High-efficiency in-line pump with EC motor of energy efficiency class IE5 compliant with IEC 60034-30-2 and electronic power adjustment in glanded pump design. The pump is configured as a single-stage low-pressure centrifugal pump with flange connection and mechanical seal. The Stratos GIGA2.0-I has been predominantly designed for pumping heating water, chilled water and water-glycol mixtures without abrasive substances in heating, air-conditioning and cooling systems.
Design:
- Single-stage low-pressure centrifugal pump with one-piece shaft in monobloc design
- Spiral housing in in-line design (suction and discharge ports with the same flanges in a line)
- PN 16 flange compliant with ANSI Class 125
- Pressure measuring connections (R 1/8) for mounted differential pressure sensor
- Pump housing and motor flange with cataphoretic coating as standard
- Mechanical seal for pumping water up to Tmax. = +90 °C/200 °F. A glycol admixture of up to 50% by volume is permissible up to T ≤ +120 °C/250 °F.
- Connection voltages:
- 3~480 V ±10% 60 Hz; 3~400 V ±10% 50/60 Hz; 3~380 V -5% +10% 50/60 Hz
- Compliance with electromagnetic compatibility without additional measures
- Interference emission for residential environment according to EN 61800-3:2018
- Interference immunity for industrial environments according to EN 61800-3:2018
Control modes:
- Permanent, automatic power adjustment to system requirements without setpoint specification Wilo Dynamic Adapt plus (factory setting).
- Constant temperature (T-const.)
- Constant differential temperature (dT-const.)
- Needs-based volume flow optimisation of the feeder pump through connectivity and communication between multiple secondary pumps (Multi-Flow Adaptation).
- Constant volume flow (Q-const.)
- Variable differential pressure (dp-v) with the option to set the nominal duty point Q and H
- Constant differential pressure (dp-c)
- Differential pressure control (dp-c) to a remote point in the pipe network (index circuit evaluator)
- Constant speed (n-const.)
- User-defined PID control
Functions:
- Selection of the field of application in the setting assistant
- Heat quantity measurement
- Cooling quantity measurement
- Adjustable volume flow limiter using the Q-Limit function (Qmin. and Qmax.)
- Operating modes of twin-head pump: Main/standby operation, efficiency-optimised parallel operation for dp-c and dp-v
- Pump automatically deactivates when no flow rate is detected (No-Flow Stop)
- Switchover between heating and cooling mode (automatic, external or manual)
- Ability to save and restore configured pump settings (3 restoration points)
- Display of current duty point in the hydraulic duty chart
- Correction of viscous fluids via adjustment of viscosity and density
- Fault and warning messages shown in plain text with advice on resolving the issue
- Integrated full motor protection
Display in the “Home screen” of the graphic display:
- Control mode currently set
- Current setpoint
- Current volume flow (only if a differential pressure sensor is connected)
- Current fluid temperature (only if temperature sensor is connected)
- Current power consumption
- Cumulative electric consumption
Version:
- 4 configurable analogue inputs: 0-10 V, 2-10 V, 0-20 mA, 4-20 mA and commercially available Pt1000 (only on two analogue inputs); +24 V DC power supply
- 2 configurable digital inputs (Ext. OFF, Ext. Min, Ext. Max, heating/cooling, manual override (uncoupled from building automation), operation lock (key lock and remote operation configuration protection))
- 2 configurable signal relays for run signals and fault messages
- Slot for Wilo-CIF modules with interfaces for building automation (BA) (optional accessories: CIF modules Modbus RTU, BACnet MS/TP, LON, PLR, CAN)
- Wilo Net as a Wilo system bus for communication between Wilo products, e.g. Multi-Flow Adaptation; dual-pump operation
- Automatic emergency operation with definable pump speed for exceptional circumstances, e.g. bus communication or sensor value malfunction
- Rotatable, graphic colour display (4.3 inches) with one button manual operation level
- Bluetooth interface via Wilo-Smart Connect module BT
- Use the Wilo-Assistant app to read and set operating data and –among other things– set up a commissioning protocol through the Bluetooth interface
- Integrated dual-pump management when using 2 single pumps as a two-pump system, connection via Wilo Net
- Cable break detection when using an analogue signal (in connection with 2 – 10 V or 4 – 20 mA)
- Time stamp for error/warnings and historical operating data
- Continuous operating data memory
- Standard condensate drainage holes in the motor housing (closed upon delivery)
- Air vent valve on the lantern
Scope of delivery:
- Pump
- Wilo-Smart Connect module BT
- Installation and operating instructions and declaration of conformity
Accessories must be ordered separately:
- 3 mounting brackets with fixation material for installation on a base
- Installation aid for mechanical seal (incl. mounting bolts)
- For connection to building automation:
- CIF module PLR
- CIF module LON
- CIF module BACnet MS/TP
- CIF module Modbus RTU
- CIF module CANopen
- CIF module Ethernet Multi-protocol (Modbus TCP, BACnet/IP)
- Connection M12 RJ45 CIF Ethernet
- Differential pressure sensor DPS 2 ... 10 V
- Differential pressure sensor DPS 4 ... 20 mA
- Temperature sensor PT1000 AA
- Sensor sleeves for the installation of temperature sensors in the pipe