Search
Contact
E-mail
Catalogue creation
My favorites
Product comparison
DrainLift SANI-L.21/T540/4C-CEE | Wilo

DrainLift SANI-L.21/T540/4C-CEE

Article number : 6098851
Technical data
Hydraulic data
Maximum operating pressure PN 6 bar
Min. fluid temperature Tmin 3 °C
Max. fluid temperature Tmax 40 °C
Min. ambient temperature Tmin 3 °C
Max. ambient temperature Tmax 40 °C
Max. fluid temperature, for short periods up to 5 min. T 65 °C
Sound-pressure level 70
Switching volume V 60 l
Useable volume at 180 mm inlet height V 60 l
Useable volume at 250 mm inlet height V 76 l
Useable volume at 315 mm inlet height V 91 l
Macerator no
Motor data
Mains connection 3~400 V, 50 Hz
Rated current IN 5.5 A
Protection class IP68
Phase 3
Rated speed n 2848 1/min
Number of poles 2
Activation type Direct On Line (DOL)
Max. switching frequency t 60 1/h
Power consumption P1(Q=max.) of selected impeller * number of pumps P1 3200 W
Operating mode per pump S1
Insulation class F
Installation dimensions
Diagonal dimension Diagonal axis 965 mm
Inlet connection -
Pipe connection on the discharge side DNd DN 80
Connection venting DN 75 (75 mm)
Connection for drainage pipe DN 50 (50 mm)

DrainLift SANI-L.12 .../L.16 .../L.21 ...

Product data
Brand Wilo
Product description DrainLift SANI-L.21/T540/4C-CEE
Article number 6098851
EAN number 4062679440125
Colour black/silver
Minimum order quantity 1
Date of sales availability 2024-01-01
Previous model article number 2549928
Previous model designation DrainLift SANI-L.21T/4C
Packaging
Packaging type Cardboard box
Packaging property Transport packaging
Pieces per pallet 1
Number per layer 1
Dimension, weight
Length with packaging 875 mm
Length L 852 mm
Height with packaging 800 mm
Height H 575 mm
Width with packaging 655 mm
Width W 635 mm
Gross weight, approx. m 92 kg
Net weight, approx. m 80 kg
Tender text

Compact, ready for connection, and fully submersible double pump lifting unit for pumping aggressive fluids.

Fluid

The C version is for pumping aggressive fluids:

  • Condensate from boilers
  • Lake water and sea water
    Max. NaCl content (salt water): 30 g/l until 20 °C
  • Swimming pool water, max. chloride content: 400 mg/l
  • Wastewater, slightly acidic with a pH value >3.5
  • Demineralised/cleaned water

Sewage pumping according to 12050

The lifting unit follows DIN EN 12050-1.

Construction

Gas- and watertight collection tank:

  • Sloped floor at an angle
  • Inspection opening with transparent cover
  • Freely selectable inlets in the shown areas
  • Level measurement with a level sensor 4 ... 20 mA

Sewage pump:

  • Mounted directly on the collection tank
  • Self-cooling motor (sheath flow cooling) with thermal motor monitoring
  • Discharge port with non-return valve including inspection opening attached

Pre-wired switchgear for automatic operation:

  • Operation through display and icon-based, alphanumeric menu
  • Collective fault signal with potential-free contact
  • Individual fault signal with potential-free contact
  • ModBus interface
  • Integrated and mains-independent alarm
  • Adjustable follow-up time
  • 1.5 m connection cable with attached plug

Scope of delivery

  • Lifting unit with switchgear and connection cable with plug
  • Flange connector from DN 80, PN 10 to DN/OD 110
  • Flexible collar DN/OD 110 for discharge connection
  • HT double socket DN/OD 75 for ventilation connection
  • HT double socket DN/OD 50 for drain connection
  • Inlet set with hole saw 124 mm (5 in) and seal for HT pipe DN/OD 110
  • Floor fixation set
  • Noise insulation mat
  • 9 V rechargeable battery
  • Installation and operating instructions
Operating Data
Approved field of application
Fluid temperature T 3 °C
Max. fluid temperature, for short periods up to 5 min. T 65 °C
Ambient temperature T 3 °C
Maximum operating pressure PN 6 bar
Max. permissible pressure in the pressure pipe P 1.5 bar
Product data
Gross volume of the tank V 122 l
Useable volume at 180 mm inlet height V 60 l
Useable volume at 250 mm inlet height V 76 l
Useable volume at 315 mm inlet height V 91 l
Sound-pressure level 70
Operating mode (non-immersed) S1
Height H 575 mm
Length L 852 mm
Width W 635 mm
Diagonal dimension Diagonal axis 965 mm
Free ball passage of the hydraulics 44 mm
Motor data
Mains connection 3~400 V, 50 Hz
Voltage tolerance ±10 %
Rated power P2 2.5 kW
Rated speed n 2848 1/min
Rated current IN 5.5 A
Insulation class F
Protection class motor IP68
Activation type Direct On Line (DOL)
Max. switching frequency t 60 1/h
Operating mode per pump S1
Motor protection Bimetall
Cable
Connection cable length L 10 m
Cable type H07RN-F
Cable cross-section 6G1 mm²
Mains plug CEE 32A, 3P+N+PE, 6h
Materials
Tank PE
Installation dimensions
Pipe connection on the suction side DN 110 (110 mm)
Pipe connection on the discharge side DN 80
Connection venting DN 75 (75 mm)
Ordering information
Brand Wilo
Product description DrainLift SANI-L.21/T540/4C-CEE
Net weight, approx. m 80 kg
Article number 6098851
Documents

Installation and operating instructions

Wilo-Control EC-L

Article Number 2543252
Edition 2022-09
Number of pages 64
Language en
PDF (8 MB)

Wilo-DrainLift SANI-L

Article Number 2552854
Edition 2024-12
Number of pages 28
Language en
PDF (6 MB)

Installation and operating instructions (digital)

Wilo-Control EC-L

Article Number 2543252
Edition 2022-09
Language bg, cs, da, de, el, en, es, et, fi, fr, hr, hu, it, lt, lv, mk, nl, no, pl, pt, ro, ru, sk, sl, sr, sv, tr, uk, zh
HTML (223 MB)

Operating instructions (digital)

Wilo-DrainLift SANI-L

Article Number 2552854
Edition 2024-12
Language cs, de, el, en, es, fr, hu, it, nl, no, pl, ro, sv, tr, uk, zh
HTML (109 MB)

Certification booklet

Wilo-DrainLift SANI

Article Number 6088777
Edition 2020-06
Number of pages 40
Language language neutral
PDF (2 MB)

Group Statement

Group Statement REACH

Edition 2021-05
Number of pages 5
Language language neutral
PDF (271 KB)
Accessory

Mains-independent alarm signal (4)

Stationary dry well installation (9)

Fittings (1)

Installation/setup (11)

Pipes/pipe joints (3)

Alarm signal (8)

Level control (9)

Services

With Wilo as your partner, you can not only be sure of choosing high-quality product solutions, but also of benefiting from a comprehensive, worry-free package of well thought-out services. We collaborate to develop a service concept tailored to your individual needs; with our expertise and personal consultancy, we make sure that the operation of your systems is as energy-efficient, reliable and economical as possible. All the while our competent Wilo service technicians are ready to assist you with fast, reliable and on-time support.

Read more

Recommended services

Maintenance
Maintenance BASIC Lifting stations (Double pump)
    

In order to ensure and guarantee operational reliability of the pumps/systems, it is recommended to have regular and DIN-compliant inspections and maintenance carried out by the works' own WILO SE Customer Service Department. The tasks are carried out in accordance with DIN 31051 / DIN EN 13306. The tasks comprise the following points:

  • Visual inspection of the pumps/systems
  • Mechanical check
  • Electrical check
  • Testing pressure vessels that may be on hand
  • Review and, if necessary, adjustment of the system parameters
  • Creating a maintenance protocol

Scheduling and organisation is performed by WILO. Other individual maintenance offers are possible on request.

Maintenance COMFORT Lifting stations (Double pump)
    

In order to ensure and guarantee operational reliability of the pumps/systems, it is recommended to have regular and DIN-compliant inspections and maintenance carried out by the works' own WILO SE Customer Service Department. The tasks are carried out in accordance with DIN 31051 / DIN EN 13306. The tasks comprise the following points:

  • Visual inspection of the pumps/systems
  • Mechanical check
  • Electrical check
  • Testing and possible filling of pressure vessels that may be on hand
  • Review and, if necessary, adjustment of the system parameters
  • Creating a maintenance protocol
  • Consumable materials are included in the contract price
  • Elimination of payroll and travel expenses for deployments between maintenance intervals (during normal service hours)

Scheduling and organisation is performed by WILO. Other individual maintenance offers are possible on request.

Maintenance PREMIUM Lifting stations (Double pump)
    

In order to ensure and guarantee operational reliability of the pumps/systems, it is recommended to have regular and DIN-compliant inspections and maintenance carried out by the works' own WILO SE Customer Service Department. The tasks are carried out in accordance with DIN 31051 / DIN EN 13306. The tasks comprise the following points:

  • Visual inspection of the pumps/systems
  • Mechanical check
  • Electrical check
  • Testing and possible filling of pressure vessels that may be on hand
  • Checking the system parameters
  • Creating a maintenance protocol
  • Consumable materials are included in the contract price
  • Elimination of payroll and travel expenses for deployments between maintenance intervals (during and outside normal service hours)
  • Software updates
  • Includes wearing parts

Scheduling and organisation is performed by WILO. Other individual maintenance offers are possible on request.

Commissioning
Commissioning Lifting stations (Double pump)
    

For perfect functioning of the pump(s) / system(s), it is recommended to have the commissioning carried out by the works' own WILO SE Customer Service Department. Optimum setting and efficient operation of the system are ensured as a result. Commissioning is comprised of the following points:

  • Commissioning of system(s) according to checklist
  • Parameterisation and setting of switchgear
  • Testing and adaptation of initial compressing of pressure tanks (filling up to 80 litres incl.)
  • Functional check of fitted system(s)
  • Practice-oriented operation instruction
  • Wilo commissioning protocol

The price for commissioning only applies to system(s) which have been installed in accordance with the installation and operating instructions and state-of-the-art technology. No costs for any materials which may be required are included.