Your advantages
- Reliable control and monitoring of up to three pumps, thanks to various monitoring and alarm functions
- Flexible level measurement with level sensor, dynamic pressure bell or float switches
- Increased plant safety when controlling pumps in explosive areas by extending the monitoring functionality in Ex-mode (hardware and software)
- Easy operation with alphanumeric, symbol-based menu and red-button technology
- Operating statuses can be viewed at any time. Greater ease of use via integration with remote monitoring systems via Modbus or optionally via GSM
- Flexible installation. Universal power supply for single-phase current and three-phase current and a wide operating temperature range of -30 °C to + 60 °C
- Universal use for water supply and sewage disposal – also for pumps in potentially explosive atmospheres
- Advanced system control with individual operation and fault signal, optionally also in the event of power failure
- Additional operational safety thanks to separate level recording for high water and dry-running protection
Equipment/function
Functions
- Two different operating modes for a broad field of application:
- "Drain" operating mode: For draining sewage chambers
- "Fill" operating mode: For filling water tanks and rainwater storage tanks
- Configurable overload protection
- Thermal motor monitoring
- Pump kick function
- Adjustable follow-up time
- Automatic pump alteration (for switchgear for 2 or 3 pumps)
- Service life optimisation (for switchgear for 2 or 3 pumps)
- Standby pump (for switchgear for 2 or 3 pumps)
- Automatic fault-actuated switchover (for switchgear for 2 or 3 pumps)
- Direction of rotation monitoring
- High water alarm with forced switch-on of the connected pump(s)
- Dry-running protection
- Fault memory for 10 error messages including the type of fault
- Operating mode "Ex" for loading presets for "Ex" applications
Equipment
- Display of the current operating status and data, as well as faults via the LCD display and LEDs
- Symbol-based menu navigation
- Configuration of operating parameters and operation via operating button
- Main switch (depending on version)
- Remote access via ModBus
- Integrated alarm buzzer
- Explosion-proof version for direct connection of sensors within potentially explosive atmospheres
Type key
Example: | Wilo-Control EC-L 1x12A-T34-DOL-WM-EMS-IPS |
Control | Switchgear |
EC | Easy control series |
L | “Lift” version for water lifting applications |
1 | Number of pumps that can be connected |
12 A | Maximum rated current per pump |
T34 | Mains connection: M = 1~220–230 V, 50/60 Hz T4 = 3~380–400 V, 50/60 Hz 34 = live wire voltage, e.g. 380–400 V |
DOL | Starting mode: Direct activation |
WM | Installation type: Wall installation |
EMS | Without main switch |
IPS | Internal pressure sensor for direct connection of an immersion bell |
Technical data
- Mains connection: 1~220-230 V, 50/60 Hz or 3~380-400 V, 50/60 Hz
- Max. rated power (P2) per pump: 4 kW
- Maximum rated current IN per pump: 12 A
- Activation type of connected pumps: Direct
- Control voltage: 24 V DC
- Ambient/operating temperature: -30…+50 °C
- Storage temperature: -30…+60 °C
- Max. relative humidity: 90 %, non-condensing
- Housing material: Polycarbonate, UV-resistant
- Protection class: IP54
- Electrical safety: Pollution degree II
Description/construction
Microcontroller-controlled switchgear for level-dependent control of two or three submersible pumps with analogue or digital signal transmitters. Individual parameters are entered via symbol-based menu navigation and an operating button.
Inputs
- 1x analogue precision input 4 – 20 mA for level control with level sensor to control 1 to 3 pumps
- 2x (for 1 pump) or 3x (for 2 pumps) digital inputs for level control with float switch
- 1x digital input for low water level with float switch (dry-running protection)
- 1x digital input for high water signal with float switch (high water alarm)
- 1x input for level control with an immersion bell (“IPS” version only)
- 1x ... 3x inputs* for thermal winding monitoring with bimetallic temperature sensor. Connection of PTC sensors is not possible!
- 1x ... 3x inputs* for connecting moisture sensors (e.g. motor compartment leakage or sealing chamber monitoring)
- 1x digital input for External On/Off for remote activation and deactivation of automatic mode
Outputs
- 1x potential-free contact for the collective run signal (SBM)
- 1x potential-free contact for the collective fault signal (SSM)
- 1x potential-free contact for the individual run signal (EBM) per pump
- 1x potential-free contact for the individual fault signal (ESM) per pump
- 1x analogue output 0-10 V for the output of the actual level value
*Depending on the number of pumps that can be connected.