EC-L-2x12A-MT34-DOL-WM-EX
Article number : 2553571
EUR 3,225.-
Price (excl. VAT)
Price group : PG14
Technical data | |
---|---|
Phases | 1 |
Rated voltage U | 230, 380/400 V |
Mains frequency f | 50 Hz |
Min. rated current I | 1 A |
Max. rated current per pump I | 12 A |
Activation type | Direct On Line (DOL) |
Control | Without frequency converter |
Protection class | IP54 |
Max. number of controllable pumps | 2 |
Materials | |
---|---|
Material | Steel |
Control EC-L1 ..., EC-L2 ..., EC-WP1 ..., EC-WP2 ...
Prices | |
---|---|
Price (excl. VAT) | EUR 3,225.- |
Price group | PG14 |
Product data | |
---|---|
Brand | Wilo |
Product description | EC-L-2x12A-MT34-DOL-WM-EX |
Article number | 2553571 |
EAN number | 4062679050850 |
Colour | grey |
Minimum order quantity | 1 |
Date of sales availability | 2020-11-02 |
Packaging | |
---|---|
Packaging type | Cardboard box |
Packaging property | Transport packaging |
Pieces per pallet | 1 |
Number per layer | 1 |
Dimension, weight | |
---|---|
Length with packaging | 340 mm |
Length L | 210 mm |
Height with packaging | 690 mm |
Height H | 600 mm |
Width with packaging | 670 mm |
Width W | 600 mm |
Gross weight, approx. m | 32 kg |
Net weight, approx. m | 30 kg |
Switchgear with microcontroller for level-dependent control of two submersible pumps with analogue or digital signal transmitters. Individual parameters are entered via symbol-based menu navigation and an operating knob.
Functions
- Two different operating modes for a broad field of application:
- “Drain” operating mode: For draining sewage chambers
- “Fill” operating mode: For filling water tanks and rainwater storage tanks
- Configurable overload protection
- Thermal motor monitoring
- Pump kick function
- Adjustable follow-up time
- Automatic pump alteration
- Service life optimisation
- Standby pump
- Automatic fault-actuated switchover
- Direction of rotation monitoring
- High water alarm with forced switch-on of the connected pumps
- Dry-running protection
- Fault memory for 10 error messages including the type of fault
- Operating mode “Ex” for loading preset values for “Ex” applications (please note information given under “Configuration”!)
Equipment
- Display of the current operating status and data as well as faults, using the LCD display and LEDs
- Symbol-based menu navigation
- Main switch
- Configuration of operating parameters and operation via operating knob
- Remote access via ModBus
- Integrated alarm buzzer
Inputs
- 1x analogue precision input 4 – 20 mA for level control with level sensor
- 3x digital inputs for level control with float switch
- 1x digital input for low water level with float switch (dry-running protection)
- 1x digital input for high water signal with float switch (high water alarm)
- 2x inputs for thermal winding protection monitoring with bimetallic temperature sensor - connection of PTC sensors is not possible!
- 2x inputs for connecting moisture sensors (e.g.: Motor compartment leakage or sealing chamber monitoring)
- 1x digital input for External On/Off for remote activation and deactivation of automatic mode
Outputs
- 1x potential-free contact* for the collective run signal (SBM)
- 1x potential-free contact* for the collective fault signal (SSM)
- 1x potential-free contact* for the individual run signal (EBM) per pump
- 1x potential-free contact* for the individual fault signal (ESM) per pump
- 1x 24 VDC output for connecting an external alarm signal
- 1x analogue output 0-10 V for the output of the actual level value
*NOTICE: Power supply must be provided by the customer!
Configuration
- Signal transmitter to be provided on-site.
- Switchgears are not protected against explosions and may only be used outside hazardous areas.
- Pumps and signal transmitters within hazardous areas can be directly connected.
Notice! Printed installation and operating instructions have been enclosed with the product in the following languages: DE, EN, FR, PL, RU. All language versions have been saved as PDF files on an enclosed USB stick or can be downloaded at https://qr.wilo.com/1401. A notebook or tablet with Adobe Reader is required for installing and commissioning.
Technical data | |
---|---|
Max. number of controllable pumps | 2 |
Phases |
|
Rated voltage U | 230, 380/400 V |
Mains frequency f |
|
Min. rated current I | 1 A |
Max. rated current per pump I | 12 A |
Activation type | Direct On Line (DOL) |
Protection class | IP54 |
Length L | 210 mm |
Width W | 600 mm |
Height H | 600 mm |
Net weight, approx. | 30 kg |
Make | Wilo |
Item no. | 2553571 |
Installation and operating instructions
Installation and operating instructions (digital)
Wilo-Control EC-L
Article Number | 2543252 |
Edition | 2022-09 |
Language | bg, cs, da, de, el, en, es, et, fi, fr, hr, hu, it, lt, lv, mk, nl, no, pl, pt, ro, ru, sk, sl, sr, sv, tr, uk, zh |