Wilo-SiFire EN

Your advantages

  • Pressure-loss optimised system designed in accordance with the EN 12845 Standard with electrical or diesel drive, jockey pump for maintaining system pressure
  • Flexible, modular and solid construction for safe transport and simple installation
  • Bypass volume flow for the protection of the pump with spacer coupling for simple maintenance
  • High-quality SC-Fire control prepared for BACnet and Modbus building management system integration
  • Special baseplate for minimal vibrations, cable laid in the construction in such a way as to ensure maximum reliability and service life

Series description
SiFire EN

Design

Pressure-boosting systems for firefighting according to EN 12845. Consists of 1 or 2 pumps, depending on the module, with horizontal baseplate - EN 733 - with spacer coupling, electric or diesel motor and a multistage, vertical electric jockey pump.

Application

Fully automatic water supply of fire-fighting systems with a sprinkler system in residential, commercial, public and industrial buildings, as well as hotels, hospitals and department stores.

Equipment/function

  • 1 or 2 pumps with horizontal base frame of series 32-200 to 150-315, with IE-equivalent standard motor or diesel motor
  • With a diaphragm installed directly on the main pump housing to prevent overheating in the event of zero flow
  • Jockey pump of series MVIL-1 or MVI-1with pressure switch and vertical pressure vessel 20 l, PN16
  • One switch cabinet per pump, fixed to a robust support structure. SC Fire model: E for the electric motor and D for the diesel motor, both equipped with Smart Controller, plus J for the jockey pump
  • Base plate made of electro-galvanised steel with height-adjustable holder for the outlet manifold
  • Pipework made of steel; painted with epoxy resin. Manifold with flanges
  • Shutting gate with safety lock on the discharge side of each pump
  • Non-return valve on the discharge side of each pump
  • A circuit with dual pressure switch, pressure gauge, non-return valve, valve for the main pump and standby pump for automatic start
  • Concentric cone on the discharge side of the main and standby pump, for speed limitation according to the parameters specified in EN 12845
  • DN2" connection for the supply tank of the pumps
  • Pressure measurement on the discharge side
  • Only for the model with diesel motor:
    • Vibration damping sleeve on the discharge side of the pump
    • Vibration damper under the base plate of the pump
    • Fuel tank with level sensor and sufficient volume for six hours of autonomous operation
    • 2 or 4 batteries on the base plate and battery charger at the SC Fire switch cabinet
  • Accessories on request:Note on fluids: Approved fluids are generally waters which do not attack the materials used, neither chemically nor mechanically, and do not contain any abrasive or long-fibre constituents. System in accordance with EN 12845
    • Horizontal 500 l supply tank, with float valve and pressure switch for LL-alarm (water shortage)
    • Flow meter: Kit with eccentric cone on the suction side, complete with check valve with hand lever or handwheel
    • Vacuum gauge with valve
    • Valves with electrical contact
    • Vibration damping sleeve for the manifold
    • Remote control panel for transmitting level A and level B alarms
    • Densitometer for the battery
    • Spare parts kit for the diesel motor
    • Sound absorber (30 dBA) for the diesel motor
    • Hydraulic heat exchanger for the diesel motor

Typekey

Example:

Wilo-SiFire EN 40/200-180-7.5/10.5/0.55 EDJ

SiFire

Compact pressure boosting system for fire fighting equipment

EN

in acc. with EN 12845

40/200

Type of main pump

180

Actual impeller diameter of the main pump

7.5

Power of the electric motor [kW]

10.5

Power of the diesel motor [kW]

00:55

Power of the motor for the jockey pump [kW]

EDJ

Configuration

E

An electric pump

D

A diesel pump

J

A jockey pump

Technical data

  • Mains connection 3~400 V, 50 Hz (1~230 V, 50 Hz for the control panel of the diesel pump)
  • IE-equivalent standard motors, diesel motor with direct injection or turbo diesel motor with air or water cooling
  • Max. ambient temperature +4°C to +40°C (+10°C to +40°C, if a diesel pump is installed)
  • Max. fluid temperature +40°C
  • Max. operating pressure 10 or 16 bar
  • Max. inlet pressure 6 bar
  • Volume flow 10 m³/h to 750 m³/h
  • Max. delivery head 128 m
  • Nominal connection diameters on the pressure side DN 65 to DN 250
  • Nominal connection diameters on the intake side DN 50 to DN 200
  • Switch cabinet protection class IP54
  • Main/standby pump with horizontal base plate in accordance with EN 733
  • With epoxy resin painted piping and hydraulic connections
  • Permitted fluids:Note on fluids: Approved fluids are generally waters which do not attack the materials used, neither chemically nor mechanically, and do not contain any abrasive or long-fibre constituents. System in accordance with EN 12845
    • Non-aggressive, clean water
    • Fire water

Materials

For pump with horizontal base plate

  • Impellers made of stainless steel AISI 316/ 1.4401
  • Pump housing made of grey cast iron EN-GJL-250
  • Shaft made of stainless steel AISI 431/ 1.4057
  • Wear rings made of bronze

For the jockey pump

  • Impellers made of stainless steel AISI 304/ 1.4301
  • Pump housing made of grey cast iron EN-GJL-250 (stainless steel AISI304/1.4301 for MVI)
  • Shaft made of stainless steel AISI 304/ 1.4301
  • O-ring seals made of EPDM

Construction

  • Base frame: Manufactured from profiles consisting of electro-galvanised steel with brackets for the switch cabinets and the outlet manifold. Special square holes at the bottom for forklift trucks, as well as integrated hooks for lifting slings. Side profiles at the top on each side to enhance the rigidity of the system when moving and lifting.
  • Plastic cover at the rear which provides visual access to the valve position and pressure gauge.
  • Pipework: Complete pipework with flanges made of epoxy resin painted steel, suitable for the connection of all common piping materials; the dimensions of the pipework must correspond to the overall hydraulic performance of the pressure boosting system
  • Pumps: 1 or 2 pumps with horizontal base frame - EN 733 - with spacer coupling, electric or diesel motor.
  • • Back-pull-out model to ensure the internal parts of the pump are easy to access without having to move the motor or piping.
  • Valves: The main pumps are fitted with a shut-off valve and non-return valve on the discharge side, both of which are painted with epoxy resin and adapted for a flange connection.
  • Diaphragm pressure vessel: Diaphragm pressure vessel 20 l/PN16, on the discharge side of the jockey pump, with drain plug.
  • Tank: The fuel tank is made of metal painted with epoxy resin and is located behind the bracket of the switch cabinet
  • Sensors and display: 2 pressure switches, 2/16 bar per pump, on the discharge side, for activating the pump start via the SCFire controller and regulator. The discharge side pressure gauge (∅ 63 mm) is located in the middle of the rear panel.
  • Controller: The system is equipped as standard with a separate switchgear/control device (SC Fire) for the electric or diesel motor and a switchgear/control device for the jockey pump.

Scope of delivery

  • Factory-mounted, ready-for-installation pressure boosting system, which has been checked for functionality and impermeability
  • Installation and operating instructions
  • Required accessories on request
Documents

Installation and operating instructions

Wilo-MVIL

Article Number 4086201
Edition 1502
Number of pages 13
PDF (934 KB)

Wilo-Control SC-Fire Diesel

Article Number 2541367
Edition 1510
Number of pages 34
PDF (1 MB)

Wilo-Control SC-Fire Electric

Article Number 2539954, 2541365, 2541366
Edition 1510
Number of pages 32
PDF (2 MB)

Wilo-Control SC-Fire Jockey

Number of pages 10
PDF (727 KB)

Wilo-SiFire EN

Article Number 4188030
Edition 2019-12
Number of pages 108
PDF (9 MB)

Wilo-MVIL

Article Number 4086201
Edition 1502
Number of pages 148
PDF (6 MB)

Wilo-MVIL

Article Number 4086201
Edition 1502
Number of pages 13
PDF (1 MB)

Wilo-Control SC-Fire Electric

Article Number 2539954, 2541365, 2541366
Edition 1510
Number of pages 31
PDF (1 MB)

Wilo-Priming tank 500 L

Article Number 4228982
Edition 2019-05
Number of pages 451
PDF (18 MB)

General overview

General Overview 2023 - International version

Edition 2022
Number of pages 74
PDF (24 MB)

Certificate REACH

Group Statement REACH

Edition 2021-05
Number of pages 4
PDF (262 KB)
Product selection
Number of results: 433
29 … 756 m³/h
[433]
Product descriptionSystem output without standby pump QMaximum operating pressure PNGross weight, approx. mArticle number
SiFire-EN-32/200-154-4,2D
29 m³/h
16 bar
485 kg
4241531
SiFire-EN-32/200-154-4,2DJ
29 m³/h
16 bar
614 kg
4241606
SiFire-EN-32/200-154-4/4,2EDJ
29 m³/h
16 bar
808 kg
4241731
SiFire-EN-32/200-154-4/4EEJ
29 m³/h
16 bar
743 kg
4241681
SiFire-EN-32/200-154-4E
29 m³/h
16 bar
410 kg
4241381
SiFire-EN-32/200-154-4EJ
29 m³/h
16 bar
454 kg
4241456
SiFire-EN-32/200-172-5,5/5,5EEJ
34 m³/h
16 bar
787 kg
4241682
SiFire-EN-32/200-172-5,5/6,8EDJ
34 m³/h
16 bar
845 kg
4241732
SiFire-EN-32/200-172-5,5E
34 m³/h
16 bar
432 kg
4241382
SiFire-EN-32/200-172-5,5EJ
34 m³/h
16 bar
476 kg
4241457
SiFire-EN-32/200-172-6,8D
34 m³/h
16 bar
500 kg
4241532
SiFire-EN-32/200-172-6,8DJ
34 m³/h
16 bar
629 kg
4241607
SiFire-EN-32/200-182-6,8D
36 m³/h
16 bar
500 kg
4241533
SiFire-EN-32/200-182-6,8DJ
36 m³/h
16 bar
629 kg
4241608
SiFire-EN-32/200-182-7,5/6,8EDJ
36 m³/h
16 bar
861 kg
4241733
SiFire-EN-32/200-182-7,5/7,5EEJ
36 m³/h
16 bar
811 kg
4241683
SiFire-EN-32/200-182-7,5E
36 m³/h
16 bar
435 kg
4241383
SiFire-EN-32/200-182-7,5EJ
36 m³/h
16 bar
479 kg
4241458
SiFire-EN-32/200-191-7,5/7,5EEJ
37 m³/h
16 bar
811 kg
4241684
SiFire-EN-32/200-191-7,5/10,5EDJ
37 m³/h
16 bar
891 kg
4241734
SiFire-EN-32/200-191-7,5E
37 m³/h
16 bar
435 kg
4241384
SiFire-EN-32/200-191-7,5EJ
37 m³/h
16 bar
479 kg
4241459
SiFire-EN-32/200-191-10,5D
37 m³/h
16 bar
530 kg
4241534
SiFire-EN-32/200-191-10,5DJ
37 m³/h
16 bar
659 kg
4241609
SiFire-EN-32/200-200-10,5D
39 m³/h
16 bar
590 kg
4241535
SiFire-EN-32/200-200-10,5DJ
39 m³/h
16 bar
719 kg
4241610
SiFire-EN-32/200-200-11/10,5EDJ
39 m³/h
16 bar
891 kg
4241735
SiFire-EN-32/200-200-11/11EEJ
39 m³/h
16 bar
811 kg
4241685
SiFire-EN-32/200-200-11E
39 m³/h
16 bar
517 kg
4241385
SiFire-EN-32/200-200-11EJ
39 m³/h
16 bar
561 kg
4241460
SiFire-EN-32/250-198-6,8D
31 m³/h
16 bar
590 kg
4241536
SiFire-EN-32/250-198-6,8DJ
31 m³/h
16 bar
719 kg
4241611
SiFire-EN-32/250-198-7,5/6,8EDJ
31 m³/h
16 bar
1024 kg
4241736
SiFire-EN-32/250-198-7,5/7,5EEJ
31 m³/h
16 bar
936 kg
4241686
SiFire-EN-32/250-198-7,5E
31 m³/h
16 bar
529 kg
4241386
SiFire-EN-32/250-198-7,5EJ
31 m³/h
16 bar
573 kg
4241461
SiFire-EN-32/250-222-10,5D
34 m³/h
16 bar
645 kg
4241537
SiFire-EN-32/250-222-10,5DJ
34 m³/h
16 bar
774 kg
4241612
SiFire-EN-32/250-222-11/10,5EDJ
34 m³/h
16 bar
1091 kg
4241737
SiFire-EN-32/250-222-11/11EEJ
34 m³/h
16 bar
960 kg
4241687
SiFire-EN-32/250-222-11E
34 m³/h
16 bar
529 kg
4241387
SiFire-EN-32/250-222-11EJ
34 m³/h
16 bar
573 kg
4241462
SiFire-EN-32/250-234-12,9D
35 m³/h
16 bar
645 kg
4241538
SiFire-EN-32/250-234-12,9DJ
35 m³/h
16 bar
774 kg
4241613
SiFire-EN-32/250-234-15/12,9EDJ
35 m³/h
16 bar
1131 kg
4241738
SiFire-EN-32/250-234-15/15EEJ
35 m³/h
16 bar
1040 kg
4241688
SiFire-EN-32/250-234-15E
35 m³/h
16 bar
569 kg
4241388
SiFire-EN-32/250-234-15EJ
35 m³/h
16 bar
613 kg
4241463
SiFire-EN-32/250-246-15/15EEJ
37 m³/h
16 bar
1040 kg
4241689
SiFire-EN-32/250-246-15/17,7EDJ
37 m³/h
16 bar
1343 kg
4241739