Search
Contact
E-mail
Catalogue creation
My favorites
Product comparison
COR 1MHI404/EC-EM-T150 | Wilo

COR 1MHI404/EC-EM-T150

Article number: 29993098
Technical data
Hydraulic data
Maximum inlet pressure p inl 6 bar
Maximum operating pressure PN 10 bar
Pipe connection on the discharge side DNd Rp 1
Pipe connection on the suction side DNs -
Number of pumps 1
Number of stages -
Number of standby pumps 0
Number of operating pumps 1
System output without standby pump Q 750 m³/h
Min. fluid temperature Tmin 3 °C
Max. fluid temperature Tmax 50 °C
Min. ambient temperature Tmin 5 °C
Max. ambient temperature Tmax 40 °C
Motor data (per motor)
Mains connection 3~400 V, 50 Hz
Voltage tolerance ±10 %
Rated power P2 0.75 kW
Rated current IN 1.95 A
Rated speed n 2900 1/min
Insulation class F
Protection class IP54
Motor efficiency 50% ηM 50% 79.5 %
Motor efficiency 75% ηM 75% 80.7 %
Motor efficiency 100% ηM 100% 80.7 %
Materials
Pump housing Stainless steel
Impeller Stainless steel
Shaft Stainless steel
Mechanical seal BQ1E3GG
Gasket material EPDM
Pipework material Brass, CW617N

3~400 V; 1~230 V

Product data
Brand Wilo
Product description COR 1MHI404/EC-EM-T150
Article number 29993098
EAN number 5013608002463
Colour Green/black/silver
Minimum order quantity 1
Date of sales availability 2020-04-22
Packaging
Packaging type One-way pallet
Packaging property Transport packaging
Pieces per pallet 1
Number per layer 1
Dimension, weight
Length with packaging 1200 mm
Length L 1000 mm
Height with packaging 940 mm
Height H 840 mm
Width with packaging 1000 mm
Width W 870 mm
Gross weight, approx. m 79 kg
Net weight, approx. m 64 kg
Tender text

Fully packaged pressure booster set consisting of:

1 MHI non self-priming horizontal stainless steel high pressure centrifugal pumps with integrated frequency converter that enables variable speed control. The pump has a 1/4 turn ball valve on suction and a 1/4 turn ball valve and a non-return valve on discharge. The discharge manifold is equipped with an 8 litre diaphragm pressure vessel with through-flow fitting to DN 4807, pressure gauge, air vent and integrated pressure sensor. Low level float switch installed inside the tank.

The polypropylene break tank has an actual capacity of 150 litres and is complete with an AB type airgap to WRAS regulations 1999 and BSEN 13077, this is suitable for backflow prevention to Category 5 systems. The water level is controlled via ½” BS1212 equilibrium ball float valve sized for a minimum of 1 bar inlet pressure. Tank can be drained via ½” drain cock.

The Weir and ¾” overflow are screened to enable installation on hygienic systems. All parts are compliant with Reg 4 which gives compliance to UK’s Water Supply Regulations of 1999..

The Wilo-ElectronicControl starts the pump in automatic mode when the system pressure falls below the set pressure by more than the set pressure difference. Once the system pressure has reached the set pressure, the Wilo-ElectronicControl stops the pump after a time interval that has been previously set.

The Wilo ElectronicControl protects the pump against

- Dry run

- Excess current

- Excess water temperature

- Frost

- Short-circuit

- Overvoltage

- Undervoltage

All mounted on a common powder coated steel base frame.

Operating Data
Max. delivery head Hmax 45.0 m
Number of pumps 1
Fluid temperature T 3 °C
Ambient temperature T 5 °C
Maximum operating pressure PN 10 bar
Maximum inlet pressure p inl 6 bar
Control
Mains frequency f 50 Hz
Phase 1
Rated voltage U 230 V
Protection class switchgear IP55
Motor data
Rated power P2 0.75 kW
Rated voltage U 230 V
Rated current IN 3.4 A
Rated speed n 2900 1/min
Activation type Frequency converter (FC)
Motor efficiency 50% ηM 50% 79.5 %
Motor efficiency 75% ηM 75% 80.7 %
Motor efficiency 100% ηM 100% 80.7 %
Insulation class F
Protection class motor IP54
Materials
Tank PP
Pump housing Stainless steel
Impeller Stainless steel
Shaft Stainless steel
Shaft seal BQ1E3GG
Gasket material EPDM
Pipework material Brass, CW617N
Installation dimensions
Pipe connection on the suction side DNs -
Pipe connection on the discharge side DNd Rp 1
Overflow connection Ø22mm, PN10
Gross volume of the tank V 150 l
Ordering information
Net weight, approx. m 64 kg
Brand Wilo
Product description COR 1MHI404/EC-EM-T150
Article number 29993098
Documents

Installation and operating instructions

Wilo-ElectronicControl

Article Number 4159796
Edition 2304
Number of pages 20
Language en
PDF (1 MB)

Wilo-Economy MHI

Article Number 2020406
Edition 2020-03
Number of pages 112
Language ar, bg, cs, da, de, el, en, es, et, fi, fr, ga, hr, hu, it, ko, lt, lv, mk, nl, no, pl, pt, ro, ru, sk, sl, sr, sv, tr, uk, zh
PDF (4 MB)

COR 1MHI**/EC-EM-T** Installation and Operating Instructions

Article Number CD_TE0063
Edition 2018-XX
Number of pages 16
Language en
PDF (991 KB)
Services

With Wilo as your partner, you can not only be sure of choosing high-quality product solutions, but also of benefiting from a comprehensive, worry-free package of well thought-out services. We collaborate to develop a service concept tailored to your individual needs; with our expertise and personal consultancy, we make sure that the operation of your systems is as energy-efficient, reliable and economical as possible. All the while our competent Wilo service technicians are ready to assist you with fast, reliable and on-time support.

Read more

Recommended services

Maintenance
Maintenance BASIC Booster Set 1-2 pumps
    
2160453

In order to ensure and guarantee operational reliability of the pumps/systems, it is recommended to have regular and DIN-compliant inspections, maintenance and repair carried out by WILO SE’s own customer service. The tasks are carried out in accordance with DIN 31051 / DIN EN 13306. The tasks comprise the following points:

  • Visual inspection of the pumps/systems
  • Mechanical check
  • Electrical check
  • Inspection of any diaphragm expansion tanks in the system (not filling)
  • Review and, if necessary, adjustment of the system parameters
  • Drawing up a maintenance and repair report

WILO SE schedules and organises initial maintenance and repairs. Further customised maintenance and repair services are possible after the first maintenance and repairs are conducted.

Maintenance COMFORT Booster Set 1-2 pumps
    
2160468

In order to ensure and guarantee operational reliability of the pumps/systems, it is recommended to have regular and DIN-compliant inspections, maintenance and repair carried out by WILO SE’s own customer service. The tasks are carried out in accordance with DIN 31051 / DIN EN 13306. The tasks comprise the following points:

  • Visual inspection of the pumps/systems
  • Mechanical check
  • Electrical check
  • Testing and possible filling of pressure vessels that may be on hand
  • Review and, if necessary, adjustment of the system parameters
  • Drawing up a maintenance and repair report
  • Consumables are included in the price
  • Small repairs are included in the maintenance and repair price
  • No labour and travel expenses are charged for deployments between maintenance and repair intervals (during normal operating hours)

WILO SE schedules and organises initial maintenance and repairs. Further customised maintenance and repair services are possible after the first maintenance and repairs are conducted. The quoted price refers to the initial maintenance and repair offered.

-NET-

Maintenance PREMIUM Booster Set 1-2 pumps
    
2160483

In order to ensure and guarantee operational reliability of the pumps/systems, it is recommended to have regular and DIN-compliant inspections and maintenance carried out by the works' own WILO SE Customer Service Department. The tasks are carried out in accordance with DIN 31051 / DIN EN 13306. The tasks comprise the following points:

  • Visual inspection of the pumps/systems
  • Mechanical check
  • Electrical check
  • Testing and possible filling of pressure vessels that may be on hand
  • Checking the system parameters
  • Creating a maintenance protocol
  • Consumable materials are included in the contract price
  • Elimination of payroll and travel expenses for deployments between maintenance intervals (during and outside normal service hours)
  • Software updates
  • Wearing parts included

Scheduling and organisation are performed by WILO SE. Other individual maintenance offers are possible on request.

Commissioning
Commissioning Booster Set 1-2 pumps
    
2216414

For perfect functioning of the pump(s) / system(s), it is recommended to have the commissioning carried out by the works' own WILO SE Customer Service Department. Optimum setting and efficient operation of the system are ensured as a result. Commissioning is comprised of the following points:

  • Commissioning of system(s) according to checklist
  • Parameterisation and setting of switchgear
  • Testing and adaptation of initial compressing of pressure tanks (filling up to 80 litres incl.)
  • Functional check of fitted system(s)
  • Practice-oriented operation instruction
  • Wilo commissioning protocol

The price for commissioning only applies to system(s) which have been installed in accordance with the installation and operating instructions and state-of-the-art technology. No costs for any materials which may be required are included.

-NET-

More suitable services

Wilo-Live Assistant
Wilo-Live Assistant Service
    
2216415

The Wilo-Live Assistant is a technical advisor at your side during pump service. By using the Wilo-Live Assistant, our expert advisers can support you in the boiler or equipment room via video transmission – live and in real time. You use your smartphone to show the installation set-up, while the Wilo expert follows everything on their screen. They can see the components as well as other details and can thus determine where the fault or breakdown originates. We prevent downtime and ensure operational reliability of your pumps and systems!

The Wilo-Live Assistant includes:

  • Interactive live support via video chat
  • Direct contact with an expert
  • Just-in-time solution to ensure maximum operational reliability of your pumps and systems
Supervision
Supervision Booster Set 1-2 pumps
    
2216412

Wilo supports during the concept phase to ensure quality work and cost efficiency. Our competent and qualified Wilo Service will support you with recommendations and technical advice throughout the entire project.

Supervision includes:

  • Regular on-site visits ensure the quality of information and advice
  • Technical consultancy, also available on site
  • Status report with recommendations after the visit
  • Comprehensive support from a Wilo expert
Installation
Installation Booster Set 1-2 pumps
    
2216413

The Wilo service offers installation of our pumps or pumping systems. We offer an end-to-end process from gathering information on site to installing our product in the overall plant. An optimal installation set-up and the interaction of various individual factors lay the foundation for long-term operational safety.

Installation includes:

  • Professional inspection
  • Provision of components/materials from Wilo and third-party suppliers
  • Installation of pipelines and electronics
  • Test runs
System Optimisation
System Optimisation Booster Set 1-2 pump
    
2216410

The Wilo Service offers proactive system optimisation by optimising settings and doing minor adjustments to ensure operational reliability. System Optimisation includes among others:

  • Overhaul of pumps/systems to restore full performance
  • Addition of new technologies or functions in older systems to save on capital expenditures (retrofitting)
Energy Solutions
Energy Solutions Booster Set 1-2 pumps
    
2216411

Wilo Service offers a proactive support to point out possible energy savings. Our service creates an overview of all installed assets to show how the energy consumption of pumps or systems can be reduced. We offer targeted consultancy and analysis, including the involvement of subsidies as well as comprehensive support around the changeover to high-efficiency technologies. Wilo-Energy solution includes:

  • Detailed assessment of the life cycle costs (LCC analysis)
  • Energy audit including information about energy saving potential
  • Proactive recommendation of replacement options
  • Improving the environmental performance of your system
  • Support in the changeover to Wilo high-efficiency pumps
Repair
Repair Booster Set 1-2 pumps
    
2216417

Wilo Service draws on their competence and experience while consulting on site to decide whether the pump can actually be repaired on site or has to be sent in for a factory repair. Wilo also provides spare parts or a replacement pump to restore the operational reliability of the system.

Repair includes:

  • Verification and elimination of error causes by experienced Wilo experts
  • Non-binding estimate for repairs
  • Electric-hydraulic test run to ensure correct data regarding functionality, quality and performance of the pump or system
  • Coating of various pump or system components for an optimised efficiency factor
  • Use of genuine spare parts only
  • Documentation of the repair in the service report