Wilo-Yonos PICO-D
Wilo-Yonos PICO-D
Your advantages
- LED display for adjusting the setpoint in 0.1 m increments and showing effective consumption
- Tool-free electrical connection using the Wilo-Connector
- Unique pump venting function per pump
- Twin-head pump for individual (Δp-c and Δp-v) or parallel operation (Δp-c)
- Very high starting torque for reliable starting
Recommended services
Wilo-Yonos PICO-D
Design
Glandless twin-head circulator with screwed connection, blocking-current proof EC motor and integrated electronic power control.
Application
All hot water heating systems, air-conditioning applications, industrial circulation systems.
Equipment/function
Operating modes
- Δ p-c for constant differential pressure
- Δ p-v for variable differential pressure
Manual functions
- Setting the operating mode
- Setting of pump output (delivery head)
- Venting function
Automatic functions
- Infinitely variable power adjustment according to the operating mode
- Automatic deblocking function
Signal and display functions
- Display of power consumption in W
- Display of the current pumping head for setting
- Indication of fault signals (error codes)
Equipment
- Quick electrical connection with Wilo-Connector
- Venting function
- Blocking-current proof motor
- Particle filter
Double pump function
- Main/standby mode (automatic fault-actuated switchover/time-dependent pump cycling). If the double pump is to be operated in the main/standby mode, the control mode and the delivery head must be set so they are identical.
- Parallel operation (efficiency-optimised peak-load activation and deactivation). If the double pump is to be operated in parallel/peak-load operation, the control mode Δp-c must be set with the same delivery head.
An additional switchgear is required for switching the pumps, e.g. in the event of a fault.
Typekey
Example: | Wilo-Yonos PICO-D 30/1-6 |
Yonos PICO | High-efficiency pump (screw-end pump), electronically controlled |
-D | Double pump |
30/ | Nominal connection diameter |
Technical data
- Fluid temperature -10 °C to +95 °C
- Mains connection 1~230 V, 50 Hz
- Protection class IPX4D
- G2 screwed connection
- Max. operating pressure 10 bar
Scope of delivery
- Pump
- 2x Wilo-Connector
- Gaskets for threaded connection
- Installation and operating instructions
Accessories
- Screwed connections
- Adapter fittings
- Wilo-Connector with 2 m connection cable and shockproof plug
- Angle plug with 2 m connection cable
Installation and operating instructions
Product description | Pump connection | EEI | Port-to-port length L0 | Maximum operating pressure PN | Mains connection | Gross weight, approx. m | Pieces per pallet | Article number | |
---|---|---|---|---|---|---|---|---|---|
Yonos PICO-D 30/1-6 | G 2 | ≤0.20 | 180 mm | 10 bar | 1~230 V, 50/60 Hz | 4.9 kg | 40 | 4230948 | |
Yonos PICO-D 30/1-8 | G 2 | ≤0.23 | 180 mm | 10 bar | 1~230 V, 50/60 Hz | 5.2 kg | 40 | 4230949 |