Search
Contact
E-mail
Catalogue creation
My favorites
Product comparison
Wilo-SiFire Easy | Wilo
Your advantages
Wilo-SiFire Easy

Your advantages

  • Pressure-loss optimised system designed in accordance with the EN 12845 standard with electrical or diesel drive, jockey pump for maintaining system pressure
  • Flexible, modular and solid construction for safe transport and simple installation
  • Bypass volume flow for the protection of the pump with spacer coupling for simple maintenance
  • Optimum regulation and ease of use via EC-Fire control with direct display of the current operating status
  • Special baseplate for minimal vibrations, cable laid in the construction in such a way as to ensure maximum reliability and service life

Series description
Wilo-SiFire Easy

Design

Pressure-boosting systems for firefighting according to EN 12845. Consists of 1 or 2 pumps, depending on the module, with horizontal baseplate - EN 733 - with spacer coupling, electric or diesel motor and a multistage, vertical electric jockey pump.

Application

Fully automatic water supply for fire-fighting systems with sprinklers in domestic, commercial and public buildings, hotels, hospitals, shopping centres and industrial buildings.

Equipment/function

  • 1 or 2 pumps with horizontal base frame of series 32-200 to 100-250, with IE-equivalent standard motor or diesel motor
  • With a diaphragm installed directly on the main pump housing to prevent overheating in the event of zero flow
  • Jockey pump of series MVIL-1 or MVI-1with pressure switch and vertical pressure vessel 20 l, PN16
  • One switch cabinet per pump, fixed to a robust support structure. EC Fire model: E for the electric motor and D for the diesel motor, both equipped with Easy Controller, plus J for the jockey pump
  • Base plate made of electro-galvanised steel with height-adjustable holder for the outlet manifold
  • Pipework made of steel; painted with epoxy resin. Manifold with flanges
  • Shutting gate with safety lock on the discharge side of each pump
  • Non-return valve on the discharge side of each pump
  • A circuit with dual pressure switch, pressure gauge, non-return valve, valve for the main pump and standby pump for automatic start
  • Concentric cone on the discharge side of the main and standby pump, for speed limitation according to the parameters specified in EN 12845
  • DN2" connection for the supply tank of the pumps
  • Pressure measurement on the discharge side
  • Only for the model with diesel motor:
    • Vibration damping sleeve on the discharge side of the pump
    • Vibration damper under the base plate of the pump
    • Fuel tank with level sensor and sufficient volume for six hours of autonomous operation
    • Two batteries on the base frame and battery charger in the EC-Fire switchgear
  • Accessories on request:Note on fluids: Approved fluids are generally waters which do not attack the materials used, neither chemically nor mechanically, and do not contain any abrasive or long-fibre constituents. System in accordance with EN 12845
    • Horizontal 500 l supply tank, with float valve and pressure switch for LL-alarm (water shortage)
    • Flow meter: Kit with eccentric cone on the suction side, complete with check valve with hand lever or handwheel
    • Vacuum gauge with valve
    • Valves with electrical contact
    • Vibration damping sleeve for the manifold
    • Remote control panel for transmitting level A and level B alarms
    • Density meter for the battery
    • Spare parts kit for the diesel motor
    • Silencer (30 dBA) for the diesel motor
    • Hydraulic heat exchanger for the diesel motor

Typekey

Example:

Wilo-SiFire Easy 40/200-180-7.5/10.5 EDJ

SiFire

Compact pressure boosting system for fire fighting equipment

Easy

Easy handling and in accordance with standard EN 12845

40/200

Type of main pump

180

Actual impeller diameter of the main pump

7.5

Power of the electric motor [kW]

10.5

Power of the diesel motor [kW]

EDJ

Configuration

E

One electric pump

D

A diesel pump

J

A jockey pump

Technical data

  • Mains connection 3~400 V, 50 Hz (1~230 V, 50 Hz for the control panel of the diesel pump)
  • IE equivalent standard motors, diesel motor with direct injection or turbo diesel motor with air or water cooling
  • Max. ambient temperature +4 °C to +40 °C (+10 °C to +40 °C, if a diesel pump is installed)
  • Max. fluid temperature +25 °C
  • Max. operating pressure 10 or 16 bar
  • Max. inlet pressure 6 bar
  • Volume flow 10 m³/h to 750 m³/h
  • Max. delivery head 128m
  • Nominal connection diameters on the discharge side DN 65 to DN 250
  • Nominal connection diameters on the intake side DN 50 to DN 200
  • Switch cabinet protection class IP54
  • Main/standby pump with horizontal base frame in accordance with EN 733
  • With epoxy resin painted piping and hydraulic connections
  • Permissible fluids: Note on fluids: Approved fluids are generally waters which do not attack the materials used, neither chemically nor mechanically, and do not contain any abrasive or long-fibre constituents. System in accordance with EN 12845
    • Non-aggressive, clean water
    • Firefighting water

Materials

For the pump with horizontal base frame

  • Impellers made of stainless steel AISI 316/ 1.4401
  • Pump housing made of grey cast iron EN-GJL-250
  • Shaft made of stainless steel AISI 431/ 1.4057
  • Wear rings made of bronze

For the jockey pump

  • Impellers made of stainless steel AISI 304/ 1.4301
  • Pump housing made of grey cast iron EN-GJL-250 (stainless steel AISI304/1.4301 for MVI)
  • Shaft made of stainless steel AISI 304/ 1.4301
  • O-ring seals made of EPDM

Construction

  • Base frame: Manufactured from profiles consisting of electro-galvanised steel with brackets for the switch cabinets and the outlet manifold. Special square holes at the bottom for forklift trucks, as well as integrated hooks for lifting slings. Side profiles at the top on each side to enhance the rigidity of the system when moving and lifting.
  • Plastic cover at the rear which provides visual access to the valve position and pressure gauge.
  • Pipework: Complete pipework with flanges made of epoxy resin painted steel, suitable for the connection of all common piping materials; the dimensions of the pipework must correspond to the overall hydraulic performance of the pressure boosting system
  • Pumps: 1 or 2 pumps with horizontal base frame - EN 733 - with spacer coupling, electric or diesel motor.
  • • Back-pull-out model to ensure the internal parts of the pump are easy to access without having to move the motor or piping.
  • Valves: The main pumps are fitted with a shut-off valve and non-return valve on the discharge side, both of which are painted with epoxy resin and adapted for a flange connection.
  • Diaphragm pressure vessel: Diaphragm pressure vessel 20 l/PN16, on the discharge side of the jockey pump, with drain plug.
  • Tank: The fuel tank is made of metal painted with epoxy resin and is located behind the bracket of the switch cabinet
  • Sensors and display: 2 pressure switches, 2/16 bar per pump, on the discharge side, for activating the pump start via the EC-Fire controller and regulator. The discharge side pressure gauge (∅ 63 mm) is located in the middle of the rear panel.
  • Controller: The system is equipped as standard with a separate switchgear/control device (EC Fire) for the electric or diesel motor and a switchgear/control device for the jockey pump.

Scope of delivery

  • Factory-mounted, ready-for-installation pressure-boosting system, which has been checked for functionality and impermeability
  • Installation and operating instructions
  • Required accessories on request
Documents

Installation and operating instructions

Wilo-SiFire Easy

Article Number 4206362
Edition 1801
Number of pages 116
PDF (8 MB)

Wilo-Priming tank 500 L

Article Number 4228982
Edition 2019-05
Number of pages 451
PDF (18 MB)

Wilo-SiFire Easy

Article Number 4206363
Edition 2019-12
Number of pages 116
PDF (4 MB)

General overview

General Overview 2024 - International version

Edition 2022
Number of pages 74
PDF (33 MB)
Product selection
Number of results: 468
29 … 756 m³/h
[468]
Product descriptionSystem output without standby pump QMaximum operating pressure PNGross weight, approx. mArticle number
SiFire-Easy-32/200-154-4,2D
29 m³/h
16 bar
570 kg
4242131
SiFire-Easy-32/200-154-4,2DJ
29 m³/h
16 bar
614 kg
4242206
SiFire-Easy-32/200-154-4/4,2EDJ
29 m³/h
16 bar
808 kg
4242331
SiFire-Easy-32/200-154-4/4EEJ
29 m³/h
16 bar
743 kg
4242281
SiFire-Easy-32/200-154-4E
29 m³/h
16 bar
475 kg
4241981
SiFire-Easy-32/200-154-4EJ
29 m³/h
16 bar
505 kg
4242056
SiFire-Easy-32/200-172-5,5/5,5EEJ
34 m³/h
16 bar
787 kg
4242282
SiFire-Easy-32/200-172-5,5/6,8EDJ
34 m³/h
16 bar
845 kg
4242332
SiFire-Easy-32/200-172-5,5E
34 m³/h
16 bar
497 kg
4241982
SiFire-Easy-32/200-172-5,5EJ
34 m³/h
16 bar
527 kg
4242057
SiFire-Easy-32/200-172-6,8D
34 m³/h
16 bar
585 kg
4242132
SiFire-Easy-32/200-172-6,8DJ
34 m³/h
16 bar
629 kg
4242207
SiFire-Easy-32/200-182-6,8D
36 m³/h
16 bar
585 kg
4242133
SiFire-Easy-32/200-182-6,8DJ
36 m³/h
16 bar
629 kg
4242208
SiFire-Easy-32/200-182-7,5/6,8EDJ
36 m³/h
16 bar
861 kg
4242333
SiFire-Easy-32/200-182-7,5/7,5EEJ
36 m³/h
16 bar
811 kg
4242283
SiFire-Easy-32/200-182-7,5E
36 m³/h
16 bar
500 kg
4241983
SiFire-Easy-32/200-182-7,5EJ
36 m³/h
16 bar
530 kg
4242058
SiFire-Easy-32/200-191-7,5/7,5EEJ
37 m³/h
16 bar
811 kg
4242284
SiFire-Easy-32/200-191-7,5/10,5EDJ
37 m³/h
16 bar
891 kg
4242334
SiFire-Easy-32/200-191-7,5E
37 m³/h
16 bar
500 kg
4241984
SiFire-Easy-32/200-191-7,5EJ
37 m³/h
16 bar
530 kg
4242059
SiFire-Easy-32/200-191-10,5D
37 m³/h
16 bar
615 kg
4242134
SiFire-Easy-32/200-191-10,5DJ
37 m³/h
16 bar
659 kg
4242209
SiFire-Easy-32/200-200-10,5D
39 m³/h
16 bar
675 kg
4242135
SiFire-Easy-32/200-200-10,5DJ
39 m³/h
16 bar
719 kg
4242210
SiFire-Easy-32/200-200-11/10,5EDJ
39 m³/h
16 bar
891 kg
4242335
SiFire-Easy-32/200-200-11/11EEJ
39 m³/h
16 bar
811 kg
4242285
SiFire-Easy-32/200-200-11E
39 m³/h
16 bar
582 kg
4241985
SiFire-Easy-32/200-200-11EJ
39 m³/h
16 bar
612 kg
4242060
SiFire-Easy-32/250-198-6,8D
31 m³/h
16 bar
675 kg
4242136
SiFire-Easy-32/250-198-6,8DJ
31 m³/h
16 bar
719 kg
4242211
SiFire-Easy-32/250-198-7,5/6,8EDJ
31 m³/h
16 bar
1024 kg
4242336
SiFire-Easy-32/250-198-7,5/7,5EEJ
31 m³/h
16 bar
936 kg
4242286
SiFire-Easy-32/250-198-7,5E
31 m³/h
16 bar
594 kg
4241986
SiFire-Easy-32/250-198-7,5EJ
31 m³/h
16 bar
624 kg
4242061
SiFire-Easy-32/250-222-10,5D
34 m³/h
16 bar
730 kg
4242137
SiFire-Easy-32/250-222-10,5DJ
34 m³/h
16 bar
774 kg
4242212
SiFire-Easy-32/250-222-11/10,5EDJ
34 m³/h
16 bar
1091 kg
4242337
SiFire-Easy-32/250-222-11/11EEJ
34 m³/h
16 bar
960 kg
4242287
SiFire-Easy-32/250-222-11E
34 m³/h
16 bar
594 kg
4241987
SiFire-Easy-32/250-222-11EJ
34 m³/h
16 bar
624 kg
4242062
SiFire-Easy-32/250-234-12,9D
35 m³/h
16 bar
730 kg
4242138
SiFire-Easy-32/250-234-12,9DJ
35 m³/h
16 bar
774 kg
4242213
SiFire-Easy-32/250-234-15/12,9EDJ
35 m³/h
16 bar
1131 kg
4242338
SiFire-Easy-32/250-234-15/15EEJ
35 m³/h
16 bar
1040 kg
4242288
SiFire-Easy-32/250-234-15E
35 m³/h
16 bar
634 kg
4241988
SiFire-Easy-32/250-234-15EJ
35 m³/h
16 bar
664 kg
4242063
SiFire-Easy-32/250-246-15/15EEJ
37 m³/h
16 bar
1040 kg
4242289
SiFire-Easy-32/250-246-15/17,7EDJ
37 m³/h
16 bar
1343 kg
4242339