Article number : 4239972
Technical data
Hydraulic data
Maximum operating pressure PN 16 bar
Min. fluid temperature Tmin 4 °C
Max. fluid temperature Tmax 25 °C
Min. ambient temperature Tmin 4 °C
Max. ambient temperature Tmax 40 °C
Motor data
Mains connection 3~400 V, 50 Hz
Rated power P2 5,5 kW
Rated current IN 10,5 A
Power factor cos φ100 0,86
Rated speed n 2900 1/min
Activation type Direct/Star-Delta
Protection class motor IP55
Protection class switchgear IP54
Diesel engine
Materials
Pump housing Stainless steel
Impeller Stainless steel
Shaft Stainless steel
Gasket material EPDM
Pipework material Steel
Installation dimensions
Pipe connection on the suction side DNs DN 80
Pipe connection on the discharge side DNd DN 100
Product data
Brand Wilo
Product description Fire SPK OPTI VF3602/2
Article number 4239972
EAN number 4062679037127
Colour green/silver
Minimum order quantity 1
Date of sales availability 2020-11-01
Packaging
Packaging type Special pallet
Packaging property N/A
Pieces per pallet 1
Number per layer 1
Dimension, weight
Length with packaging 1470 mm
Length L 1270 mm
Height with packaging 1760 mm
Height H 1630 mm
Width with packaging 1725 mm
Width W 1525 mm
Gross weight, approx. m 287 kg
Net weight, approx. m 257 kg
Tender text

Pressure-boosting systems for firefighting in accordance with EN 16925 as fully automatic single pump compact unit for firefighting purposes consisting of: 2 electrical vertical multistage pumps, one main pump and one jockey pump, one switchgear equipped with firefighting dedicated controller for pumps and alarms and fixed on robust supports. Solid base frame with anti-avibration dampers, one circuit with double pressure switch, manometer, non-return valve, valve for main pump automatic start. Available in two versions, with direct suction connections, or with a suction manifold.

Control + alarm control E/J switchgear for fire-extinguishing systems in accordance with EN 16925 requirements.

Switchgear integrated in steel sheeting housing IP54.

Very high control quality and very simple operation due to the firefighting dedicated controller, with multi-languages screen, easy navigation with simple menu and push button plus immediate operation status with symbols. Communication-ready controller for supervising system operations.

System wired ready for connection and mounted on base frame with pipes.

Inlet pressure:

The maximum intake pressure must be taken into account when planning the system configuration (see Technical data).

The maximum permissible intake pressure is calculated from the maximum operating pressure of the system minus the maximum pump delivery head at Q = 0. For sprinkler installation following EN16925, the water pressure shall not exceed 12 bar.

Booster installed under suction condition.

It's necessary to install a priming tank for each main pump, with connection on the discharge pipe above the pump.

Volume flow

Up to 45 m3/h (12,5 l/s) system configuration per main pump.

Switchgear/control device for fire water supply systems

Wilo Control + alarm control E/J

Hardware:

Fully electronic central control unit and electro-mechanical components, built-in painted steel case, with protection class IP54, control and display and alarm devices on the front door.

Features and functions:

The controller design is suitable for the performance of each pump model. The device consists of several components:

Main switch: For switching the switchgear On/Off. (Unauthorised action in case of fire).

Display: Backlit graphic LCD display, built into the switch cabinet door for operating and display purposes. Displays the operating data and the receptive current operating statuses of pump and the controller. The menu selection as well as the parameter input are done by push buttons on the front door.

Microprocessor: Integrated PLC logic with thresholds, counters, alarms, status; 24 VAC auxiliary power supply; advanced I/O wired functions. The respective programming configuration is strictly dependent on system and sprinkler installation.

Indicators: Long-life indicator lights to show, power supply status, pump running, motor status, pressure switch on, automatic mode excluded, manual reset, alarm stop.

Buttons: Push button to manage manual start or manual stop, alarm reset and menu selection.

Fuse protection: Protection fuses, capable of carrying the start current for a period of no less than 20s.

Motor start: Direct start contactor.

Motor protection: Only for signaling.

Priming tank monitoring: By float switch to keep the water level at minimum 2/3 of the priming tank.

Power monitoring: Current, voltage, phases, cos phi and power of the pump.

Monitoring and controlling: Pump room temperature, working hours of the motor, pump status, pump statistics and starts, Jockey pump starts (if available), maintenance programme.

Fault message and acknowledgment: All alarm messages are displayed via LEDs or the graphic LCD. The LEDs color and alarm code must be acknowledged.

Software:

  • Factory programmed for fully automatic operation.
  • Voltage, pump current and pump power information.
  • Menu navigation with text on screen

Communication:

  • Isolated RS485 communication interface built in with Modbus RTU protocol.

Standards followed:

  • Fixed automatic sprinkler systems (EN16925) Electric motor pump part
  • Electrical Equipment of Machines (EN 60204-1)
  • Low-Voltage Switchgear and Controlgear Assemblies (EN 61439-1 and EN 61439-2)
  • EMC – Immunity for Industrial Environments (EN 61000-6-2)
  • EMC – Emission Standard for Residential, Commercial and Industrial (EN 61000-6-3)

Function description:

With the Wilo E control devices, electric motor pump and sensors for pump management or information level can be controlled. The switch gear, which is managed by means of a microprocessor, is used to control and regulate all necessary functions of a pressure boosting systems for firefighting in accordance with EN 16925, for testing or real sprinkling situation.

The operational logic for the fire extinguishing unit is based on the cascade calibration of the pressure switches for pump starting.

When a large quantity of water is requested, due to the opening of one or more circuits or due to a broken sprinkler, pressure decreases in the system. This drives the main pump to start through the switchgear controller.

Once the sprinkler circuit or the gate valve that supply the sprinkler heads is closed, the system reaches the maintaining pressure of the installation; it will be necessary to press the –Stop– buttons on front door to stop the pump.

Operating Data
Max. delivery head Hmax 37,2 m
Fluid temperature T 4 °C
Ambient temperature T 4 °C
Maximum operating pressure PN 16 bar
Motor data
Mains connection 3~400 V, 50 Hz
Rated power P2 5,5 kW
Rated current IN 10,5 A
Power factor cos φ100 0,86
Rated speed n 2900 1/min
Protection class switchgear IP54
Jockey pump
Rated current IN 1,8 A
Rated power P2 550 W
Impeller jockey pump Stainless steel
Pump housing jockey pump Grey cast iron
Shaft jockey pump Stainless steel
Static gaskets jockey pump EPDM
Installation dimensions
Pipe connection on the suction side DNs DN 80
Pipe connection on the discharge side DNd DN 100
Ordering information
Brand Wilo
Product description Fire SPK OPTI VF3602/2
Net weight, approx. m 257 kg
Article number 4239972
Documents

Group Statement

Group Statement REACH

Edition 2021-05
Number of pages 5