Wilo-CronoLine-IL-E
Your advantages
- Energy savings due to integrated electronic power adjustment
- Optional interfaces for bus communication using plug-in IF-Modules
- Simple operation with Green Button Technology and display
- Integrated dual pump management
- Integrated full motor protection (PTC thermistor sensor) with trip electronics
Recommended services
Environmentally friendly properties
- Use of IE4 motor technology and hydraulics with an MEI ≥ 0.4 saves energy
- Sustainable and carbon-neutral production and processes in our European factories
Design
Electronically controlled glanded single pump in in-line design with flange connection and automatic power adjustment
Application
The pumping of heating water (in accordance with VDI 2035), chilled water and water-glycol mixtures without abrasive substances in heating, chilled water and cooling systems.
Equipment/function
Operating modes
- Δp-c for constant differential pressure
- Δp-v for variable differential pressure
- PID-Control
- Constant speed (n=constant)
Manual operation level
- Green button and display
Manual functions
- Differential pressure setpoint setting
- Setting the speed (manual control mode)
- Setting the operating mode
- Setting the pump ON/OFF
- Configuration of all operating parameters
- Fault acknowledgement
External control functions
- "Overriding Off" control input
- “External pump cycling” control input (only effective in twin-head pump operation)
- Analogue input 0 – 10 V, 0 – 20 mA for constant speed (DDC) and remote setpoint adjustment
- Analogue input 2 – 10 V, 4 – 20 mA for constant speed (DDC) and remote setpoint adjustment
- Analogue input 0 – 10 V for actual value signal from pressure sensor
- Analogue input 2 – 10 V, 0 – 20 mA, 4 – 20 mA for actual value signal from pressure sensor
Signal and display functions
- Collective fault signal SSM
- Collective run signal SBM
Data exchange
- Infrared interface for wireless data exchange with IR-Stick
- Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation
Safety functions
- Full motor protection with integrated trip electronics
- Access disable
Dual pump management (twin-head pump or 2 x single pumps)
- Main/standby operation (automatic fault-actuated switchover)
- Pump cycling main/standby operation after 24 hours
- Parallel operation
- Parallel operation (efficiency-optimised peak-load activation and deactivation)
Typekey
Example | IL-E 50/190-11/2-R1 |
IL-E | In-line pump with electronic control |
50 | Nominal diameter DN of the pipe connection |
190 | Nominal impeller diameter |
11 | Rated power P2 in kW |
2 | Number of poles |
R1 | Version without pressure sensor |
Technical data
- Permissible temperature range of -20 °C to +140 °C
- Mechanical seal for pumping water up to Tmax = +140 °C. Up to T ≤ +40 °C, a glycol admixture of 20 % to 40 % by volume is permissible. An alternative mechanical seal must be provided for water-glycol mixtures with a glycol content of > 40% to max. 50% by volume and a fluid temperature of > +40 °C to max. +120 °C or other fluids that differ from water. When using water-glycol mixtures, the use of an S1 variant with a corresponding mechanical seal is generally recommended.
- Mains connection
- 3~440 V ±10 %, 50/60 Hz
- 3~400 V ±10%, 50/60 Hz
- 3~380 V -5% +10%, 50/60 Hz
- Compliance with electromagnetic compatibility without additional measures:
- Interference emission for residential environment according to EN 61800-3:2018
- Interference immunity for industrial environments according to EN 61800-3:2018
- Protection class IP55
- Nominal diameter DN 40 to DN 200
- Max. operating pressure 16 bar up to +120 °C, 13 bar up to +140 °C
Materials
- Pump housing and lantern: EN-GJL-250
- Impeller
- Standard version: EN-GJL-200
- Special version: Bronze CuSn 10
- Special version: Stainless steel 1.4408
- Shaft: 1.4122
- Mechanical seal: AQEGG; other mechanical seals on request
Construction
Single-stage, low-pressure centrifugal pump in in-line design with
- Mechanical seal
- Flange connection
- Lantern
- Coupling
- Drive with integrated electronic speed control
Scope of delivery
- Pump
- Installation and operating instructions
Options
- …-R1 variant without differential pressure sensor
- …-L1 variant with bronze impeller (at additional charge)
- …-L4 variant with stainless steel impeller (at additional charge)
Accessories
- 3 Mounting brackets with fixation material for installation on a base
- Wilo-IR-Stick
- IF-Module PLR for connecting to PLR/interface converter
- IF-Module LON for connection to the LONWORKS network
- IF-Module BACnet
- IF-Module Modbus
- CAN IF-Module
- VR-HVAC control system
- Control system CCe-HVAC
- Control system SCe-HVAC
- Differential pressure sensor (DDG)