Wilo-CronoLine-IL
Wilo-CronoLine-IL
Your advantages
- Reduced life cycle costs thanks to optimized efficiency
- Standard condensate drainage holes in the motor housings
- Can be used flexibly in air-conditioning and cooling systems, with application benefits due to direct draining of condensate via optimised lantern design (patented)
- High standard of corrosion protection thanks to cataphoretic coating
- High worldwide availability of standard motors (according to Wilo specifications) and standard mechanical seals
Recommended services
CronoLine-IL
Design
Glanded pump in in-line design with flange connection
Application
Pumping of heating water (acc. to VDI 2035), chilled water and water/glycol mixtures without abrasive substances in heating, chilled water and cooling systems.
Typekey
Example | IL 40/160-4/2 |
IL | In-line pump |
40 | Nominal diameter DN of the pipe connection |
160 | Nominal impeller diameter |
4 | Rated motor power P2 in kW |
2 | Number of poles |
Technical data
- Permissible temperature range -20 °C to +140 °C
- Mains connection 3~400 V, 50 Hz (others on request)
- Protection class IP 55
- Nominal diameter DN 32 to DN 250
- Max. operating pressure 16 bar (25 bar on request)
Materials
- Pump housing and lantern: Standard: EN-GJL-250; optionally spheroidal cast iron EN-GJS-400-18-LT
- Impeller: Standard: EN-GJL-200; special version: Bronze CuSn 10
- Shaft: 1.4122
- Mechanical seal: AQEGG; other mechanical seals on request
Construction
Single-stage, low-pressure centrifugal pump in in-line design with
- Mechanical seal
- Flange connection with pressure measuring connection R 1/8
- Lantern
- Coupling
- IEC standard motor
Scope of delivery
- Pump
- Installation and operating instructions
Options
- ...-L1 variant with bronze impeller (at additional charge)
- ...-H1 variant with housing made of spheroidal cast iron (at additional charge)
- ...-P4 variant for maximum operating pressure of 25 bar (see Wilo price list)
- Other voltages and frequencies as well as ATEX approval on request
Accessories
- Mounting brackets for installation on a base
- PTC thermistor sensor, PTC resistor tripping relay
- Special motors
- Special mechanical seals
- SC-HVAC, CC-HVAC control systems and switchgears