P135
Techniniai duomenys | |
---|---|
Maitinimo įtampa | 1~230 V, 50 Hz |
Nominalioji galia P2 P2 | 370 W |
Valdymas | be dažnio keitiklio |
Įjungimo būdas | Tiesioginis tinkle (DOL) |
Elektromagnetinis suderinamumas | EN 61000 |
Standartinė jungtis | EN 1254 |
Montavimas | Montavimas ant grindų |
Eksploatavimo duomenys | |
---|---|
Didž. įtako slėgis | 8 bar |
Matmenys | |
---|---|
Matmenys H1 | 775,0 mm |
Matmenys H2 | 730,0 mm |
Matmenys H3 | 225,0 mm |
Dimensions H4 | 545,0 mm |
Dimensions H5 | 590,0 mm |
Matmenys L | 455,0 mm |
Pressurisation Unit Dimension Drawing
Pressurisation Unit Wiring Diagram
Produkto duomenys | |
---|---|
Gamintojas | Wilo |
Produkto žymėjimas | P135 |
Prekės numeris | 2819492 |
EAN numeris | 5013608000582 |
Spalva | žalias / sidabrinis / pilkas |
Mažiausias užsakymo kiekis | 1 |
Turimumas rinkoje | 2012-06-01 |
Pakuotė | |
---|---|
Pakuotės rūšis | Europinis padėklas |
Pakuotė | Transportavimo pakuotė |
Skaičius ant padėklo | 4 |
Kiekis kiekvienam sluoksniui | 4 |
Masė ir matmenys | |
---|---|
Ilgio matmuo su pakuote | 1000 mm |
Ilgis L | 455 mm |
Aukščio matmuo su pakuote | 925 mm |
Aukštis H | 775 mm |
Pločio matmuo su pakuote | 800 mm |
Plotis W | 350 mm |
Bendroji masė (apyt.) m | 42 kg |
Grynoji masė (apyt.) m | 27 kg |
The Wilo Comfort single pump pressurisation units are designed for use on heating or chilled water systems up to and including 3.5, 6.0 and 8.0 bar cold fill pressures.
The unit is fitted with an 18 litre polypropylene break tank c/w type AB air gap to BS13077:2008 and water regulations 1999, Wras approved equilibrium ball float valve to BS1212 and a low water float switch and strainers for pump protection.
Each pump is fitted with a non return valve and quick release couplings for ease of maintenance. The pressure transducer monitors the system pressure and feeds a 0-10v signal to the comfort controller.
Comfort Controller is complete with the following features:
- User friendly interface that has a 2 line LCD backlight display
- Healthy / fail LED
- Password protection
- System Fill for initial fill of system
- Pump check routine, that runs the pump for 2 seconds if inactive for 7-90 days
- Pump trip and fail alarms
- System leak alarm
- Excessive starts alarm
- Alarm log
- Hours Run
- Connectivity: BACnet = RS485 interface, BACnet MS/TP protocol
2 wire BACnet
Volt Free Contacts are supplied with terminals for common, normally open and normally closed.
(5A, 230V)
Pump no.1 trip, Pump no. 1 run, High Pressure, Low Pressure, Excess starts, Low water and Boiler Interlock (NC only)
(10A, 230V)
To be selected from Power fail, Common alarm, Common pressure alarm
Standards Applied:
Low Voltage and Machinery Directive 2006/42/EC, EMC Directive EMC 2004/108/EC, BSEN809, BS7074-1 to 3, BS13077:2008 and water regulations 1999.
Techniniai duomenys | |
---|---|
Maitinimo įtampa | 1~230 V, 50 Hz |
Valdymas | be dažnio keitiklio |
Eksploatavimo duomenys | |
---|---|
Didž. įtako slėgis | 8 bar |
Informacija apie užsakymo pateikimą | |
---|---|
Plotis W | 350 mm |