Wilo-Trennsystem Basic
Wilo separation system Basic
Your advantages
- The ready-to-plug system and compact design with various hydraulic connection options allow for an easy installation
- Convenient operation and simple setting functions provided by electronic functions HiControl 1
- Integrated self-protection routines ensure a high level of reliability
- A break tank with safety device provides hygienic safety in accordance with EN 1717 Fluid category 5
- Easy maintenance through direct access to the system components
Recommended services
Wilo separation system Basic
Design
Automatic drinking water separation system
Application
The drinking water separation system is designed for applications where a hygienically clean separation of public water supplies is required:
- Animal drinking troughs
- Sports ground irrigation
- Garden irrigation
Equipment/function
Ready for connection module with compact design, consisting of:
- HiMulti 3 P self-priming centrifugal pump, mounted on a base frame with oscillation absorbers
- 11 l replenishment reservoir for fresh water replenishment with float valve
- Connection on the discharge side, Rp 1" hose
- Connection for municipal water supply network R ¾"
- 1.5 m mains connection cable and plug
- Electronic control device with integrated switch-off quantity detection and dry-running protection
Typekey
Example: | Wilo-TRSB1-25 EM |
Wilo | Brand name |
TRSB | Basic separation system |
1 | Product level |
2 | Rated flow rate Q in m³/h |
5 | Number of impellers |
EM | Single-phase |
Technical data
- Mains connection: 1~230 V, 50 Hz
- IP rating: IPX4
- Insulation class: F
- Rated speed: 2900 rpm
- Motor with integrated thermal motor protection probe
- Max. volume flow: 4.5 m3/h
- Max. operating pressure: 8 bar
- Triggering pressure: 1.5 bar
- Max. fluid temperature: +5 °C to +30 °C
- Max. ambient temperature: +5 °C to +40 °C
- Break tank volume: 11 litres
- Nominal connection diameters:
- Discharge port: G 1" thread, union nut
- Suction connection G 3/4" male thread
- Overflow:
- Operational overflow: Hose nipple Ø 19-21
- Emergency overflow: free discharge according to EN 1717, liquid category 5
Materials
- Technopolymer pump housing
- Shaft 1.4021 stainless steel
- Impeller PPE/PS-GF30
- Ceramic / carbon mechanical seal
Construction
Automatic drinking water separation system as a compact module for potable water and non-potable water in accordance with EN 1717 liquid category 5.
All parts that come into contact with the fluid are corrosion-proof.
Scope of delivery
- Ready-for-connection system with fixation material
- Installation and operating instructions
- "Protect from frost" sticker
- "Not drinking water" sticker
Options
- Overflow signalling device
- Cover cap made of EPP
Product description | Article number | |
---|---|---|
TRSB1-24 EM | 2551979 | |
TRSB1-25 EM | 2551980 |