Wilo-Comfort-N-Vario COR-1 MVISE...-GE

Series description

Special features/product advantages

  • Virtually noiseless system due to glandless stainless steel high-pressure multistage centrifugal pumps with integrated frequency converter
  • Up to 20 dB[A] quieter than conventional systems with comparable hydraulic output
  • Easily adjustable and operationally reliable due to the MVISE pump series used with integrated dry-running detection and automatic cut-out in event of low water

Design type

Water-supply units with a non-self-priming glandless high-pressure multistage centrifugal pump and integrated speed control

Application

  • Fully automatic water supply and pressure boosting in residential, commercial and public buildings, hotels, hospitals, department stores and for industrial systems.
  • Pumping of drinking water and process water, cooling water, fire water (apart from fire-extinguishing systems in accordance with DIN 14462 and with the approval of the local fire safety authorities) or other types of industrial water that do not attack the materials either chemically or mechanically and do not contain abrasive or long-fibre constituents.

Equipment/function

  • 1 MVISE series pump with glandless pump motor and infinitely variable control mode via integrated frequency converter
  • All components in contact with fluid are corrosion resistant
  • Base frame made of galvanised 1.4301 stainless steel, with height-adjustable vibration absorbers for insulation against structure-borne noise
  • Check valve, on the pressure side
  • Non-return valve, pressure side
  • Diaphragm pressure vessel 8 l, PN16

Scope of delivery

  • Factory-mounted, connection-ready pressure boosting system checked for functionality and impermeability
  • Packaging
  • Installation and operating instructions

Type key

Example:

Wilo-COR-1 MVISE 206/GE

CO

Compact pressure boosting system

R

Control by frequency converter

1

With one pump

MVISE

Pump series

2

Rated volume flow of the single pump [m3/h]

06

Number of single-pump stages

GE

Basic unit; i.e. without additional control device

Technical data

  • Mains connection 3~400 V, 50 Hz
  • Fluid temperature max. 50 °C
  • Operating pressure 16 bar
  • Inlet pressure 6 bar
  • Nominal connection diameters Rp 1¼ - Rp 1½
  • Protection class IP 44

Materials

  • Foot 1.4301 stainless steel
  • Impellers 1.4301 stainless steel
  • Stage chambers 1.4301 stainless steel
  • Pressure shroud 1.4301 stainless steel
  • Shaft 1.4122 stainless steel
  • Bearing/mechanical seal made of carbon, resin-impregnated
  • Pipework made of 1.4571 stainless steel

Description/construction

  • Base frame: Stainless steel with height-adjustable vibration absorbers for comprehensive insulation against structure-borne noise
  • Pipework: complete pressure-side pipework made of stainless steel, suitable for the connection of all piping materials used in building services; the pipework is dimensioned according to the overall hydraulic performance of the pressure boosting system
  • Pumps: 1 pump from the MVISE 2.., 4.., 8.. series is used; the adapted frequency converter on the pump motor enables continuous auto control for all pumps of these series; all pump components in contact with fluid are made of stainless steel
  • Valves: the pump is fitted on the pressure side with a check valve with DVGW approval mark and a DVGW-approved non-return valve
  • Diaphragm pressure vessel: 8 l/PN 16 located on the discharge side with a butyl rubber diaphragm, completely safe in accordance with food safety laws; for testing and inspection purposes, with shut-off ball cock, with drain and throughflow fitting according to DIN 4807

Duty chart

Comfort-N-Vario COR

Downloads

General overview 2018 International version

Article Number 2200591
Edition 2018
Version number 1
Page format 209.9 x 297.0 mm
Number of pages 72

PDF (11 MB)

Download

Product

PDF: Wilo-Comfort-N-Vario COR-1 MVISE...-GE

Configure

Page selection

Format selection

Optional information

You can enter any personal information that you want to be displayed in the header.

Download