Wilo-CronoBloc-BL-E
Your advantages
- Energy savings due to integrated electronic power adjustment
- Optional interfaces for bus communication using plug-in IF-Modules
- Simple operation due to tried-and-tested Green Button Technology and display
- Integrated full motor protection (PTC thermistor sensor) with trip electronics
- Meets user requirements thanks to performance and main dimensions in accordance with EN 733 (for end-suction pumps)
Recommended services
Design
Electronically controlled glanded single pump in close-coupled design with flange connection and automatic power adjustment.
Application
The pumping of heating water (in accordance with VDI 2035), chilled water and water-glycol mixtures without abrasive substances in heating, chilled water and cooling systems.
Equipment/function
Operating modes
- Δp-c for constant differential pressure
- Δp-v for variable differential pressure
- PID-Control
- Constant speed (n=constant)
Manual operation level
- Green button and display
Manual functions
- Differential pressure setpoint setting
- Setting the speed (manual control mode)
- Setting the operating mode
- Setting the pump ON/OFF
- Configuration of all operating parameters
- Fault acknowledgement
External control functions
- 1x “Overriding Off” control input
- 1x “External pump alternation” control input (effective only in twin-head pump operation)
- 1x Analogue input 0–10 V, 2–10 V, 0–20 mA, 4–20 mA for constant speed (DDC) and remote setpoint adjustment
- 1x Analogue input 0–10 V, 2–10 V, 0–20 mA, 4–20 mA for actual value signal from pressure sensor
Signal and display functions
- Collective fault signal SSM
- Collective run signal SBM
Data exchange
- Infrared interface for wireless data exchange with IR-Stick
- Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation
- Interface to dual-pump communication
Safety functions
- Full motor protection with integrated trip electronics
- Access disable
Dual-pump management (2 x single pump; Y-piece application only)
- Main/standby operation (automatic fault-actuated switchover)
- Pump alternation main/standby operation after 24 hours
- Parallel operation
- Parallel operation (efficiency-optimised peak load activation and deactivation)
Type key
Example | BL-E 80/145-11/2-xx |
BL-E | Close-coupled end suction pump with electronic control |
80 | Nominal diameter DN of the pipe connection (discharge port) |
145 | Nominal impeller diameter in mm |
11 | Rated power of motor P2 in kW |
2 | Number of poles |
-xx | Version: E.g. R1 - version without differential pressure sensor |
Technical data
- Permissible temperature range of -20 °C to +140 °C
- Minimum efficiency index (MEI) ≥ 0.4
- Mechanical seal for pumping water up to Tmax = +140 °C. Up to T ≤ +40 °C, a glycol admixture of 20 % to 40 % by volume is permissible. An alternative mechanical seal must be provided for water-glycol mixtures with a glycol content of > 40% to max. 50% by volume and a fluid temperature of > +40 °C to max. +120 °C or other fluids that differ from water. When using water-glycol mixtures, the use of an S1 variant with a corresponding mechanical seal is generally recommended.
- Mains connection
- 3~440 V -5% +10%, 50/60 Hz
- 3~400 V ±10%, 50/60 Hz
- 3~380 V -5% +10%, 50/60 Hz
- Compliance with electromagnetic compatibility without additional measures:
- Interference emission for residential environment according to EN 61800-3:2018
- Interference immunity for industrial environments according to EN 61800-3:2018
- IP55 rating
- Nominal diameter DN 32 to DN 150
- Max. operating pressure 16 bar up to +120 °C, 13 bar up to +140 °C
Materials
- Pump housing and lantern: EN-GJL-250
- Impeller
- Standard version: EN-GJL-200
- Special version: Bronze CuSn 10
- Special version: Stainless steel 1.4408
- Shaft: 1.4122
- Mechanical seal: AQEGG; other mechanical seals on request
Construction
Single-stage low-pressure centrifugal pump in close-coupled design, with axial suction port and radially arranged discharge port with
- Mechanical seal
- Flange connection with pressure measuring connection R 1/8
- Lantern
- Coupling
- Drive with integrated electronic speed control
Scope of delivery
- Pump
- Installation and operating instructions
Options
- Variant …-R1 without differential pressure sensor
- ...-L1 variant with bronze impeller (at additional charge)
- …-L4 variant with stainless steel impeller (at additional charge)
Accessories
- Supporting blocks for installation on a base
- IR-Stick
- IF module PLR for connecting to PLR/interface converter
- IF module LON for connection to the LONWORKS network
- IF module BACnet
- IF module Modbus
- IF module CAN
- Control system VR-HVAC
- Control system CCe-HVAC
- Control system SCe-HVAC
- Differential pressure sensor (DDG)