Sinum Double Pump Unit D130 400V
Data sheet
Technical data
-
Rated current IN15.6 A
-
Rated power P28.0 W
-
Protection classIP54
-
InterfaceRS485 (TIA-485A), optically insulated
-
Connection inputG 1½
-
Connection outputG 1½
-
Tank connectionG1½-PN10-DIN-ISO228-1
-
Max. refill pressure6 bar
-
Min. refill pressure4 bar
-
Min. boiler output3300 kW
-
Max. boiler output10000 kW
-
Break tank volume V130 l
-
Maximum allowed limit of glycol in %50 %
Operating data
-
Min. operating pressure8 bar
-
Max. operating pressure PN14 bar
-
Min. storage temperature5 °C
-
Max. storage temperature50 °C
-
Min. fluid temperature3 °C
-
Max. fluid temperature70 °C
-
Min. ambient temperature3 °C
-
Max. ambient temperature50 °C
Information for order placements
-
Net weight, approx.153.00 kg
-
MakeWilo
-
Item no.2198873
-
InstallationHorizontal
Tender text
For pressurisation, deaeration and topping up in sealed heating installations (acc. to EN12828) and chilled water (cooling) installations.
Sinums with pump units are used for storage of expansion water, deaeration and topping up your installation automatically as an integrated controlled unit carried out with state of the art micro-electronics. The Sinum balanced pressure expansion equipment is sized according to the total system volume and the boiler or chiller load. The Sinum vessel is 80% efficient irrespective of the static height of the system. It is the ideal solution for large installations or high installations where standard
diaphragm expansion equipment is limited.
Special features/Product advantages
- Easy installation thanks to intuitive menu navigation in the HMI, large display and self-learning microprocessor.
- Different operating modes guarantee continuous degassing.
- Advanced technology ensures low power consumption, long service life and easy maintenance.
- Improved convenience through volumetric controls and automatic topping-up during the heating and cooling cycles.
- Modular design offers a high level of installation flexibility.
- Optional: Integration in existing building management systems through digital and analogue outputs.
Technical data
-
Break tank volume V130 l
-
InstallationHorizontal
-
Connectableyes
-
Digital control unityes
-
Exchangeable membraneno
-
Min. operating pressure8 bar
-
Max. operating pressure PN14 bar
-
Min. refill pressure4 bar
-
Max. refill pressure6 bar
-
Min. fluid temperature T3 °C
-
Max. fluid temperature T70 °C
-
Min. ambient temperature3 °C
-
Max. ambient temperature50 °C
-
Min. storage temperature5 °C
-
Max. storage temperature50 °C
-
Maximum allowed limit of glycol in %50 %
-
Mains frequency f50 Hz
-
Phase3
-
Rated voltage U400 V
-
Voltage tolerance±10 %
-
Rated current IN15.6 A
-
Protection classIP54
-
Max. boiler output10000 kW
-
Min. boiler output3300 kW
-
Connection inletG 1½
-
Connection outletG 1½
-
Item no.2198873
-
EAN number4048482837901
-
MakeWilo
-
Net weight, approx.153.00 kg
Ordering information
Information for order placements
-
BrandWilo
-
Product descriptionSinum Double Pump Unit D130 400V
-
EAN number4048482837901
-
Article number2198873
-
Gross weight, approx. m188.0 kg
-
Net weight, approx. m153 kg
-
Overall length L540.0 mm
-
Height without packaging H1190 mm
-
ColourWhite
-
Packaging propertyTransport packaging
-
Packaging typeEuropallet
-
Number per layer1
-
Width without packaging B530.0 mm
-
Minimum order quantity1
-
Pieces per pallet1
-
Date of sales availability2018-04-09
-
Date of introduction2018-04-09