CO3 / 110
Technical data | |
---|---|
Mains connection | 3~380 V, 50/60 Hz |
Min. rated current I | 222 A |
Max. rated current per pump I | 662 A |
Activation type | Star-Delta (YΔ) |
Control | Without frequency converter |
Protection class | IP54 |
Max. number of controllable pumps | 3 |
Max. rated power per pump motor P2 | 330 kW |
Phases | 3 |
Materials | |
---|---|
Material, housing | 1.0330/DC01 (CCR Coated) |
Standard: 3~ 380 V, 50/60 Hz
Product data | |
---|---|
Brand | Wilo |
Product description | CO3 / 110 |
Article number | 2488059 |
Minimum order quantity | 1 |
Date of sales availability | 2010-01-01 |
Packaging | |
---|---|
Packaging type | Special pallet |
Packaging property | Transport packaging |
Pieces per pallet | 1 |
Number per layer | 1 |
Dimension, weight | |
---|---|
Length with packaging | 800 mm |
Length L | 800 mm |
Height with packaging | 2100 mm |
Height H | 1900 mm |
Width with packaging | 500 mm |
Width W | 500 mm |
Gross weight, approx. m | 198 kg |
Net weight, approx. m | 178 kg |
Operating Principle
• Booster systems: When pressure falls below the lower set-point, the panel starts the first pump; if demand persists it brings in additional pumps sequentially. As pressure rises past the upper set-point, pumps drop out in the same order until the standby arrangement is restored. Duty rotation at each new start spreads wear evenly.
• Dry-run protection: A minimum-level float switch inhibits pump operation if the suction tank empties.
Product Features and Benefits
• Hand-0-Auto selector for every pump
• Contact-manometer pressure sensing—no electronics required
• Dry-run float switch interlock
• Automatic duty rotation and standby change-over on fault
• Adjustable start/stop delay timers to prevent rapid cycling
• Individual run lamp & fault lamp per pump
• Individual run and fault relay outputs for BMS integration
• Common low-level lamp for quick tank-level status
• Sturdy steel enclosure, IP54
Control and Signal Functions
• External dry-contact Run / Stop command
• SSM common fault relay (NC)
• SBM common run relay (NO)
• Separate fault relay per pump
• Separate run relay per pump
Options / Accessories (factory-fitted on request)
• Panel-cooling fan
• Lockable main isolator switch
• PTC thermistor relay for motor protection
• Soft-starter for reduced inrush current
• Front-panel multifunction power meter / multimeter
Technical data | |
---|---|
Max. number of controllable pumps | 3 |
Phases | 3 |
Rated voltage U | 380 V |
Mains frequency f |
|
Min. rated current I | 222 A |
Max. rated current per pump I | 662 A |
Activation type | Star-Delta (YΔ) |
Protection class | IP54 |
Material, housing | 1.0330/DC01 (CCR Coated) |
Length L | 800 mm |
Width W | 500 mm |
Height H | 1900 mm |
Net weight, approx. | 178 kg |
Make | Wilo |
Item no. | 2488059 |