Product descriptionPump connectionPort-to-port length L0Maximum operating pressure PNMains connectionGross weight, approx. mPieces per palletArticle number
Star-ZD 25/6
G 1½
180 mm
10 bar
1~230 V, 50 Hz
6.7 kg
60
4111288
Series description
Wilo-Star-ZD

Design

Glandless twin-head circulator with threaded connection; preselectable speed stages for power adjustment

Application

Domestic hot water circulation systems in industry and building services.

Equipment/function

Operating modes

  • Speed-stage switching

Manual functions

  • Setting the speed stages (3 speed stages)

Equipment

  • Double switchover valve in pump housing
  • Cable inlet in possible on both sides
  • Internal bypass
  • quick connection with spring clips
  • Blocking-current proof motor

Typekey

Example:

Wilo-Star-ZD 25/6

Star-ZD

Double circulation pump for drinking water

25/

Nominal connection diameter

6

Nominal delivery head [m] at Q = 0 m³/h

Technical data

  • Fluid temperature
    • Drinking water up to 3.21 mmol/l (18 °dH): max. +65°C, in short-time duty (2 h) up to +70°C
  • Mains connection 1~230 V, 50 Hz
  • Protection class IP 44
  • Nominal diameter G1½
  • Max. operating pressure 10 bar

Materials

  • Pump housing: red brass
  • Impeller: Plastic
  • Shaft: Ceramic
  • Bearing: Carbon, synthetic resin-impregnated

Scope of delivery

  • Pump
  • Gaskets
  • Installation and operating instructions

Accessories

  • Screwed connections
Documents

Installation and operating instructions

Wilo-Star-Z/-ZD

Article Number 4236978
Edition 2019-08
Number of pages 184