Parallel operation (efficiency-optimised peak-load activation and deactivation)

Scope of delivery

  • Pump
  • Installation and operating instructions

Type key

Example

IP-E 40/160-4/2-R1

IP-E

In-line pump with electronic control

40

Nominal diameter DN of the pipe connection

160

Nominal impeller diameter

4

Rated motor power P2 in kW

2

Number of poles

R1

Version without pressure sensor

Technical data

  • Permissible temperature range -20 °C to +120 °C
  • Mains connection
    • 3~400 V ±10 %, 50 Hz
    • 3~380 V -5 % +10 %, 60 Hz
  • Protection class IP 55
  • Nominal diameter DN 32 to DN 80
  • Max. operating pressure 10 bar (special version: 16 bar)

Materials

  • Pump housing and lantern: EN-GJL-250
  • Impeller: PPO-GF30
  • Shaft: 1.4021
  • Mechanical seal: AQEGG; other mechanical seals on request

Description/construction

Single-stage, low-pressure centrifugal pump in in-line design with

  • Mechanical seal
  • Flange connection
  • Drive with integrated electronic speed control

Downloads

General overview 2018 International version

Article Number 2200591
Edition 2018
Version number 1
Page format 209.9 x 297.0 mm
Number of pages 72